2021-09-09 12:23:02 | PLAN REVIEW / NFIP |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER BUILDING - PX3169 |
| PLANS EXAMINER 1&2 FAMILY - SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| 2017 NEC |
| CITY ORDINANCE NO. 4658-16 |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| |
| NOTICE: |
| |
| PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD AREA |
| (SFHA). IT IS LOCATED IN ZONE AE WITH A BASE FLOOD |
| ELEVATION OF 6.0 FEET NAVD. BASED ON THE VALUE OF THIS |
| SUBMITTAL, THE WORK ON THE PROPERTY IS CONSIDERED A |
| SUBSTANTIAL IMPROVEMENT (S/I) PER FEMA P-758. |
| |
| 2020 FBC EXISTING BUILDING |
| 1201.3FLOOD HAZARD AREAS. |
| IN FLOOD HAZARD AREAS, IF ALL PROPOSED WORK, INCLUDING |
| REPAIRS, WORK REQUIRED BECAUSE OF A CHANGE OF |
| OCCUPANCY, AND ALTERATIONS, CONSTITUTES SUBSTANTIAL |
| IMPROVEMENT, THEN THE BUILDING SHALL COMPLY WITH |
| SECTION 1612 OF THE FLORIDA BUILDING CODE, BUILDING, OR |
| SECTION R322 OF THE FLORIDA BUILDING CODE, RESIDENTIAL, |
| AS APPLICABLE. |
| |
| CITY ORDINANCE NO. 4658-16 |
| |
| CITY OF WEST PALM BEACH ORDINANCE NO. 4658-16 |
| AS OF OCTOBER 5, 2017, THE FEDERAL EMERGENCY MANAGEMENT |
| AGENCY (FEMA) ESTABLISHED A NEW FLOOD INSURANCE RATE |
| MAP (FIRM) UTILIZING THE RECENTLY COMPLETED FLOOD |
| HAZARD DETERMINATION (FHD) FOR THE CITY OF WEST PALM |
| BEACH, FL. |
| |
| ALL NEW BASE FLOOD ELEVATIONS (BFE) SHALL BE BASED ON |
| NAVD88 DATUM. ON AUGUST 23, 2017, THE CITY OF WEST PALM |
| BEACH, BY ORDINANCE, NO. 4658-16, ESTABLISHED A |
| TWO-FOOT FREEBOARD ABOVE THE (BFE). |
| FINISHED FLOOR ELEVATIONS SHALL BE PLACED ON FOUNDATION |
| PLAN AND/OR FLOOR PLAN. |
| |
| 1. PROPOSED SITE PLAN SHOWS EXISTING FINISHED FLOOR AT |
| 8.82 FT NAVD AND PROPOSED ADDITION WITH FINISHED FLOORS |
| AT 8.82 FT NAVD., EXISTING ACCESSORY STRUCTURE FINISHED |
| FLOOR IS AT 7.46 FT NAVD AND FREE STANDING GARAGE |
| FINISHED FLOOR WILL BE AT 7.46 FT NAVD. |
| R322.1.5LOWEST FLOOR. |
| |
| 2. MACHINERY SERVICING BUILDINGS SHALL BE AT OR ABOVE |
| THE DFE OF 8.0 FT NAVD. |
| R322.1.6PROTECTION OF MECHANICAL, PLUMBING AND |
| ELECTRICAL SYSTEMS. |
| |
| 3. NEW 2 CAR GARAGE FINISHED FLOOR ELEVATION WILL BE |
| 7.46 FT NAVD. |
| R322.2.2ENCLOSED AREA BELOW DESIGN FLOOD ELEVATION. |
| R322.2.2.1INSTALLATION OF OPENINGS. |
| FLOOD OPENINGS REQUIRED. |
| |
| 4. ACCESSORY STRUCTURE WILL BE CONVERTED TO HABITABLE |
| SPACE. FINISHED FLOOR ELEVATION IS 7.46 FT NAVD. |
| R322.1.5LOWEST FLOOR. |
| R322.2.1ELEVATION REQUIREMENTS. |
| R322.2.2ENCLOSED AREA BELOW DESIGN FLOOD ELEVATION. |
| R322.2.2.1INSTALLATION OF OPENINGS. |
| FLOOD OPENINGS REQUIRED. |
| |
| NOTICE: PROVIDE AN ELEVATION CERTIFICATE WITH AN |
| ACCURATELY COMPLETED BOUNDY LINE SURVEY FOR MAIN |
| RESIDENCE AND FREE STANDING GARAGE. |
| |
| 3 EC S REQUIRED FOR EACH STRUCTURE |
| |
| A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS |
| REQUIRED AT TIME OF PERMIT APPLICATION. |
| |
| A BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE IS |
| REQUIRED AT PLACEMENT OF 1ST FLOOR. |
| |
| A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS |
| REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL |
| PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY. |
| NOTE: YOU MAY SUBMIT THIS EC FOR REVIEW AFTER FINAL |
| GRADE AND PLACEMENT OF EQUIPMENT SERVICING THE |
| BUILDING. |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |
| |