Plan Review Notes
Plan Review Notes For Permit 21080122
Permit Number 21080122
Review Stop B
Sequence Number 3
Notes
Date Text
2023-05-09 09:21:36NEW BUILDING - CONVENIENCE STORE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE THE FLORIDA STATE FRONT PAGES FOR THE
 PROVIDED PRODUCT APPROVALS.
  
 2) PLEASE SHOW THE REQUIRED WIND DESIGN PRESSURES FOR
 EACH WIND ZONE FOR THE ROOFING SYSTEMS - FBC 1609
  
 3) PLEASE PROVIDE A PROPOSED ELEVATION CERTIFICATE -
 FBC WPB 107.3.5.1
  
 4) DRAWING A1.3 SHOWS THE WIDTH OF THE ACCESSIBLE STALL
 DOOR AT 32 INCHES INCLUDING THE DOOR IN THE 32 INCHES -
 THE CLEAR DOOR OPENING NEEDS TO BE 32 INCHES - FBC A
 404.2.3 CLEAR WIDTH.
 DOOR OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES
 (815 MM) MINIMUM. CLEAR OPENINGS OF DOORWAYS WITH
 SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF
 THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES.
  
 5) DRAWING S2.2 SHOWS THE DESIGN WIND SPEED AT 168MPH
 ON THE ROOF PLAN NOTE - SHOULD BE 170MPH PER FBC WPB
 SECTION 120
  
 6) SEPARATE PERMITS ARE REQUIRED FOR - DUMPSTER
 ENCLOSURE, CANOPY, GAS TANKS, PARKING LOT
  
 7) DRAWINGS CV-B, A1.4, S2.2 DO NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN
 PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED
 TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).
  
  
  
  