Date |
Text |
2021-09-08 08:40:25 | 09/08/21 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. ON SHEET A1.00, IT SHOWS A DIFFERENT LAYOUT FROM THE |
| GENERAL FOOD SERVICE EQUIPMENT SERVICE, AND ONE HAS A |
| FOUR-BURNER STOVE AND THE OTHER SIX BURNERS. I COULD |
| NOT FIND THE 18 K BTU P10B SPECIFICATIONS. WOULD YOU |
| PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC |
| SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 2. WOULD YOU PLEASE SHOW THE LENGTH OF ALL CUT SECTIONS |
| OF PIPE ON DRAWING PER 2020 FBC FG SECS. 402.4.1, |
| 402.4.2. |
| |
| 3. WOULD YOU PLEASE SUBMIT THE MANUFACTURER'S |
| SPECIFICATIONS FOR THE PRESSURE REGULATORS PER THE 2020 |
| FBC FG SEC. 410.1. |
| |
| 4. WOULD YOU PLEASE SHOW ALL UNIONS IN FRONT OF |
| REGULATOR 1 FOOT OF EITHER SIDE PER THE 2020 FBC FG SEC |
| 410.2? |
| |
| 5. WOULD YOU PLEASE LABEL THE SHUTOFF VALVE ON GAS |
| ISOMERIC PER THE 2020 FBC FG SEC. 409.5? |
| |
| 6. THE SHUT OFF INSIDE SHALL BE ACCESSIBLE WITHOUT |
| MOVING THE EQUIPMENT PER THE 2020 FBC SEC. G2403 (202) |
| GD, ACCESS. |
| |
| 7. WOULD YOU PLEASE PROVIDE A DRIP LEG BEFORE THE |
| EQUIPMENT IS INSTALLED PER THE 2020 FBC FG 408.2. |
| |
| 8. THE EMERGENCY HOOD SHUT DOWN SHUTOFF VALVE SHALL BE |
| BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE |
| UPSTREAM. UNION TO BE DOWNSTREAM OF MANUAL VALVE. SECS. |
| 10.4, 10.5 OF NFPA 96-08. A READILY ACCESSIBLE MEANS |
| FOR MANUAL ACTIVATION SHALL BE LOCATED BETWEEN (42 IN. |
| AND 48 IN.) ABOVE THE FLOOR, BE ACCESSIBLE IN THE EVENT |
| OF A FIRE, SHALL BE IN A PATH OF EGRESS, AND CLEARLY |
| IDENTIFY THE HAZARD PROTECTED. NFPA 96, SEC. 10.5.1. AT |
| LEAST ONE MANUAL ACTUATION DEVICE SHALL BE LOCATED A |
| MINIMUM OF 3 M (10 FT) AND A MAXIMUM OF 6 M (20 FT) |
| FROM THE PROTECTED HOOD EXHAUST SYSTEM(S) WITHIN A PATH |
| OF EGRESS OR AT AN ALTERNATIVE LOCATION ACCEPTABLE TO |
| THE AHJ. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |