2022-09-26 16:22:51 | 2ND REVIEW FMC |
| PERMIT: 21080122 |
| |
| CODES IN EFFECT: 2020 |
| |
| FBC- FLORIDA BUILDING CODE |
| FMC- FLORIDA MECHANICAL CODE |
| FEC- FLORIDA ENERGY CONSERVATION |
| FGC- FLORIDA FUEL GAS |
| FEX- FLORIDA EXISTING BUILDING CODE |
| FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| F.S.- FLORIDA STATUTES |
| FAC- FLORIDA ACCESSIBILITY CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE ENERGY CODE CALCULATIONS PAGE 2 OF 18 HAS THE |
| JURISDICTION AS ALACHUA COUNTY, ALACHUA, FL. 111000. |
| PLEASE PROVIDE THE CORRECT INFORMATION AS THE |
| JURISDICTION IS THE CITY OF WEST PALM BEACH. IT ALSO |
| APPEARS THAT ON PAGES 5,6 AND 7 OF 18 THAT GAINESVILLE |
| REGIONAL AP WAS USED FOR THE WEATHER INFORMATION. |
| PROVIDE THE CORRECT LOCATION ON THIS DOCUMENT. PALM |
| BEACH INTERNATIONAL, PBI. FBC 107.3.5 |
| |
| 2) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS IS |
| STILL USING MIAMI IAP AS THE LOCATION. THIS SHOULD SHOW |
| WEST PALM BEACH. FBC 107.3.5 |
| |
| 3) PREVIOUS COMMENT: PLEASE PROVIDE SPECIFICATIONS ON: |
| CHEFTOP OVEN, VENTLESS HOOD AND THE THERMO DRAWER. FBC |
| 107.3.5 |
| |
| 4) PLEASE SHOW THE MECHANICAL EQUIPMENT ON THE ROOF |
| WILL HAVE THE REQUIRED FALL PROTECTION. FMC 304.11 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |