2022-10-03 14:34:09NEW BUILDING - CONVENIENCE STORE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE THE PRODUCT APPROVALS FOR THE DOORS,
 AND ROOFING SYSTEMS THAT ARE LISTED ON PAGE CV-B - OR
 HAVE THE PROVIDED PRODUCT APPROVALS REVIEWED AND MARKED
 APPROVED BY THE BUILDING DESIGNER OF RECORD - FBC WPB
 107.3.4
  
 2) DRAWINGS S1.1 SHOWS THE WIND SPEED USED FOR WIND
 DESIGN AS 168MPH - RISK CATEGORY II WIND SPEED SHOULD
 BE 170MPH PER FBC WPB SECTION 120.
  
 3) DRAWING CV-B SHOWS ASCE 7-10 USED FOR WIND DESIGN -
 SHOULD BE ASCE 7-16 FBC CHAPTER 35
  
 4) DRAWING S1.1 SHOWS THE WIND DESIGN USING "EXPOSURE
 B" - THE BUILDING IS NEXT TO A LARGE LAKE - "EXPOSURE
 D" SHOULD BE USED.
  
 5) IN THE PRODUCT APPROVAL PROVIDED FOR THE FLAT DECK -
 PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE
 ROOFING PRODUCT APPROVAL - ROOFING SYSTEM TO BE USED ON
 THE PROVIDED PRODUCT APPROVAL MAY REQUIRE ADDITIONAL
 SIGNED AND SEALED ATTACHMENT DETAILS FROM AN ARCHITECT
 OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A
 HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE PRODUCT
 APPROVAL - SEE GENERAL NOTES IN THE PRODUCT APPROVAL.
  
 6) THE SOIL REPORT PROVIDED - DOES NOT SHOW AS
 DIGITALLY SIGNED IN ADOBE READER - SIGNED AND SEALED
 DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  
  
  
  