2021-09-22 13:12:468TH FLOOR ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW ALL FIRE RATED DOORS TO BE SELF CLOSING
 AND SELF LATCHING FBC 716.5.9
 2) DRAWING A4.00 SHOWS A NEW 3' OPENING TO THE STAIRS -
 DRAWING S-1.00 A SHOWS A NEW 6' OPENING - PLEASE
 CLARIFY - OPENINGS SHOULD MATCH.
 3) DRAWING S-1.00A SHOWS A CUT SECTION REFERRING TO
 DRAWING S5.15 - DRAWING S5.15 WAS NOT ADDED TO
 PROJECTDOX.
 4) PLEASE SHOW THE GLAZED DOORS IN THE 1 HOUR FIRE
 BARRIER TO COMPLY WITH REQUIREMENTS - FIRE RATED
 GLAZING, SELF CLOSING, SELF LATCHING ETC PER FBC 716
 5) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS - ALL
 PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE DESIGNER OF RECORD FBC WPB 107
  