2021-09-02 15:45:21 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1 |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 21080098 3800 WASHINGTON RD # 1108 |
| |
| 1ST REVIEW |
| PLUMBING COMMENTS: DENIED |
| |
| 1.EXISTING FLOOR PLAN SHOWS BATH #1 WITH BATHTUB. |
| PROPOSED PLAN SHOWS A SHOWER. ELECTRICAL PLAN SHOWS A |
| SHOWER, SHOWER PAN DETAIL, CURB DETAIL AND VANITY |
| DETAIL. SCOPE OF WORK ONLY INDICATES KITCHEN |
| REPLACEMENT. PER WPB FBC 107.2.1, CLARIFY. |
| |
| 2.NEW KITCHEN SINK IS RELOCATED FROM EXISTING SINK |
| LOCATION AND A DISHWASHER HAS BEEN ADDED. PER WPB FBC |
| 107.2.1, PROVIDE THE FOLLOWING NOTES. |
| ?A) MODIFY IN WALL EXISTING HOT AND COLD WATER PIPE TO |
| ACCOMMODATE NEW KITCHEN SINK. COMPLY WITH FBC PL 604, |
| 605, 606. |
| ?B) MODIFY IN WALL EXISTING KITCHEN WASTE FIXTURE DRAIN |
| TO ACCOMMODATE NEW KITCHEN SINK. COMPLY WITH FBC PL |
| 909.1 AND TABLE 909.1. |
| ?C) PER FBC PL 604.9, A WATER-HAMMER ARRESTOR SHALL BE |
| INSTALLED WHERE QUICK-CLOSING VALVES (DISHWASHER AND |
| ICE LINE) ARE UTILIZED. WATER-HAMMER ARRESTORS SHALL BE |
| INSTALLED IN ACCORDANCE WITH THE MANUFACTURER?S |
| INSTRUCTIONS. WATER-HAMMER ARRESTORS SHALL CONFORM TO |
| ASSE 1010 |
| ?D) PER FBC PL 409.4, THE WASTE CONNECTION OF A |
| RESIDENTIAL DISHWASHER SHALL CONNECT DIRECTLY TO A WYE |
| BRANCH FITTING ON THE TAILPIECE OF THE KITCHEN SINK, |
| DIRECTLY TO THE DISHWASHER CONNECTION OF A FOOD WASTE |
| DISPOSER, OR THROUGH AN AIR BREAK TO A STANDPIPE. THE |
| WASTE LINE OF A RESIDENTIAL DISHWASHER SHALL RISE AND |
| BE SECURELY FASTENED TO THE UNDERSIDE OF THE SINK RIM |
| OR COUNTER TOP. |
| ?E) PER FBC PL 412.3, INDIVIDUAL SHOWER AND TUB-SHOWER |
| COMBINATION VALVES SHALL BE BALANCED-PRESSURE, |
| THERMOSTATIC OR COMBINATION |
| BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO |
| THE REQUIREMENTS OF ASSE 1016/ASME A112.1016/CSA |
| B125.16 OR ASME A112.18.1/CSA B125.1 AND SHALL BE |
| INSTALLED AT THE POINT OF USE. SHOWER AND TUB-SHOWER |
| COMBINATION VALVES REQUIRED BY THIS SECTION SHALL BE |
| EQUIPPED WITH A MEANS TO LIMIT THE MAXIMUM SETTING OF |
| THE VALVE TO 120?F (49?C), WHICH SHALL BE FIELD |
| ADJUSTED IN ACCORDANCE WITH THE MANUFACTURER?S |
| INSTRUCTIONS. IN-LINE THERMOSTATIC VALVES SHALL NOT BE |
| UTILIZED FOR COMPLIANCE WITH THIS SECTION. |
| |
| 3.PER WPB FBC 107.2.1, INDICATE ANY ICE MAKER AND IF |
| THERE IS ONE, SHOW HOW WATER IS TO BE PROVIDED AND HOW |
| CONDENSATE WOULD BE REMOVED IF APPLICABLE. |
| |
| 4. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR FLOOR |
| PENETRATION SHOWER DRAIN RELOCATION TUB TO SHOWER. |
| COMPLY WITH THE REQUIREMENTS OF FBC CHAPTER 7. |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| MOBILE 561-246-0882 |
| PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| THURSDAYS |
| |
| 21080098 3800 WASHINGTON RD # 1108 |