2021-10-16 10:49:30PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 3RD REVIEW - FREE STANDING 2-CAR GARAGE
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE #1:
 PROVISO ON SITE PLAN A0.0: SEPERATE PERMIT REQUIRED FOR
 SITE WALLS.
  
 NOTICE #2:
 PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD AREA
 (SFHA). IT IS LOCATED IN ZONE AE WITH A BASE FLOOD
 ELEVATION OF 6.0 FEET NAVD. DESIGN FLOOD ELEVATIN SHALL
 BE 8.0' NAVD OR HIGHER.
 PROPOSED TOP OF SLAB IS 6.56' NAVD. FLOOD OPENINGS ARE
 REQUIRED PER R322.
  
  
 NOTICE #3:
 PROVIDE AN ELEVATION CERTIFICATE WITH AN ACCURATELY
 COMPLETED BOUNDY LINE SURVEY FOR THE FREE STANDING
 2-CAR GARAGE.
  
 3 EC S REQUIRED:
  
 A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS
 REQUIRED AT TIME OF PERMIT APPLICATION.
  
 A BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AT PLACEMENT OF 1ST FLOOR.
  
 A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL
 PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY.
 NOTE: YOU MAY SUBMIT THIS EC FOR REVIEW AFTER FINAL
 GRADE AND PLACEMENT OF EQUIPMENT SERVICING THE
 BUILDING.
  
 COMMENTS:
  
 1. PROVIDE A CURRENT FLORIDA PRODUCT APPROVAL OR THE
 ICC-ES REPORT FOR THE PROPOSED ENGINEERED FLOOD VENTS
 MODEL 1540-521.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 2. FLOOD OPENINGS SHALL BE INSTALLED PER R322.2.2.
 R322.2.2.1INSTALLATION OF OPENINGS.
 THE WALLS OF ENCLOSED AREAS SHALL HAVE OPENINGS
 INSTALLED SUCH THAT:
 1. FLOOD OPENINGS SHALL BE INSTALLED ON ADJACENT SIDES
 OF EACH ENCLOSED AREA; IF A BUILDING HAS MORE THAN ONE
 ENCLOSED AREA BELOW THE DESIGN FLOOD ELEVATION, EACH
 AREA SHALL HAVE OPENINGS.
 2. THE BOTTOM OF EACH OPENING SHALL BE NOT MORE THAN 1
 FOOT (305 MM) ABOVE THE HIGHER OF THE FINAL INTERIOR
 GRADE OR FLOOR AND THE FINISHED EXTERIOR GRADE
 IMMEDIATELY UNDER EACH OPENING.
 3. OPENINGS SHALL BE PERMITTED TO BE INSTALLED IN DOORS
 AND WINDOWS; DOORS AND WINDOWS WITHOUT INSTALLED
 OPENINGS DO NOT MEET THE REQUIREMENTS OF THIS SECTION.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  