2021-08-23 07:16:05 | 1ST REVIEW FBC-2020 MECHANICAL |
| PERMIT-21080310 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE ADD A NOTE ON THE DRAWING STATING ALL HOODS |
| WILL REQUIRE A SEPARATE PERMIT APPLICATION, DRAWINGS |
| AND PLAN REVIEW. THE HOODS WILL NOT BE REVIEWED UNDER |
| THIS PERMIT. |
| |
| 2) PLEASE ADD A NOTE ON THE DRAWING STATING ALL |
| REFRIGERATION WILL REQUIRE A SEPARATE PERMIT |
| APPLICATION, DRAWINGS AND PLAN REVIEW. THE |
| REFRIGERATION WILL NOT BE REVIEWED UNDER THIS PERMIT. |
| |
| 3) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS BASED ON THE |
| USE OF SPACE IN THIS TENANT SPACE I.E. KITCHEN, DINING, |
| BAR, RECEPTION. FBC M 403.3.1.1 AND TABLE 403.3.1.1 |
| |
| 4) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| CALCULATIONS. FBC EC C403.2.1 |
| |
| 5) SHOW LOCATION OF THE NEW OACU-1. FBC 107.2.1 |
| |
| 6) PLEASE IDENTIFY THE RETURN AIR LOCATION FOR AHU-1 |
| AND AHU-3. FBC M 601.5 (7) |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| MICHAEL EDWARDS |
| MECHANICAL EXAMINER |