2021-09-10 16:43:13PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 REF. SHUTTER SCHEDULE FOR THE FOLLOWING COMMENTS:
  
 1. TYPE OF CONSTRUCTION MISSING.
  
 2. TYPE OF GLAZING PROTECTION MISSING.
  
 3. PROTECTIVE DEVICE MANUF. MISSING.
  
 4. DESIGN PRESSURES MISSING.
  
 5. TYPE OF ANCHORS MISSING. SEE NOTE #1 ON SCHEDULE.
 ANCHORS MUST BE SPECIFIC.
  
 6. SHUTTER MOUNTING CONNECTION TYPE SHOULD BE A-A FOR
 SHUTTER #2 AND B-B FOR SHUTTERS # 1 AND 3. SEE PRODUCT
 APPROVAL FL320-R10.
  
 7. SPECIFIC ANCHOR TYPE - SEE #5 ABOVE.
  
 8. SUBSTRATE INDICATED AS GROUTED MASONRY. THIS NEEDS
 TO BE ENTERED IN #1 ABOVE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.