Plan Review Notes
Plan Review Notes For Permit 21080195
Permit Number 21080195
Review Stop M
Sequence Number 1
Notes
Date Text
2021-09-22 11:17:071ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21080195
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.02: PLEASE SHOW THE RATED DAMPERS AT ALL
 LOCATIONS WHERE THE NEW MECHANICAL DUCTS PENETRATE THE
 RATED WALLS. THERE ARE IS ONE MISSING IN THE 38? X 12?
 SA AT THE NEW STORAGE AND PARKING GARAGE RATED
 SEPARATION WALL. ALSO IN THE NEW MECHANICAL ROOM THE
 DUCT WORK PENETRATING THE SHAFT THAT IS PART OF THE
 SMOKE MITIGATION SHOULD HAVE A FIRE/SMOKE DETECTOR. FBC
 M 607
  
 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR THIS NEW CONDITIONED SPACE. FBC EC
 C403.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  