Plan Review Notes
Plan Review Notes For Permit 21080195
Permit Number 21080195
Review Stop M
Sequence Number 2
Notes
Date Text
2021-10-25 15:36:281) PLEASE PROVIDE THE LOCATION WHERE THE MECHANICAL
 EQUIPMENT SIZING CALCULATIONS ARE IN THIS SUBMITTAL AS
 I DID NOT FIND THEM. FBC 107.2.1
  
 2) THE 28 INCH X 18 INCH DUCT LABELED EA FROM THE
 GARAGE INTO THE RETURN OF THE MECHANICAL SYSTEM WILL
 NEED TO BE ELIMINATED AS YOU CANNOT USED THE GARAGE AS
 RETURN AIR FOR THE OFFICE SPACE. FBC M 601.5; 7
  
 3) PLEASE SHOW THE SMOKE MITIGATION ROUTE FROM THE
 OFFICE SPACE TO THE 44 INCH X 48 INCH SMOKE MITIGATION
 DUCT IN THE SHAFT. FBC 107.2.1
  
 4) THE BUILDING CORE WAS NOT DESIGNED FOR THIS OFFICE
 SPACE. PLEASE SHOW THE CALCULATIONS THAT THE BATH
 EXHAUST FANS AND THE SMOKE MITIGATION FANS ARE DESIGNED
 TO HANDLE THIS ADDITIONAL LOAD. FBC 107.2.1
  