Date |
Text |
2021-09-21 15:49:26 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) THERE IS AN INDICATION OF A PROPOSED WATER CURTAIN |
| AT A GLASS WALL & DOOR. |
| |
| THIS PROPOSED INSTALLATION A MISAPPLICATION FO THE CODE |
| AND IS NOT AAPPROVED. |
| |
| THERE IS ALSO A GLASS DOOR PROPOSED. THIS GLASS DOOR |
| MUST BE ADDRESSED SEPARATELY. |
| |
| |
| PER NFPA 13 |
| |
| 8.15.26* SPRINKLER-PROTECTED GLAZING. |
| WHERE SPRINKLERS ARE USED IN COMBINATION WITH GLAZING |
| AS AN ALTERNATIVE TO A REQUIRED FIRERATED |
| WALL OR WINDOW ASSEMBLY, THE SPRINKLER-PROTECTED |
| ASSEMBLY SHALL COMPLY WITH THE |
| FOLLOWING: |
| (1) SPRINKLERS SHALL BE LISTED AS SPECIFIC APPLICATION |
| WINDOW SPRINKLERS UNLESS THE STANDARD |
| SPRAY SPRINKLERS ARE SPECIFICALLY PERMITTED BY THE |
| BUILDING CODE. |
| (2) SPRINKLERS SHALL BE SUPPLIED BY A WET-PIPE SYSTEM. |
| (3) GLAZING SHALL BE HEAT-STRENGTHENED, TEMPERED, OR |
| GLASS CERAMIC AND SHALL BE FIXED. |
| (4) WHERE THE ASSEMBLY IS REQUIRED TO BE PROTECTED FROM |
| BOTH SIDES, SPRINKLERS SHALL BE |
| INSTALLED ON BOTH SIDES OF THE GLAZING. |
| (5) THE USE OF SPRINKLER-PROTECTED GLAZING SHALL BE |
| LIMITED TO NON-LOAD-BEARING WALLS. |
| (6) THE GLAZED ASSEMBLY SHALL NOT HAVE ANY HORIZONTAL |
| MEMBERS THAT WOULD INTERFERE WITH UNIFORM |
| DISTRIBUTION OF WATER OVER THE SURFACE OF THE GLAZING, |
| AND THERE SHALL BE NO OBSTRUCTIONS |
| BETWEEN SPRINKLERS AND GLAZING THAT WOULD OBSTRUCT |
| WATER DISTRIBUTION. |
| (7) THE WATER SUPPLY DURATION FOR THE DESIGN AREA THAT |
| INCLUDES THE WINDOW SPRINKLERS SHALL |
| NOT BE LESS THAN THE REQUIRED RATING OF THE ASSEMBLY |
| |
| ADDITIONALLY, THIS PROPOSED GLASS WALL IS A 2HR |
| FIREWALL, NOT A FIRE BARRIER. THIS ALTERNATIVE |
| PROTECTION IS NOT ALLOWED ON FIREWALLS. |
| |
| THE FRAME OF THE PROPOSED GLASS WALL MUST ALSO BE |
| RATED. |
| |
| ADDITIONAL INFO: |
| |
| WHEN IT COMES TO THE GLASS ASSEMBLIES, THERE ARE SIX |
| ITEMS THAT MUST BE CONSIDERED. A DESIGN MUST TAKE NOTE |
| OF GLASS SIZE, GLAZING TYPE, GLAZING FRAMES, HORIZONTAL |
| MULLIONS, AND OPENINGS AND PENETRATIONS. |
| |
| 1. THE SIZE OF THE GLASS IS BASED ON FIRE TESTING AND |
| SPRINKLER LIMITATIONS. THE GLASS HEIGHT CANNOT EXCEED |
| 13 FT, AND THERE IS NO LIMITATION TO THE LENGTH OF THE |
| WINDOW AS THE WINDOW SPRINKLER SPACING CAN MEET THE |
| INSTALLATION REQUIREMENTS OF THE MANUFACTURER?S |
| LISTING. |
| 2. WINDOWS INTENDED TO BE PROTECTED BY SPRINKLERS MUST |
| BE VERTICAL. SLOPED AND CURVED GLASS CANNOT BE |
| PROTECTED BY WINDOW SPRINKLERS. |
| 3. WHEN WINDOW SPRINKLERS ARE UTILIZED IN FIRE |
| SEPARATIONS, THE GLASS |
| MUST BE 1/4-IN. THICK AND HEAT STRENGTHENED OR |
| TEMPERED. |
| 4. WINDOW FRAMES SHALL BE LISTED WITH THE SAME |
| FIRE-RESISTANCE RATING AS THE GLASS; THIS IS OFTEN AN |
| OVERLOOKED ITEM. |
| 5. WHEN DEALING WITH WINDOW SPRINKLERS, HORIZONTAL |
| MULLIONS ARE IN ESSENCE AN OBSTRUCTION TO THE |
| SPRINKLER?S SPRAY PATTERN AND PREVENT THE ABILITY FOR |
| THE WATER TO RUN DOWN THE GLASS FACE. THE INTENT OF A |
| WINDOW SPRINKLER IS TO COMPLETELY COAT THE GLASS WITH A |
| WATER SPRAY IN ORDER TO KEEP THE GLASS FROM FAILING DUE |
| TO HOT SPOTS. (SEE FIGURE 1.) |
| 6. WINDOW SPRINKLERS ARE ALSO ONLY INTENDED TO PROTECT |
| FIXED GLASS. OPERABLE WINDOWS CAN NOT BE PROTECTED. |
| DOORS IN THESE FIRE PARTITIONS MUST BE TREATED |
| SEPARATELY. |
| |
| |
| 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |