Plan Review Notes For Permit 21080195 |
Permit Number |
21080195 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2021-10-25 15:36:28 | 1) PLEASE PROVIDE THE LOCATION WHERE THE MECHANICAL | | EQUIPMENT SIZING CALCULATIONS ARE IN THIS SUBMITTAL AS | | I DID NOT FIND THEM. FBC 107.2.1 | | | | 2) THE 28 INCH X 18 INCH DUCT LABELED EA FROM THE | | GARAGE INTO THE RETURN OF THE MECHANICAL SYSTEM WILL | | NEED TO BE ELIMINATED AS YOU CANNOT USED THE GARAGE AS | | RETURN AIR FOR THE OFFICE SPACE. FBC M 601.5; 7 | | | | 3) PLEASE SHOW THE SMOKE MITIGATION ROUTE FROM THE | | OFFICE SPACE TO THE 44 INCH X 48 INCH SMOKE MITIGATION | | DUCT IN THE SHAFT. FBC 107.2.1 | | | | 4) THE BUILDING CORE WAS NOT DESIGNED FOR THIS OFFICE | | SPACE. PLEASE SHOW THE CALCULATIONS THAT THE BATH | | EXHAUST FANS AND THE SMOKE MITIGATION FANS ARE DESIGNED | | TO HANDLE THIS ADDITIONAL LOAD. FBC 107.2.1 | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | | | |
|