Date |
Text |
2021-09-08 07:37:14 | 09/08/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. ON SHEET A0.00, THE COVER SHEET FOR THE PLUMBING |
| SAYS P0.1, P1.1, AND P3.1, BUT WHEN YOU GO TO THE |
| PAGES, THERE ARE P001, P101, AND P201. WOULD YOU PLEASE |
| CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 2. ON SHEET A1.00 HAS AN OPTION TO HOVER THE KITCHEN |
| EQUIPMENT AND DOWNLOAD THE SPECIFICATION. STILL, PLEASE |
| SUBMIT THESE UNDER SUPPORTING DOC IN PDF IF POSSIBLE |
| PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 3. ON SHEET A4.00; |
| |
| A. ON DETAIL 2, WOULD YOU PLEASE PROVIDE THE DIMENSION |
| FOR THE CLEAR FLOOR SPACE FOR THE WATER CLOSET FOR |
| WOMEN'S AND MEN'S BATHROOM PER THE 2020 FBC ACC. SEC. |
| 604.3.1. |
| |
| B. ON ELEVATION B AND F FOR THE TOILET GRAB BAR SAYS 6 |
| INCHES FROM THE WALL, WHICH IS NOT AN ACTUAL NUMBER AS |
| THE TOILET IS 16 INCHES TO 18 INCHES TO THE CENTER, AND |
| THAT NUMBER MAY CONFUSE THE INSTALLER. WOULD YOU PLEASE |
| CORRECT PER THE 2020 FBC ACC SEC. 604.2 LOCATION AND |
| WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS? |
| |
| C. ON ELEVATION B AND F, THE HORIZONTAL GRAB BARS ON |
| THE REAR NEED TO BE MEASURED TO THE CENTER OF THE WATER |
| CLOSET TO 12 INCHES TO THE WALL AND 24 INCHES TO THE |
| OPEN SIDE PER THE 604.5.2 REAR WALL. |
| |
| D. ON ELEVATION B AND F, THE TOILET PAPER DISPENSERS |
| SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT |
| OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF |
| DISPENSER PER THE 2020 FBC ACC SEC. 604.7. |
| |
| E. ON ELEVATION C AND G, WOULD YOU PLEASE SHOW THE |
| TOILET TO BE 17 INCHES TO 19 INCHES MAXIMUM MEASURED TO |
| THE TOP OF THE SEAT PER THE 2020 FBC ACC SEC. 604.4 |
| SEATS. |
| |
| F. ON ELEVATION C AND G, WOULD YOU PLEASE ADD THAT |
| REFLECTIVE PART OF THE MIRROR TO BE 40 INCHES TO THE |
| REFLECTIVE SIDE PER THE 2020 FBC ACC SEC. 603.3. |
| |
| G. SEATS OF WATER CLOSETS SHALL BE OPEN-FRONT TYPE PER |
| 2020 FBC P 425.3 WATER CLOSET SEATS. |
| |
| 4. ON SHEET A6.01: |
| |
| A. IF POSSIBLE, WOULD YOU PLEASE DELETE OR |
| STRIKETHROUGH ANY ADA DETAILS NOT PERTAINING TO THIS |
| PROJECT TO MINIMIZE CONFUSION IN THE FIELD INSTALLATION |
| PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| B. ON THE SAME PAGE ON TOP FOR A, B, C, THE TOILET GRAB |
| BAR SAYS 6 INCHES FROM THE WALL, WHICH IS NOT AN ACTUAL |
| NUMBER AS THE TOILET IS 16 INCHES TO 18 INCHES TO THE |
| CENTER, AND THAT NUMBER MAY CONFUSE THE INSTALLER. |
| WOULD YOU PLEASE CORRECT PER THE 2020 FBC ACC SEC. |
| 604.2 LOCATION AND WPB AMENDMENTS TO THE FBC |
| SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| |
| 5. ON SHEET P001; |
| |
| A. WOULD YOU PLEASE PROVIDE THE MINIMUM NUMBER OF |
| FIXTURES FOR THE OCCUPANT LOAD BASED ON THE ACTUAL USE |
| OF THE BUILDING OR SPACE PER TABLE 403.1 MINIMUM NUMBER |
| OF FIXTURES. |
| |
| |
| 6. ON SHEET P101; |
| |
| A. WOULD YOU PLEASE PROVIDE A SITE PLAN SHOWING THE |
| LOCATION OF THE EXISTING GREASE INTERCEPTORS. WPB |
| AMEND. TO FBC SEC. 107.2.1. IS IT SHARED WITH OTHER |
| RESTAURANTS, AND IF SO, WHAT IS THEIR VOLUME. |
| |
| B. LAVS FOR HAND WASH AND WASTES THAT DO NOT REQUIRE |
| TREATMENT OR SEPARATION SHALL NOT BE DISCHARGED INTO |
| ANY INTERCEPTOR OR SEPARATOR PER THE 2020 FBC SEC. P |
| 1003.2 APPROVAL. THE HANDWASHING SINK AND ICEMAKER IN |
| THE KITCHEN OR BAR CAN NOT GO INTO THE INTERCEPTOR. |
| |
| C. THERE IS A PLUMBING SCHEDULE THAT DOES NOT HAVE A |
| DESCRIPTION OF EACH FIXTURE ON THIS PAGE. THERE IS A |
| GENERAL FOOD SERVICE EQUIPMENT SCHEDULE SUBMITTED. |
| WOULD YOU PLEASE PROVIDE AND INCORPORATE ON THIS PAGE |
| PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| D. WOULD YOU PLEASE PROVIDE INFORMATION ON THE |
| DISHWASHER GOING INTO THE GREASE INTERCEPTOR AS IT |
| SHALL HAVE A PRE-RINSE SINK FOR IT TO GO INTO IT PER |
| THE 2020 FBC SEC. P 1003.3.1 GREASE INTERCEPTORS. FOOD |
| WASTE DISPOSERS SHALL NOT DISCHARGE TO A GREASE |
| INTERCEPTOR PER THE 2020 FBC SEC. 1003.3.2 FOOD WASTE |
| DISPOSERS RESTRICTION. |
| |
| E. WOULD YOU PLEASE SUBMIT DETAIL OF THE DRYWELL FOR |
| THE CONDENSATE LINE PER THE WPB AMENDMENTS TO THE FBC |
| SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| F. IN THE KITCHEN AREA, THERE IS A THREE-COMPARTMENT |
| SINK. WOULD YOU PLEASE PROVIDE DETAIL ON THE DRAINS TO |
| AN INDIRECT WASTE INDEPENDENTLY FROM EACH OTHER PER THE |
| 2017 FBC SEC. P 802.1.1. |
| |
| 7. ON SHEET P301; |
| |
| A. HOT WATER LINES LOOPED FOR THE RECIRCULATING SYSTEM |
| ARE NOT IN A CONTINUOUS LOOP, AND THERE IS A |
| REQUIREMENT IN THE FLORIDA ENERGY CODE SEC. C404.6.1. |
| |
| B. THE RECIRCULATING MANIFOLD TO THE HOT WATER LINES |
| SHALL BE SUPPLIED TO THE SOURCE; PLEASE REFER TO THE |
| 2020 FBC ENERGY CODE TABLE C404.5.1. MAXIMUM ALLOWABLE |
| PIPE LENGTH METHOD. |
| |
| C. HOT WATER LINES NOT IN CONDITION SPACE OR UNDER SLAB |
| NEED TO BE INSULATED WITH A MINIMUM R-3 PER THE 2020 |
| FBC SEC. RE 403.5.3. |
| |
| D. WOULD YOU PLEASE SHOW THE RECIRCULATING PUMP ON THE |
| ISOMETRIC? THE RECALCULATING PER MANUFACTURES |
| SPECIFICATION AND MAINTENANCE MAY REQUIRE SHUT-OFF |
| VALVES ON EACH SIDE OF THE RECALCULATING PUMP PER THE |
| 2020 FBC SEC. 606.2 LOCATION OF SHUTOFF VALVES. |
| |
| E. WOULD YOU PLEASE SHOW THE THERMAL EXPANSION DEVICE |
| ON THE COLD WATER THAT PASSES THROUGH A CHECK VALVE PER |
| THE 2020 FBC SEC. P 607.3 THERMAL EXPANSION CONTROL. |
| |
| F. WOULD YOU PLEASE SHOW THE FULL OPEN SHUT-OFF VALVE |
| THAT ENTERS THE STRUCTURE PER THE 2020 FBC SEC. P 606.2 |
| LOCATION OF SHUTOFF VALVES. |
| |
| G. FIXTURES UNDER THE COFFEE MAKER/ICE MAKER REQUIRE AN |
| INLINE VACUUM BREAKER THAT COMPLIES WITH THE ASSE 1024 |
| NON-CARBONATED PER THE 2020 FBC SEC. 608.17.1.2. |
| |
| H. SODA MACHINES SHALL BE EQUIPPED WITH AN IN-LINE |
| VACUUM BREAKER THAT COMPLIES WITH ASSE 1022 PER THE |
| 2020 FBC SEC. 608.17.1.1. |
| |
| J. THERE ARE TWO CYLINDERS ON THE 1 1/4 COLD WATER |
| LINE. WOULD YOU PLEASE LABEL PER THE WPB AMENDMENTS TO |
| THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| I. THE FLOOR DRAIN IN THE KITCHEN AREA IS NOT LABELED, |
| AND THERE IS A SECOND FLOOR DRAIN SHOWN ON A1.00 IN |
| FRONT OF THE STOVE, IS THAT ADDED. WOULD YOU PLEASE |
| CORRECT AND ADD TO ISOMETRIC PER THE WPB AMENDMENTS TO |
| THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. THE BAR AREA HAS NO FLOOR DRAIN, BUT IT IS |
| NOT A CODE REQUIREMENT BUT RECOMMENDED. |
| |
| K. THE MOP SINK IS SHOWN ABOVE GROUND, AND A FLOOR |
| MODEL IS SPECKED OUT W/SPASHES. WOULD YOU PLEASE |
| INDICATE IT ON THE ISOMETRIC WITH ITS VENT PER THE WPB |
| AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. IF NOT A FLOOR MODEL, PLEASE |
| INDICATE, AND A CLEANOUT IS NOT REQUIRED IF ONE WILL BE |
| INSTALL SHOW TO THE OPPOSITE WALL IF DESIRED. |
| |
| L. THERE IS A STEAM UNIT THAT REQUIRES TWO 3/4 INCH |
| WATER LINES, ONE TREATED AND THE OTHER UNTREATED FOR |
| P5B AND NOT SHOWN. WOULD YOU PLEASE SHOW PER THE WPB |
| AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| PLEASE FEEL FREE TO SET UP A MEETING OR CONTACT ME ON |
| ANY OF THE COMMENTS BY PHONE OR ZOOM MEETING IF YOU |
| LIKE TO PREVENT FURTHER REVIEWS. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |