2021-08-10 15:17:16THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE LIFE SAFETY PLAN SHEET INDICATES A TOTAL
 OCCUPANCY LOAD OF 59, HOWEVER THE SEATING PLAN SEAT
 INDICATES 73 SEAT ALONE. THIS WOULD NOT EVEN TAKE INTO
 ACCOUNT OR INCLUDE, THE OTHER OCCUPIED AREAS.
  
 PLEASE REVIEW AND CORRECT.
  
  
 2) THE LIFE SAFETY SHEET INDICATES THE PARTY ROOM AT 96
 SQ FT WITH AN OCCUPANCY LOAD OF 6.4 OR 7. THE PARTY
 ROOM SEATING PLAN INDICATES 12 SEATS.
  
 PLEASE REVIEW AND CORRECT.
  
  
 3) THERE REAR EXIT SIGN IS TOO DEEP WITHIN THE REAR
 EXIT CORRIDOR TO BE SEEN FROM THE FRONT COMMON AREA.
  
 ADD EXIT SIGN AT REAR CORRIDOR OPEN AREA LEADING TO
 REAR EXIT CORRIDOR.
  
  
  
 4) THERE ARE INDICATIONS OF A NEW HOOD. ALL HOOD AND
 HOOD SUPPRESSION SHALL BE INSTALLED UNDER SEPARATE
 PERMIT AND SHOP DRAWINGS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
 ADD EXIT SIGN AT REAR CORRIDOR OPEN AREA LEADING TO
 REAR EXIT CORRIDOR
  
  
  
  
  
  
 FIRE PROVISO:
 ADD EXIT SIGN