Plan Review Notes
Plan Review Notes For Permit 21080195
Permit Number 21080195
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-09-21 15:49:26THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION OF A PROPOSED WATER CURTAIN
 AT A GLASS WALL & DOOR.
  
 THIS PROPOSED INSTALLATION A MISAPPLICATION FO THE CODE
 AND IS NOT AAPPROVED.
  
 THERE IS ALSO A GLASS DOOR PROPOSED. THIS GLASS DOOR
 MUST BE ADDRESSED SEPARATELY.
  
  
 PER NFPA 13
  
 8.15.26* SPRINKLER-PROTECTED GLAZING.
 WHERE SPRINKLERS ARE USED IN COMBINATION WITH GLAZING
 AS AN ALTERNATIVE TO A REQUIRED FIRERATED
 WALL OR WINDOW ASSEMBLY, THE SPRINKLER-PROTECTED
 ASSEMBLY SHALL COMPLY WITH THE
 FOLLOWING:
 (1) SPRINKLERS SHALL BE LISTED AS SPECIFIC APPLICATION
 WINDOW SPRINKLERS UNLESS THE STANDARD
 SPRAY SPRINKLERS ARE SPECIFICALLY PERMITTED BY THE
 BUILDING CODE.
 (2) SPRINKLERS SHALL BE SUPPLIED BY A WET-PIPE SYSTEM.
 (3) GLAZING SHALL BE HEAT-STRENGTHENED, TEMPERED, OR
 GLASS CERAMIC AND SHALL BE FIXED.
 (4) WHERE THE ASSEMBLY IS REQUIRED TO BE PROTECTED FROM
 BOTH SIDES, SPRINKLERS SHALL BE
 INSTALLED ON BOTH SIDES OF THE GLAZING.
 (5) THE USE OF SPRINKLER-PROTECTED GLAZING SHALL BE
 LIMITED TO NON-LOAD-BEARING WALLS.
 (6) THE GLAZED ASSEMBLY SHALL NOT HAVE ANY HORIZONTAL
 MEMBERS THAT WOULD INTERFERE WITH UNIFORM
 DISTRIBUTION OF WATER OVER THE SURFACE OF THE GLAZING,
 AND THERE SHALL BE NO OBSTRUCTIONS
 BETWEEN SPRINKLERS AND GLAZING THAT WOULD OBSTRUCT
 WATER DISTRIBUTION.
 (7) THE WATER SUPPLY DURATION FOR THE DESIGN AREA THAT
 INCLUDES THE WINDOW SPRINKLERS SHALL
 NOT BE LESS THAN THE REQUIRED RATING OF THE ASSEMBLY
  
 ADDITIONALLY, THIS PROPOSED GLASS WALL IS A 2HR
 FIREWALL, NOT A FIRE BARRIER. THIS ALTERNATIVE
 PROTECTION IS NOT ALLOWED ON FIREWALLS.
  
 THE FRAME OF THE PROPOSED GLASS WALL MUST ALSO BE
 RATED.
  
 ADDITIONAL INFO:
  
 WHEN IT COMES TO THE GLASS ASSEMBLIES, THERE ARE SIX
 ITEMS THAT MUST BE CONSIDERED. A DESIGN MUST TAKE NOTE
 OF GLASS SIZE, GLAZING TYPE, GLAZING FRAMES, HORIZONTAL
 MULLIONS, AND OPENINGS AND PENETRATIONS.
  
 1. THE SIZE OF THE GLASS IS BASED ON FIRE TESTING AND
 SPRINKLER LIMITATIONS. THE GLASS HEIGHT CANNOT EXCEED
 13 FT, AND THERE IS NO LIMITATION TO THE LENGTH OF THE
 WINDOW AS THE WINDOW SPRINKLER SPACING CAN MEET THE
 INSTALLATION REQUIREMENTS OF THE MANUFACTURER?S
 LISTING.
 2. WINDOWS INTENDED TO BE PROTECTED BY SPRINKLERS MUST
 BE VERTICAL. SLOPED AND CURVED GLASS CANNOT BE
 PROTECTED BY WINDOW SPRINKLERS.
 3. WHEN WINDOW SPRINKLERS ARE UTILIZED IN FIRE
 SEPARATIONS, THE GLASS
 MUST BE 1/4-IN. THICK AND HEAT STRENGTHENED OR
 TEMPERED.
 4. WINDOW FRAMES SHALL BE LISTED WITH THE SAME
 FIRE-RESISTANCE RATING AS THE GLASS; THIS IS OFTEN AN
 OVERLOOKED ITEM.
 5. WHEN DEALING WITH WINDOW SPRINKLERS, HORIZONTAL
 MULLIONS ARE IN ESSENCE AN OBSTRUCTION TO THE
 SPRINKLER?S SPRAY PATTERN AND PREVENT THE ABILITY FOR
 THE WATER TO RUN DOWN THE GLASS FACE. THE INTENT OF A
 WINDOW SPRINKLER IS TO COMPLETELY COAT THE GLASS WITH A
 WATER SPRAY IN ORDER TO KEEP THE GLASS FROM FAILING DUE
 TO HOT SPOTS. (SEE FIGURE 1.)
 6. WINDOW SPRINKLERS ARE ALSO ONLY INTENDED TO PROTECT
 FIXED GLASS. OPERABLE WINDOWS CAN NOT BE PROTECTED.
 DOORS IN THESE FIRE PARTITIONS MUST BE TREATED
 SEPARATELY.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  