2022-05-18 13:08:33 | 2ND REVIEW FMC |
| PERMIT: 21080226 |
| |
| CODES IN EFFECT: 2020 |
| |
| FBC- FLORIDA BUILDING CODE |
| FMC- FLORIDA MECHANICAL CODE |
| FEC- FLORIDA ENERGY CONSERVATION |
| FGC- FLORIDA FUEL GAS |
| FEX- FLORIDA EXISTING BUILDING CODE |
| FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| F.S.- FLORIDA STATUTES |
| FAC- FLORIDA ACCESSIBILITY CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PROVIDE DRYER DUCT THAT WOULD MEET THE SIZE AND |
| MATERIAL THICKNESS OF FRC M1502 |
| |
| 2) SEE PREVIOUS COMMENTS BELOW: |
| 1ST REVIEW FBC-2020 MECHANICAL |
| PERMIT-21080226 |
| |
| |
| 1) PLEASE PROVIDE THE ENERGY CALCULATIONS. FBC EC |
| 101.5.1.1.2 |
| |
| 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| CALCULATIONS. FBC EC R403.7 |
| |
| |
| 4) PLEASE SHOW A DETAIL FOR THE ANCHORING O THE OUTDOOR |
| CONDENSING UNIT. FBC RES M1307.2 |
| |
| 5) PLEASE SHOW THE CONDENSATION PIPING AND THE |
| TERMINATION LOCATION. FBC RES M1411.3 |
| |
| 6) PLEASE PROVIDE A MECHANICAL DRAWING THAT HAS THE |
| DIGITAL SIGNATURE OF AN ENGINEER OR ARCHITECT, YOU MAY |
| ALSO PROVIDE THE MECHANICAL DRAWING SIGNED BY THE |
| MECHANICAL CONTRACTOR THAT HOLDS THE PERMIT TO INSTALL |
| THE SYSTEM FOR THIS PROJECT. F.S. 471.003(H) |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| MICHAEL EDWARDS |
| MECHANICAL EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL. 33401 |
| 561-805-6728 |