Plan Review Notes
Plan Review Notes For Permit 21080063
Permit Number 21080063
Review Stop B
Sequence Number 1
Notes
Date Text
2021-08-10 11:30:31WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21080063
 ADD: 101 N. CLEMATIS ST. # 506
 CONT: WINDOW & DOOR DESIGN CENTER
 TEL: 561-743-9688
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. AUGUST 10TH/ 2021
 ACTION: DENIED
 1) THE WIND LOAD CHART BY TARNOWSKI ENGINEERING STATES
 THE UNIT LOCATION IS A C EXPOSURE. DEPENDING ON THE
 UNIT LOCATION IN THE BUILDING IT MAYBE A C EXPOSURE OR
 D EXPOSURE. PLEASE SUBMIT THE BUILDING FOOT PRINT THE
 LOCATION OF THE UNIT AND IN CORRELATION WITH THE
 INTERCOASTAL WATERWAY TO DETERMINE THE EXPOSURE AND IF
 THE WORK IS TO OCCUR IN WALL ZONE 4 OR WALL ZONE 5 A
 END ZONE.
 2020 FBC-BUILDING CODE SECTION 1609.4.3. EXPOSURE
 CATEGORIES. EXPOSURE D SHALL APPLY WHERE THE GROUND
 SURFACE ROUGHNESS, AS DEFINED BY SURFACE ROUGHNESS D,
 PREVAILS IN THE UPWARD DIRECTION FOR A DISTANCE OF AT
 LEAST 5,000 FEET OR 20 TIMES THE HEIGHT OF THE
 BUILDING, WHICHEVER IS GREATER. EXPOSURE SHALL ALSO
 APPLY WHERE THE GROUND SURFACE ROUGHNESS IMMEDIATELY
 UPWIND OF THE SITE IS B OR C , AND THE SITE IS WITHIN A
 DISTANCE OF 600 FEET OR 20 TIMES THE BUILDING HEIGHT,
 WHICHEVER IS GREATER, FROM AN EXPOSURE D CONDITION AS
 DEFINED IN THE PREVIOUS SENTENCE.
  
 2) THE SUBMITTED LAYOUT PLAN NEEDS TO COMPLY WITH
 CERTIFICATION BY CONTRACTOR. 107.3.4.3. THE CONTRACTOR
 (QUALIFIER) THAT CREATED / DREW THE SET OF PLANS WILL
 NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS.
 PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE
 NUMBER FOR THE TRADE YOU ARE LICENSED IN AND PLANS
 DRAWN.
  
 3) THE SUBMITTED WIND CHART APPEARS TO BE A PAPER
 ORIGINAL SIGNED AND SEALED DOCUMENT THAT WAS UPLOADED
 TO BE A DIGITAL DOCUMENT. FLORIDA ADMINISTRATIVE CODE
 61G15-23.005 (3)(C) A DOCUMENT IN THE FILE FOLDER,
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 DIGITALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS (DIGITAL SIGNATURES),
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  