Plan Review Notes
Plan Review Notes For Permit 21080310
Permit Number 21080310
Review Stop G
Sequence Number 1
Notes
Date Text
2021-09-08 08:40:2509/08/21 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET A1.00, IT SHOWS A DIFFERENT LAYOUT FROM THE
 GENERAL FOOD SERVICE EQUIPMENT SERVICE, AND ONE HAS A
 FOUR-BURNER STOVE AND THE OTHER SIX BURNERS. I COULD
 NOT FIND THE 18 K BTU P10B SPECIFICATIONS. WOULD YOU
 PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. WOULD YOU PLEASE SHOW THE LENGTH OF ALL CUT SECTIONS
 OF PIPE ON DRAWING PER 2020 FBC FG SECS. 402.4.1,
 402.4.2.
  
 3. WOULD YOU PLEASE SUBMIT THE MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS PER THE 2020
 FBC FG SEC. 410.1.
  
 4. WOULD YOU PLEASE SHOW ALL UNIONS IN FRONT OF
 REGULATOR 1 FOOT OF EITHER SIDE PER THE 2020 FBC FG SEC
 410.2?
  
 5. WOULD YOU PLEASE LABEL THE SHUTOFF VALVE ON GAS
 ISOMERIC PER THE 2020 FBC FG SEC. 409.5?
  
 6. THE SHUT OFF INSIDE SHALL BE ACCESSIBLE WITHOUT
 MOVING THE EQUIPMENT PER THE 2020 FBC SEC. G2403 (202)
 GD, ACCESS.
  
 7. WOULD YOU PLEASE PROVIDE A DRIP LEG BEFORE THE
 EQUIPMENT IS INSTALLED PER THE 2020 FBC FG 408.2.
  
 8. THE EMERGENCY HOOD SHUT DOWN SHUTOFF VALVE SHALL BE
 BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE
 UPSTREAM. UNION TO BE DOWNSTREAM OF MANUAL VALVE. SECS.
 10.4, 10.5 OF NFPA 96-08. A READILY ACCESSIBLE MEANS
 FOR MANUAL ACTIVATION SHALL BE LOCATED BETWEEN (42 IN.
 AND 48 IN.) ABOVE THE FLOOR, BE ACCESSIBLE IN THE EVENT
 OF A FIRE, SHALL BE IN A PATH OF EGRESS, AND CLEARLY
 IDENTIFY THE HAZARD PROTECTED. NFPA 96, SEC. 10.5.1. AT
 LEAST ONE MANUAL ACTUATION DEVICE SHALL BE LOCATED A
 MINIMUM OF 3 M (10 FT) AND A MAXIMUM OF 6 M (20 FT)
 FROM THE PROTECTED HOOD EXHAUST SYSTEM(S) WITHIN A PATH
 OF EGRESS OR AT AN ALTERNATIVE LOCATION ACCEPTABLE TO
 THE AHJ.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved