Plan Review Notes
Plan Review Notes For Permit 21080226
Permit Number 21080226
Review Stop M
Sequence Number 2
Notes
Date Text
2022-05-18 13:08:332ND REVIEW FMC
 PERMIT: 21080226
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE DRYER DUCT THAT WOULD MEET THE SIZE AND
 MATERIAL THICKNESS OF FRC M1502
  
 2) SEE PREVIOUS COMMENTS BELOW:
 1ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21080226
  
  
 1) PLEASE PROVIDE THE ENERGY CALCULATIONS. FBC EC
 101.5.1.1.2
  
 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBC EC R403.7
  
  
 4) PLEASE SHOW A DETAIL FOR THE ANCHORING O THE OUTDOOR
 CONDENSING UNIT. FBC RES M1307.2
  
 5) PLEASE SHOW THE CONDENSATION PIPING AND THE
 TERMINATION LOCATION. FBC RES M1411.3
  
 6) PLEASE PROVIDE A MECHANICAL DRAWING THAT HAS THE
 DIGITAL SIGNATURE OF AN ENGINEER OR ARCHITECT, YOU MAY
 ALSO PROVIDE THE MECHANICAL DRAWING SIGNED BY THE
 MECHANICAL CONTRACTOR THAT HOLDS THE PERMIT TO INSTALL
 THE SYSTEM FOR THIS PROJECT. F.S. 471.003(H)
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  