2021-08-23 07:16:051ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21080310
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE ADD A NOTE ON THE DRAWING STATING ALL HOODS
 WILL REQUIRE A SEPARATE PERMIT APPLICATION, DRAWINGS
 AND PLAN REVIEW. THE HOODS WILL NOT BE REVIEWED UNDER
 THIS PERMIT.
  
 2) PLEASE ADD A NOTE ON THE DRAWING STATING ALL
 REFRIGERATION WILL REQUIRE A SEPARATE PERMIT
 APPLICATION, DRAWINGS AND PLAN REVIEW. THE
 REFRIGERATION WILL NOT BE REVIEWED UNDER THIS PERMIT.
  
 3) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS BASED ON THE
 USE OF SPACE IN THIS TENANT SPACE I.E. KITCHEN, DINING,
 BAR, RECEPTION. FBC M 403.3.1.1 AND TABLE 403.3.1.1
  
 4) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBC EC C403.2.1
  
 5) SHOW LOCATION OF THE NEW OACU-1. FBC 107.2.1
  
 6) PLEASE IDENTIFY THE RETURN AIR LOCATION FOR AHU-1
 AND AHU-3. FBC M 601.5 (7)
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  