Date |
Text |
2021-10-01 10:42:50 | 10/01/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. ON SHEET A4.02, IN THE MEN'S RESTROOM, THE WATER |
| CLOSET COMPARTMENT SHALL BE LOCATED IN THE CORNER, |
| DIAGONAL TO THE DOOR 2020 FBBC ACC. SEC. 604.8.1.7 |
| WATER CLOSET. |
| |
| 2. ON SHEET A5.10; |
| |
| A. DETAIL EIGHT HAS A SECTION VIEW FOR VANITY; IT HAS |
| THE 27 INCH KNEE CLEARANCE, BUT THE HEIGHT OF THE TOP |
| OF THE COUNTER IS AT 3'-0" THIS SHOULD BE 2'-10" PER |
| THE 2020 FBC ACC SEC. 606.3. |
| |
| B. ON THAT SAME DETAIL, THE REFLECTIVE PART OF THE |
| MIRROR NEEDS TO BE 40 INCHES TO THE REFLECTIVE SIDE PER |
| THE 2020 FBC ACC SEC. 603.3. |
| |
| 3. ON SHEET A7.10; |
| |
| A. ON THE GENERAL NOTES, NUMBER FIVE REFERS TO ANSI, |
| WHICH MAY NOT APPLY TO THIS DRAWING, AND FOR |
| ACCESSIBILITY AND PLUMBING, IT HAS THE 2014 YEAR, WHICH |
| IS NOT THE CORRECT YEAR. WOULD YOU PLEASE CORRECT PER |
| THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION |
| ON CONSTRUCTION DOCUMENTS? |
| |
| B. ON DETAIL THREE FOR THE REAR WALL FOR THE TOILET |
| GRAB BAR SAYS 6 INCHES FROM THE WALL, WHICH IS NOT AN |
| ACTUAL NUMBER AS THE TOILET IS 16 INCHES TO 18 INCHES |
| TO THE CENTER, AND THAT NUMBER MAY CONFUSE THE |
| INSTALLER. WOULD YOU PLEASE CORRECT PER THE 2020 FBC |
| ACC SEC. 604.2 LOCATION AND WPB AMENDMENTS TO THE FBC |
| SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| |
| C. ALSO, ON THAT SAME DETAIL, THE SANITARY NAPKIN SHOWS |
| IT NOT SUNK IN THE WALL, WHICH IS IN THE CLEAR FLOOR |
| SPACE OF THE WATER CLOSET. WOULD YOU PLEASE CORRECT PER |
| THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION |
| ON CONSTRUCTION DOCUMENTS? |
| |
| D. ON THAT SAME DETAIL, IT SHOWS THE FLUSH CONTROLS ON |
| THE WRONG SIDE OF THE WATER CLOSET PER THE 2020 ACC |
| SEC. 604.6 FLUSH CONTROLS. HANDICAP WATER CLOSET FLUSH |
| CONTROL SHALL BE HAND OPERATED OR AUTOMATIC AND SHALL |
| BE 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR PER THE |
| 2020 FBC ACC SEC. 604.9.5. |
| |
| E. ON DETAIL FOUR, THE PARTITIONS TO PROVIDE PRIVACY |
| SHALL EXTEND NOT LESS THAN 60 INCHES ABOVE THE FINISHED |
| FLOOR SURFACE PER THE 2020 FBC SEC. P 405.3.5 URINAL |
| PARTITIONS. |
| |
| F. SEATS OF WATER CLOSETS SHALL BE OPEN-FRONT TYPE PER |
| 2020 FBC P 425.3 WATER CLOSET SEATS |
| |
| H. UNDER MOUNTING HEIGHTS LETTER B, IT SAYS 1'-4" |
| MINIMUM FOR ALL; PLEASE ADD 1'-6" MAXIMUM FROM THE SIDE |
| WALL PER THE 2020 FBC ACC. SEC. 604.2 LOCATION. ON |
| LETTER H THE TOILET PAPER SAYS 36" MAXIMUM FROM THE |
| REAR WALL. IT SHOULD BE 7 INCHES MINIMUM AND 9 INCHES |
| MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE |
| CENTERLINE OF DISPENSER PER THE 2020 FBC ACC SEC. |
| 604.7. ON THE LETTER I, KNEE CLEARANCE IS 29 INCHES, |
| AND IT SHALL BE A MINIMUM OF 2 INCHES KNEE CLEARANCE |
| PER THE 2020 FBC SEC. 306.3. ON LETTER O, THE |
| REFLECTIVE PART OF THE MIRROR NEEDS TO BE 40 INCHES TO |
| THE REFLECTIVE SIDE PER THE 2020 FBC ACC SEC. 603.3. |
| |
| I. DOOR HANDLE HARDWARE SHOULD BE NOTED ON BOTH SIDES |
| OF THE DOOR PER THE 2020 FBC ACC SEC. 404.2.7. |
| |
| |
| 4. ON SHEET P-4.01; |
| |
| A. ON THE ISOMETRIC, THE WATER CLOSETS ARE IN A |
| HORIZONTAL WET VENT, AND THE DRINKING FOUNTAIN HAS TO |
| BE DOWNSTREAM FROM IT PER THE 2020 FBC SEC. P 912.1. |
| |
| B. THERE ARE TWO FLOOR DRAINS ON THE WOMEN'S AND MEN'S |
| RESTROOMS, WITH LABELS COVERING THEM. WOULD YOU PLEASE |
| MOVE THEM FOR CLARITY PER THE WPB AMENDMENTS TO THE FBC |
| SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| |
| C. ON THE ISOMETRIC, PLEASE SHOW THE TRAP PRIMER FOR |
| ALL THREE-FLOOR DRAINS. WOULD YOU PLEASE CORRECT PER |
| THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION |
| ON CONSTRUCTION DOCUMENTS? |
| |
| D. WOULD YOU PLEASE SHOW LOCATIONS OF WATER HAMMER |
| ARRESTORS IN ALL QUICK CLOSING VALVES ON THE WATER |
| DIAGRAM 2020 FBC SEC. P604.9. |
| |
| E. IN THAT SAME DIAGRAM FOR THE HOT WATER HEAR AND |
| PUMP, WOULD YOU PLEASE GIVE A DETAILED REFERENCE FOR |
| THE DETAIL ON PAGE P5.01 PER THE WPB AMENDMENTS TO THE |
| FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 5. ON SHEET P5.01; |
| |
| A. PLEASE PROVIDE THE SIZE FOR THE INSULATION FOR THE |
| RECIRCULATING SYSTEM THE PIPING THAT SHALL BE INSULATED |
| IN ITS ENTIRETY, INCLUDING THE SUPPLY AND RETURN PIPING |
| OF A CIRCULATING PER C404.4 (A) INSULATION OF PIPING. |
| |
| B. WOULD YOU PLEASE SUBMIT LISTED FIRE-STOPPING DETAILS |
| FOR THE PIPPING THROUGH RATED WALLS OR THE FLOORS. |
| WOULD YOU PLEASE SUBMIT THE COMPLETE ASSEMBLY DETAILS |
| FOR THE SYSTEMS PER THE WPB AMENDMENTS TO FBC SEC. |
| 107.2.1? |
| |
| 6. WOULD YOU PLEASE PROVIDE DETAIL ON THE ARCHITECTURAL |
| SHOWING THE ACCESSIBILITY CLEAR FLOOR SPACE DIAGRAM AND |
| DIMENSIONS FOR THE DRINKING FOUNTAIN, URINAL, WATER |
| CLOSET, LAVATORY IN THE STALL AND OUTSIDE THE STALL PER |
| THE 2020 FBC ACC SEC. 606.2. 2 CLEAR FLOOR SPACE. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |