Date |
Text |
2022-09-16 10:49:23 | FAILED |
| |
| 1) PROVISO: PRIOR TO ISSUANCE OF THE FIRST CERTIFICATE |
| OF OCCUPANCY FOR THE BUILDING, YOU MUST SUBMIT TWO |
| COPIES OF THE AS BUILT PLANS FOR THE SHEETS CITED IN |
| RESOLUTION 13-19 TO CLOSE OUT THE MINOR PLANNED |
| DEVELOPMENT AMENDMENT |
| |
| 2) PROVISO: ANY PERMITS THAT ARE NOT CLOSED WILL NEED |
| TO INCLUDE THE MOST RECENT PLANS TO BE SUBMITTED AS |
| PART OF A PERMIT REVISION TO ENSURE CONSISTENCY. |
| |
| 3) UPDATED COMMENT: THE NORTH/SOUTH INSIDE DIMENSION OF |
| LEVEL B2 (SHEET A1.1B1) HAS BEEN REDUCED BY |
| APPROXIMATELY 20 INCHES WHEN COMPARED TO THE APPROVED |
| FOUNDATION PERMIT AND THE LAST SET OF PLANS THAT STAFF |
| REVIEWED AS PART OF THE MINOR PLANNED DEVELOPMENT |
| AMENDMENT. THE DIMENSION LINES VERIFYING THE 24-FOOT |
| DRIVE AISLE AND 18-FOOT PARKING SPACE DEPTH FOR THE |
| ENTIRE GARAGE NEED TO BE INCLUDED ON THE PLAN SO THAT |
| STAFF CAN VERIFY THAT THE SPACES AND AISLES STILL MEET |
| CODE MINIMUMS. |
| |
| 4) SHEET A1.100 SHOWS THE DIMENSION FROM THE AMENITY |
| DECK TO THE EASTERN PROPERTY LINE AS 9 FEET 11.5 |
| INCHES. THE VARIANCE GRANTED BY RESOLUTION NO. 13-19 |
| REQUIRES A 10-FOOT SETBACK AT THIS LOCATION. IT APPEARS |
| THAT THE PROPERTY LINE GETS CLOSER TO THE BUILDING AT |
| THE INSIDE CORNER, WHICH CAUSES IT TO BE LESS THAN 10 |
| FEET (WHICH IS SHOWN ON SHEET A1.102 AT A FURTHER NORTH |
| MEASURE POINT). |
| |
| 5) THERE ARE DISCREPANCIES BETWEEN SHEETS A1.100 AND |
| A1.101. EX. SITE LAYOUT AROUND GENERATOR AND MORE FPL |
| TRANSFORMERS SHOWN ON SHEET 1.100. ADDITIONALLY, WHERE |
| SHOWN, THE SETBACK DIMENSIONS DO NOT MATCH. ALL SHEETS |
| MUST SHOW CONSISTENT, CODE COMPLIANT, ACCURATE PLANS. |
| |
| 6) UPDATED COMMENT: THANK YOU FOR PROVIDING THE UPDATED |
| ELEVATION DRAWINGS. PLEASE SEE THE ITEMS LISTED BELOW. |
| ALL SHEETS MUST SHOW CONSISTENT, CODE COMPLIANT, |
| ACCURATE PLANS. |
| |
| A. SHEET A3.100 (NORTH ELEVATION) SHOWS CONFLICTING |
| WESTERN SETBACKS AT LEVEL 2 AND 5. THE LEVEL 2 SETBACK |
| DIMENSION DOES NOT COMPLY WITH THE VARIANCE GRANTED BY |
| RESOLUTION NO. 13-19. |
| B. SHEET A3.102 (WEST AND EAST ELEVATIONS) SHOWS |
| AMENITY FLOORS 2 AND 3 SETBACKS NOT COMPLYING WITH THE |
| VARIANCE GRANTED BY RESOLUTION NO. 13-19. |
| C. SHEET A3.102 (WEST ELEVATION) SHOWS THE GROUND FLOOR |
| SETBACK NOT COMPLYING WITH THE VARIANCE GRANTED BY |
| RESOLUTION NO. 13-19. |
| |
| 7) THE FOLLOWING ITEMS REQUIRE REVIEW AS SEPARATE |
| PERMITS WITH PLANS: |
| |
| A. THE WALLS, FENCES, GATES AND COLUMNS |
| B. HARDSCAPE, INCLUDING PAVERS, ARTIFICIAL TURF, DOG |
| PARK ITEMS, BENCHES/PLAZA AREA, ETC. |
| C. LANDSCAPE |
| D. IRRIGATION |
| E. GENERATOR |
| F. WATER FEATURES |
| G. PARKING STRIPING |
| H. SITE LIGHTING, INCLUDING BOLLARDS, NOTE: SINCE |
| ACACIA ROAD IS A SEPARATE PARCEL, IT REQUIRES ITS OWN |
| PERMIT FOR THE LIGHTING, BUT MAY BE INCLUDED ON ONE SET |
| OF PLANS FOR BOTH PERMIT NUMBERS. PHOTOMETRIC PLANS ARE |
| REQUIRED WITH THE PERMITS. |
| I. BICYCLE RACKS, INCLUDES WITHIN THE BICYCLE STORAGE |
| ROOM. |
| J. EV CHARGING STATIONS |
| |
| CONTACT ERIC SCHNEIDER @ (561) 822-1446 |
| [email protected] |
| |