2022-09-29 13:24:40 | 2ND REVIEW FBC-2020 PLUMBING |
| PERMIT- 21080122 |
| 9/28/2022 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. COMMENTS REMAINING FROM |
| THE 1ST REVIEW ARE PRINTED BELOW WITH ADDITIONAL NOTES |
| FOR CLARIFICATION. |
| |
| 2) CV-B & P-0.1: PLEASE PROVIDE ON THE PLAN A LIST OF |
| SEPARATE PERMITS THAT ARE REQUIRED RELATING TO THE |
| MASTER PLUMBING PERMIT- BACKFLOW PREVENTER FOR POTABLE |
| WATER SERVICE, GREASE AND SOLIDS INTERCEPTOR |
| INSTALLATIONS, IRRIGATION SYSTEM- SECTION 105.1 AND |
| 107.1 WPB. |
| |
| DUE TO A CHANGE IN PROCESS, THE POTABLE WATER BACKFLOW |
| PERMIT AND GREASE INTERCEPTOR PERMIT ARE REQUIRED TO BE |
| SUBMITTED PRIOR TO ISSUANCE OF THE PRIMARY PERMIT. YOU |
| CAN SUBMIT AN APPLICATION "TBD" (TO BE DETERMINED) IF |
| YOU DO NOT HAVE A CONTRACTOR SELECTED BY EMAILING A |
| COMPLETED PERMIT APPLICATION TO [email protected] |
| . YOU WILL RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD |
| PLANS. YOU MAY UPLOAD PLANS AND PAY FEES AT A FUTURE |
| DATE, BUT THE APPLICATION IS REQUIRED AT THIS TIME. WE |
| RECOMMEND THAT YOU PAY FEES AND UPLOAD PLANS AT THE |
| SAME TIME. AFTER YOU HAVE THE PERMIT(S) GENERATED, |
| NOTIFY ME VIA EMAIL AND I WILL CHANGE THE REVIEW STATUS |
| TO PASS. |
| |
| 8) P-0.1: PROVIDE A PLUMBING FIXTURE SCHEDULE- SECTION |
| 107.2.1 WPB. |
| |
| NOT PROVIDED. |
| |
| 9) C4.0 & P1.0: THE LOCATIONS OF THE INTERCEPTORS AS |
| SHOWN ON THE PLANS DO NOT MATCH- SECTION 107.2.1 WPB. |
| A) PLEASE SHOW FIELD LOCATION OF SCHEDULE NOTE 4 ON |
| C4.0. |
| |
| PLANS NOT CORRECTED. |
| |
| 10) P1.0 & P2.0: THE CLEAR WATER WASTE FROM THE HAND |
| SINKS AND FLOOR SINKS UNDER ICE BINS AND ICE MAKERS |
| ETC. SHALL NOT DRAIN INTO THE GREASE WASTE LINE AND |
| INTERCEPTOR- SECTIONS 1003.2 AND 1003.3.1 FBC P. |
| |
| PLANS NOT CORRECTED. THIS IS A MANDATORY REQUIRMENT IN |
| ACCORDANCE WITH THE FBC P AND THE WPB UTILITIES DEPT- |
| PLEASE CORRECT THE PLANS. |
| |
| 11) P1.0 & P2.0: THE URINAL DRAIN SHALL NOT CONNECT |
| INTO THE MEN'S WET-VENTED HORIZONTAL BRANCH DRAIN- |
| SECTION 912.1 FBC P. PLEASE RELOCATE THE DRAIN |
| CONNECTION TO A POINT DOWNSTREAM OF THE WET VENTED |
| FIXTURES. |
| |
| P1.1: THE URINAL DRAIN AND VENT ARE APPROVED. PROVIDE A |
| VENT AT THE BACK-TO-BACK DOUBLE LAVATORY LOCATION TO |
| SERVE A DRY VENT FOR THE HORIZONTAL WET VENT- SEC. |
| 912.2.1 FBC P. |
| |
| 12) SHEETS P1.0 & P2.0 ARE BEING USED TO IDENTIFY BOTH |
| THE SANITARY AND WATER PLANS. ACCORDING TO THE INDEX |
| THE WATER PLANS SHOULD BE LABELED P1.1 AND P2.1- PLEASE |
| CORRECT- SECTION 107.2.1 WPB. |
| |
| PLEASE REVIEW THE INDEX ON SHEET CV-B AND LABEL THE |
| PLUMBING PLANS AS THEY ARE LABELED IN THE INDEX. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |