2021-10-18 10:00:34 | RESIDENTIAL (R2) THIRD BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #21080079 |
| |
| NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| SHALL COMPLY WITH THE MATERIALS AND METHODS |
| REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| |
| 1- DESIGN WIND PRESSURE CALCULATIONS SUBMITTED: |
| BASED ON THE AERIAL VIEWS ON THE PROPERTY APPRAISER |
| WEBSITE, IT LOOKS LIKE SOME OPENINGS ( WINDOW #6 AND |
| SLIDING GLASS DOORS) ARE IN THE END ZONE NOT IN THE |
| INTERIOR ZONE AND THE BUILDING DIMENSIONS ARE WRONG. |
| THIS IS CRITICAL BECAUSE PRODUCT APPROVALS SUBMITTED |
| MAY NOT MEET THE DESIGN PRESSURES. REVISE CALCULATIONS |
| SUBMITTED SHOWING THE OPENINGS THAT ARE LOCATED IN THE |
| END ZONE OR PROVIDE SITE SPECIFIC DESIGN WIND PRESSURES |
| SHOWING THE ACTUAL BUILDING DIMENSIONS AND WALL ZONES. |
| SEC. 107.2.1.2 CITY AMENDMENTS. |
| |
| RESPONSE: |
| REPEAT COMMENT. CALCULATIONS WERE NOT REVISED. AS |
| MENTIONED BEFORE, IT LOOKS LIKE SOME OPENINGS ( WINDOW |
| #6 AND SLIDING GLASS DOORS) ARE IN THE END ZONE NOT IN |
| THE INTERIOR ZONE. REVISE CALCULATIONS SUBMITTED |
| SHOWING THE OPENINGS THAT ARE LOCATED IN THE END ZONE |
| OR PROVIDE SITE SPECIFIC DESIGN WIND PRESSURES SHOWING |
| THE ACTUAL BUILDING DIMENSIONS AND WALL ZONES. SEC. |
| 107.2.1.2 CITY AMENDMENTS. |
| NOTE: GIVEN THE SHAPE, HEIGHT AND DIMENSIONS OF THIS |
| BUILDING AND BASED ON THE LOCATION OF THE OPENINGS, THE |
| CONSERVATIVE APPROACH IS TO ASSUME THAT SOME OPENINGS |
| ARE LOCATED IN THE END ZONE AS SUGGESTED ON THE WEBSITE |
| WHERE CONTRACTOR IS ENTERING THE DATA TO OBTAIN THE |
| DESIGN WIND PRESSURES. OTHERWISE SITE SPECIFIC |
| ENGINEERING WHERE THE ENGINEER TAKES INTO CONSIDERATION |
| THE ACTUAL SHAPE AND BUILDING DIMENSIONS WILL BE |
| REQUIRED TO SHOW OPENINGS ARE NOT LOCATED IN THE END |
| ZONE. SEC. 107.2.1.2 CITY AMENDMENTS. |
| |
| 2- PRODUCT APPROVALS SUBMITTED WILL BE REVIEWED ONCE |
| THE DESIGN WIND PRESSURES ARE REVISED. PLEASE CHECK |
| PRODUCT APPROVALS SUBMITTED MEET THE REVISED DESIGN |
| PRESSURES. OTHERWISE NEW PRODUCT APPROVALS ARE |
| REQUIRED. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 3- WINDOW MULLIONS PRODUCT APPROVAL SUBMITTED: |
| CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY |
| COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| REPEAT COMMENT. |
| |
| |
| NOTE: SEE SEC. 702.4 FBC-EXISTING BUILDING CODE. WINDOW |
| OPENING CONTROL DEVICES IN WINDOW REPLACEMENT ARE |
| REQUIRED WHEN THE FOLLOWING APPLY: |
| IN GROUP R-2 OR R-3 BUILDINGS CONTAINING DWELLING UNITS |
| AND ONE- AND TWO-FAMILY DWELLINGS AND TOWNHOUSES |
| REGULATED BY THE FLORIDA BUILDING CODE, RESIDENTIAL, |
| WINDOW OPENING CONTROL DEVICES COMPLYING WITH ASTM |
| F2090 SHALL BE INSTALLED WHERE AN EXISTING WINDOW IS |
| REPLACED AND WHERE ALL OF THE FOLLOWING APPLY TO THE |
| REPLACEMENT WINDOW: |
| 1.THE WINDOW IS OPERABLE; |
| 2. THE WINDOW REPLACEMENT INCLUDES REPLACEMENT OF THE |
| SASH AND THE FRAME; |
| 3.ONE OF THE FOLLOWING APPLIES: |
| 3.1.IN GROUP R-2 OR R-3 BUILDINGS CONTAINING DWELLING |
| UNITS, THE TOP OF THE SILL OF THE WINDOW OPENING IS AT |
| A HEIGHT LESS THAN 36 INCHES (915 MM) ABOVE THE |
| FINISHED FLOOR; OR |
| 3.2. IN ONE- AND TWO-FAMILY DWELLINGS AND TOWNHOUSES |
| REGULATED BY THE FLORIDA BUILDING CODE, RESIDENTIAL, |
| THE TOP SILL OF THE WINDOW OPENING IS AT A HEIGHT LESS |
| THAN 24 INCHES (610 MM) ABOVE THE FINISHED FLOOR; |
| 4.THE WINDOW WILL PERMIT OPENINGS THAT WILL ALLOW |
| PASSAGE OF A 4-INCH-DIAMETER (102 MM) SPHERE WHEN THE |
| WINDOW IS IN ITS LARGEST OPENED POSITION; AND |
| 5.THE VERTICAL DISTANCE FROM THE TOP OF THE SILL OF THE |
| WINDOW OPENING TO THE FINISHED GRADE OR OTHER SURFACE |
| BELOW, ON THE EXTERIOR OF THE BUILDING, IS GREATER THAN |
| 72 INCHES (1829 MM). |
| THE WINDOW OPENING CONTROL DEVICE, AFTER OPERATION TO |
| RELEASE THE CONTROL DEVICE ALLOWING THE WINDOW TO FULLY |
| OPEN, SHALL NOT REDUCE THE MINIMUM NET CLEAR OPENING |
| AREA OF THE WINDOW UNIT TO LESS THAN THE AREA REQUIRED |
| BY THE FLORIDA BUILDING CODE, BUILDING |
| |
| |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |