Plan Review Notes
Plan Review Notes For Permit 21080122
Permit Number 21080122
Review Stop P
Sequence Number 2
Notes
Date Text
2022-09-29 13:24:402ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21080122
 9/28/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS REMAINING FROM
 THE 1ST REVIEW ARE PRINTED BELOW WITH ADDITIONAL NOTES
 FOR CLARIFICATION.
  
 2) CV-B & P-0.1: PLEASE PROVIDE ON THE PLAN A LIST OF
 SEPARATE PERMITS THAT ARE REQUIRED RELATING TO THE
 MASTER PLUMBING PERMIT- BACKFLOW PREVENTER FOR POTABLE
 WATER SERVICE, GREASE AND SOLIDS INTERCEPTOR
 INSTALLATIONS, IRRIGATION SYSTEM- SECTION 105.1 AND
 107.1 WPB.
  
 DUE TO A CHANGE IN PROCESS, THE POTABLE WATER BACKFLOW
 PERMIT AND GREASE INTERCEPTOR PERMIT ARE REQUIRED TO BE
 SUBMITTED PRIOR TO ISSUANCE OF THE PRIMARY PERMIT. YOU
 CAN SUBMIT AN APPLICATION "TBD" (TO BE DETERMINED) IF
 YOU DO NOT HAVE A CONTRACTOR SELECTED BY EMAILING A
 COMPLETED PERMIT APPLICATION TO [email protected]
 . YOU WILL RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD
 PLANS. YOU MAY UPLOAD PLANS AND PAY FEES AT A FUTURE
 DATE, BUT THE APPLICATION IS REQUIRED AT THIS TIME. WE
 RECOMMEND THAT YOU PAY FEES AND UPLOAD PLANS AT THE
 SAME TIME. AFTER YOU HAVE THE PERMIT(S) GENERATED,
 NOTIFY ME VIA EMAIL AND I WILL CHANGE THE REVIEW STATUS
 TO PASS.
  
 8) P-0.1: PROVIDE A PLUMBING FIXTURE SCHEDULE- SECTION
 107.2.1 WPB.
  
 NOT PROVIDED.
  
 9) C4.0 & P1.0: THE LOCATIONS OF THE INTERCEPTORS AS
 SHOWN ON THE PLANS DO NOT MATCH- SECTION 107.2.1 WPB.
 A) PLEASE SHOW FIELD LOCATION OF SCHEDULE NOTE 4 ON
 C4.0.
  
 PLANS NOT CORRECTED.
  
 10) P1.0 & P2.0: THE CLEAR WATER WASTE FROM THE HAND
 SINKS AND FLOOR SINKS UNDER ICE BINS AND ICE MAKERS
 ETC. SHALL NOT DRAIN INTO THE GREASE WASTE LINE AND
 INTERCEPTOR- SECTIONS 1003.2 AND 1003.3.1 FBC P.
  
 PLANS NOT CORRECTED. THIS IS A MANDATORY REQUIRMENT IN
 ACCORDANCE WITH THE FBC P AND THE WPB UTILITIES DEPT-
 PLEASE CORRECT THE PLANS.
  
 11) P1.0 & P2.0: THE URINAL DRAIN SHALL NOT CONNECT
 INTO THE MEN'S WET-VENTED HORIZONTAL BRANCH DRAIN-
 SECTION 912.1 FBC P. PLEASE RELOCATE THE DRAIN
 CONNECTION TO A POINT DOWNSTREAM OF THE WET VENTED
 FIXTURES.
  
 P1.1: THE URINAL DRAIN AND VENT ARE APPROVED. PROVIDE A
 VENT AT THE BACK-TO-BACK DOUBLE LAVATORY LOCATION TO
 SERVE A DRY VENT FOR THE HORIZONTAL WET VENT- SEC.
 912.2.1 FBC P.
  
 12) SHEETS P1.0 & P2.0 ARE BEING USED TO IDENTIFY BOTH
 THE SANITARY AND WATER PLANS. ACCORDING TO THE INDEX
 THE WATER PLANS SHOULD BE LABELED P1.1 AND P2.1- PLEASE
 CORRECT- SECTION 107.2.1 WPB.
  
 PLEASE REVIEW THE INDEX ON SHEET CV-B AND LABEL THE
 PLUMBING PLANS AS THEY ARE LABELED IN THE INDEX.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  