Plan Review Notes For Permit 21080195 |
Permit Number |
21080195 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-09-22 13:12:46 | 8TH FLOOR ALTERATION | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) PLEASE SHOW ALL FIRE RATED DOORS TO BE SELF CLOSING | | AND SELF LATCHING FBC 716.5.9 | | 2) DRAWING A4.00 SHOWS A NEW 3' OPENING TO THE STAIRS - | | DRAWING S-1.00 A SHOWS A NEW 6' OPENING - PLEASE | | CLARIFY - OPENINGS SHOULD MATCH. | | 3) DRAWING S-1.00A SHOWS A CUT SECTION REFERRING TO | | DRAWING S5.15 - DRAWING S5.15 WAS NOT ADDED TO | | PROJECTDOX. | | 4) PLEASE SHOW THE GLAZED DOORS IN THE 1 HOUR FIRE | | BARRIER TO COMPLY WITH REQUIREMENTS - FIRE RATED | | GLAZING, SELF CLOSING, SELF LATCHING ETC PER FBC 716 | | 5) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE | | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE | | PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS - ALL | | PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED | | APPROVED BY THE DESIGNER OF RECORD FBC WPB 107 | | |
|