2021-10-27 07:59:14 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2020 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT:21080091 |
| ADD: 315 S. FLAGLER DR. / CHAPEL RENOVATION |
| CONT: PHILIP E. JOHNSON INC. |
| TEL: 561-366-1034 |
| E-MAIL: [email protected] |
| |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. OCT. 27TH/ 2021 |
| ACTION: DENIED |
| |
| 1) THE CODE ANALYSIS SHEET A101C INDICATES THE |
| CONSTRUCTION TYPE TO BE I-B. PLEASE NOTE THIS IS A 13 |
| STORY HIGHRISE, OCCUPANCY TYPE I-2. PLEASE REVIEW THE |
| 2020 FBC-B TABLE 504.4. |
| |
| 2) SHEET S-2 WIND LOAD SHEET PROVIDED IS FOR BUILDINGS |
| 60 FEET IN HEIGHT OR LESS. PLEASE UPDATE THE WIND CODE |
| ANALYSIS FOR A 13-STORY BUILDING. NEGATIVE PRESSURES |
| ARE TAKEN FROM THE MEAN ROOF HEIGHT. 2020 FBC-B |
| 1603.1.4 WIND DESIGN DATA. |
| |
| 3) PLEASE SUBMIT THE COMPONENTS AND CLADDING PRODUCT |
| APPROVALS. 2020 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES. |
| (B) WINDOWS & MULLIONS |
| |
| 4) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP |
| DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD |
| PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC. |
| |
| 5)107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| FOR REVIEW BY THE BUILDING OFFICIAL. |
| |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. |
| |
| 6) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY IN THE |
| PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| IDENTIFY THE OPENING WIDTH & HEIGHT, SILL HEIGTH, TYPE |
| OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR |
| REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B |
| 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| |
| 7) SHEET S311 CEILING DETAILS. IT APPEARS THE CEILING |
| IS TO BE HUNG FROM METAL TRACK AND METAL STUDS BUT |
| THERE IS NO INFORMATION AS TO THE SIZE OF TRACK OR |
| STUDS, THICKNESS, GAUGE OF TRACK & STUDS, SPACING OF |
| ANY OF THE FRAMING MEMBERS, ANCHORING OF TRACK TO THE |
| STRUCTURAL DECK ABOVE, OR THE AMOUNT OF ANCHORS AND |
| SIZE FROM FRAMING MEMBER TO FRAMING MEMBER. 107.2.1.2. |
| ADDITIONAL INFORMATION IS REQUIRED. 2020 FBC-B TABLE |
| 2508.1STEEL FRAMING FOR GYPSUM BOARD. |
| |
| 8) SHEET A714 WINDOW CUT SECTION SHOW A NEW STEEL |
| LINTEL. THE STRUCTURAL SHEETS DO NOT PROVIDE THE SIZE |
| OF THE LINTEL, NOR HOW THE LINTEL IS TO BE ANCHORED AS |
| PART OF THE MWFRS, MAIN WIND FORCE RESISTING SYSTEM. |
| 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 9) SHEET A701 INTERIOR ELEVATIONS SHOWS MARBLE WAINSCOT |
| ON SOME WALLS, OTHER WALLS THE MARBLE GOES FROM THE |
| FLOOR TO THE CEILING. SHEET A821 SHOWS MARBLE CLADDING |
| ABOVE THE WINDOW. THE PLAN DOES NOT INDICATE HOW THE |
| MARBLE VENEER IS TO BE ANCHORED TO THE INTERIOR WALL |
| SUB-SURFACE. SECTION 1405.8 IS SLAB-TYPE VENEERS |
| (EXTERIOR OF BUILDING), HOW DO YOU ANCHOR THE MARBLE |
| VENEERS TO THE INTERIOR WALLS. HOW ARE YOU GOING TO |
| SUPPORT THE MARBLE SLABS OVER WINDOWS? 107.2.1.2 |
| ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 10) THE PERMIT VALUE OF $85,000.00 IS LOW CONSIDERED |
| ALL OF THE MARBLE WORK THAT IS TAKING PLACE AND DROPPED |
| CEILING WITHIN THE CHAPEL. 109.3 BUILDING PERMIT |
| VALUATION.IF, IN THE OPINION OF THE BUILDING OFFICIAL, |
| THE CLAIMED VALUATION OF BUILDING, ALTERATION, |
| STRUCTURE, ELECTRICAL, GAS, MECHANICAL, OR PLUMBING |
| SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE |
| APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING |
| PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| TOTAL REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| |
| |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| |
| AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING |
| FROM CITY HALL. |
| MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| PART-TIME/ RETIRED. |
| |
| IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| BACK INTO THE OFFICE CALL |
| (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| THANK YOU. |
| |