Plan Review Notes
Plan Review Notes For Permit 21080195
Permit Number 21080195
Review Stop P
Sequence Number 1
Notes
Date Text
2021-10-01 10:42:5010/01/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET A4.02, IN THE MEN'S RESTROOM, THE WATER
 CLOSET COMPARTMENT SHALL BE LOCATED IN THE CORNER,
 DIAGONAL TO THE DOOR 2020 FBBC ACC. SEC. 604.8.1.7
 WATER CLOSET.
  
 2. ON SHEET A5.10;
  
 A. DETAIL EIGHT HAS A SECTION VIEW FOR VANITY; IT HAS
 THE 27 INCH KNEE CLEARANCE, BUT THE HEIGHT OF THE TOP
 OF THE COUNTER IS AT 3'-0" THIS SHOULD BE 2'-10" PER
 THE 2020 FBC ACC SEC. 606.3.
  
 B. ON THAT SAME DETAIL, THE REFLECTIVE PART OF THE
 MIRROR NEEDS TO BE 40 INCHES TO THE REFLECTIVE SIDE PER
 THE 2020 FBC ACC SEC. 603.3.
  
 3. ON SHEET A7.10;
  
 A. ON THE GENERAL NOTES, NUMBER FIVE REFERS TO ANSI,
 WHICH MAY NOT APPLY TO THIS DRAWING, AND FOR
 ACCESSIBILITY AND PLUMBING, IT HAS THE 2014 YEAR, WHICH
 IS NOT THE CORRECT YEAR. WOULD YOU PLEASE CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS?
  
 B. ON DETAIL THREE FOR THE REAR WALL FOR THE TOILET
 GRAB BAR SAYS 6 INCHES FROM THE WALL, WHICH IS NOT AN
 ACTUAL NUMBER AS THE TOILET IS 16 INCHES TO 18 INCHES
 TO THE CENTER, AND THAT NUMBER MAY CONFUSE THE
 INSTALLER. WOULD YOU PLEASE CORRECT PER THE 2020 FBC
 ACC SEC. 604.2 LOCATION AND WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 C. ALSO, ON THAT SAME DETAIL, THE SANITARY NAPKIN SHOWS
 IT NOT SUNK IN THE WALL, WHICH IS IN THE CLEAR FLOOR
 SPACE OF THE WATER CLOSET. WOULD YOU PLEASE CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS?
  
 D. ON THAT SAME DETAIL, IT SHOWS THE FLUSH CONTROLS ON
 THE WRONG SIDE OF THE WATER CLOSET PER THE 2020 ACC
 SEC. 604.6 FLUSH CONTROLS. HANDICAP WATER CLOSET FLUSH
 CONTROL SHALL BE HAND OPERATED OR AUTOMATIC AND SHALL
 BE 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR PER THE
 2020 FBC ACC SEC. 604.9.5.
  
 E. ON DETAIL FOUR, THE PARTITIONS TO PROVIDE PRIVACY
 SHALL EXTEND NOT LESS THAN 60 INCHES ABOVE THE FINISHED
 FLOOR SURFACE PER THE 2020 FBC SEC. P 405.3.5 URINAL
 PARTITIONS.
  
 F. SEATS OF WATER CLOSETS SHALL BE OPEN-FRONT TYPE PER
 2020 FBC P 425.3 WATER CLOSET SEATS
  
 H. UNDER MOUNTING HEIGHTS LETTER B, IT SAYS 1'-4"
 MINIMUM FOR ALL; PLEASE ADD 1'-6" MAXIMUM FROM THE SIDE
 WALL PER THE 2020 FBC ACC. SEC. 604.2 LOCATION. ON
 LETTER H THE TOILET PAPER SAYS 36" MAXIMUM FROM THE
 REAR WALL. IT SHOULD BE 7 INCHES MINIMUM AND 9 INCHES
 MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE
 CENTERLINE OF DISPENSER PER THE 2020 FBC ACC SEC.
 604.7. ON THE LETTER I, KNEE CLEARANCE IS 29 INCHES,
 AND IT SHALL BE A MINIMUM OF 2 INCHES KNEE CLEARANCE
 PER THE 2020 FBC SEC. 306.3. ON LETTER O, THE
 REFLECTIVE PART OF THE MIRROR NEEDS TO BE 40 INCHES TO
 THE REFLECTIVE SIDE PER THE 2020 FBC ACC SEC. 603.3.
  
 I. DOOR HANDLE HARDWARE SHOULD BE NOTED ON BOTH SIDES
 OF THE DOOR PER THE 2020 FBC ACC SEC. 404.2.7.
  
  
 4. ON SHEET P-4.01;
  
 A. ON THE ISOMETRIC, THE WATER CLOSETS ARE IN A
 HORIZONTAL WET VENT, AND THE DRINKING FOUNTAIN HAS TO
 BE DOWNSTREAM FROM IT PER THE 2020 FBC SEC. P 912.1.
  
 B. THERE ARE TWO FLOOR DRAINS ON THE WOMEN'S AND MEN'S
 RESTROOMS, WITH LABELS COVERING THEM. WOULD YOU PLEASE
 MOVE THEM FOR CLARITY PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 C. ON THE ISOMETRIC, PLEASE SHOW THE TRAP PRIMER FOR
 ALL THREE-FLOOR DRAINS. WOULD YOU PLEASE CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS?
  
 D. WOULD YOU PLEASE SHOW LOCATIONS OF WATER HAMMER
 ARRESTORS IN ALL QUICK CLOSING VALVES ON THE WATER
 DIAGRAM 2020 FBC SEC. P604.9.
  
 E. IN THAT SAME DIAGRAM FOR THE HOT WATER HEAR AND
 PUMP, WOULD YOU PLEASE GIVE A DETAILED REFERENCE FOR
 THE DETAIL ON PAGE P5.01 PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. ON SHEET P5.01;
  
 A. PLEASE PROVIDE THE SIZE FOR THE INSULATION FOR THE
 RECIRCULATING SYSTEM THE PIPING THAT SHALL BE INSULATED
 IN ITS ENTIRETY, INCLUDING THE SUPPLY AND RETURN PIPING
 OF A CIRCULATING PER C404.4 (A) INSULATION OF PIPING.
  
 B. WOULD YOU PLEASE SUBMIT LISTED FIRE-STOPPING DETAILS
 FOR THE PIPPING THROUGH RATED WALLS OR THE FLOORS.
 WOULD YOU PLEASE SUBMIT THE COMPLETE ASSEMBLY DETAILS
 FOR THE SYSTEMS PER THE WPB AMENDMENTS TO FBC SEC.
 107.2.1?
  
 6. WOULD YOU PLEASE PROVIDE DETAIL ON THE ARCHITECTURAL
 SHOWING THE ACCESSIBILITY CLEAR FLOOR SPACE DIAGRAM AND
 DIMENSIONS FOR THE DRINKING FOUNTAIN, URINAL, WATER
 CLOSET, LAVATORY IN THE STALL AND OUTSIDE THE STALL PER
 THE 2020 FBC ACC SEC. 606.2. 2 CLEAR FLOOR SPACE.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  