2023-05-09 14:18:40 | 3RD REVIEW FBC-2020 PLUMBING |
| PERMIT- 21080122 |
| 5/9/23 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. COMMENTS REMAINING FROM |
| THE 1ST AND 2ND REVIEWS ARE PRINTED BELOW WITH |
| MODIFICATIONS FOR CLARITY. |
| |
| 1) PLEASE NOTE: DUE TO A CHANGE IN PROCESS, THE GREASE |
| INTERCEPTOR PERMIT IS REQUIRED TO BE SUBMITTED PRIOR TO |
| APPROVAL OF THE PLUMBING PLAN REVIEW. YOU CAN SUBMIT AN |
| APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT HAVE |
| A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT |
| APPLICATION TO [email protected]. YOU WILL |
| RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU |
| MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE |
| APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT |
| YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER |
| YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL |
| AND I WILL CHANGE THE REVIEW STATUS TO PASS. |
| |
| 2) COMMENT #10 FROM THE 1ST AND 2ND REVIEW STILL |
| EXISTS- SHEETS A1.4, A1.5, P1.0 & P1.1: THE DRAINAGE |
| FROM THE HANDSINKS ( EQUIPMENT ITEM #83) AND THE FLOOR |
| SINKS BELOW THE ICE MAKER (22) SHALL NOT DRAIN INTO THE |
| GREASE WASTE LINE AND INTERCEPTOR- SECS. 1003.2 AND |
| 1003.3.1 FBC P. |
| PLANS NOT CORRECTED. THIS IS A MANDATORY REQUIRMENT IN |
| ACCORDANCE WITH THE FBC P AND THE WPB UTILITIES DEPT- |
| PLEASE CORRECT THE PLANS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |