Plan Review Notes
Plan Review Notes For Permit 21080025
Permit Number 21080025
Review Stop P
Sequence Number 1
Notes
Date Text
2021-08-12 11:29:4208/12/21 1ST POLL PLUMBING REVIEW**DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. WOULD YOU PLEASE SUBMIT TOTAL DYNAMIC HEAD
 CALCULATIONS FOR THE MAXIMUM SYSTEM FLOW COMPONENTS. IT
 REQUIRES THAT THE MAXIMUM SYSTEM FLOW RATE DOES NOT
 EXCEED THE LISTED MAXIMUM FLOW RATE OF THE SUCTION
 OUTLET FITTING ASSEMBLY (DRAIN COVER). THE TDH
 CALCULATIONS MUST INCLUDE ALL THE SYSTEM COMPONENTS,
 INCLUDING SUCTION AND RETURN PIPING, FITTINGS, VALVES,
 HEATER, FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS
 EXCEPT THE PUMP PER THE ANSI/APSP/ICC 7 - 2015 SECS.
 4.4.9, 4.4.9.1 MAXIMUM SYSTEM FLOW RATE?UNSECURED
 CONTROL SYSTEMS.
  
 2. INDICATE ON THE PUMP CURVE WHICH CURVE KEY IS FOR
 THE PUMP BEING INSTALLED ON THIS SYSTEM PER THE WPB
 AMEND. TO FBC SEC. 107.2.1.
  
 3. ALL POOL HEATERS SHALL BE EQUIPPED WITH A READILY
 ACCESSIBLE ON-OFF SWITCH THAT IS MOUNTED OUTSIDE THE
 HEATER TO ALLOW SHUTTING OFF THE HEATER WITHOUT
 ADJUSTING THE THERMOSTAT SETTING PER THE 2020
 FBC-ENERGY ? SEC. R403.10.1
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  