2022-08-22 09:01:07 | 4TH REVIEW FMC |
| PERMIT: 21071625 |
| |
| CODES IN EFFECT: 2020 |
| |
| FBC- FLORIDA BUILDING CODE |
| FMC- FLORIDA MECHANICAL CODE |
| FEC- FLORIDA ENERGY CONSERVATION |
| FGC- FLORIDA FUEL GAS |
| FEX- FLORIDA EXISTING BUILDING CODE |
| FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| F.S.- FLORIDA STATUTES |
| FAC- FLORIDA ACCESSIBILITY CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| THANK YOU FOR THE COMMENTS SUBMITTED IN THIS LATEST |
| REVIEW CYCLE. I WILL TRY TO EXPLAIN IN THIS RESPONSE |
| WHY YOU MUST COMPLY WITH THE CODE SECTION 403.3.1.1 AND |
| TABLE 403.3.1.1 OR PROVIDE APPROVED (BY THE CODE |
| OFFICIAL) STATISTICAL DATA. A LETTER FROM THE ENGINEER |
| AND THE ARCHITECT STATING THAT THESE AREAS ARE PRIVATE |
| IS NOT ACCEPTABLE TO THIS REVIEWER AS NEITHER OF YOU |
| HAVE CONTROL OF THE USE OF THESE AREAS. |
| THIS BUILDING IS A 25 STORY BUILDING OF CONDO?S TO BE |
| SOLD. THE OWNER?S OF THESE CONDO?S WILL HAVE FRIENDS |
| AND FAMILY OVER. THIS WILL EFFECT THE OCCUPANT COUNT OF |
| THESE AREAS. IN THE ENGINEER?S LETTER THE FURNITURE IS |
| BEING CALLED PERMANENT. I SEE NO WAY OF CALLING THE |
| FURNITURE PERMANENT AS IT IS NOT SECURED IN PLACE AND |
| COULD BE MOVED OR ADDED TO. AGAIN THE ARCHITECT OR |
| ENGINEER HAS NO CONTROL OF THIS BUILDING AND HOW THE |
| FURNITURE WILL BE MAINTAINED. |
| THE LOUNGE AREAS SHOW FURNITURE DESIGNS MUCH LIKE YOU |
| COULD FIND IN A RESIDENCE. THIS TYPE OF FURNITURE DOES |
| WEAR OUT AND WOULD NEED TO BE REPLACED AT SOME POINT. |
| THERE IS ROOM IN EACH OF THESE AREAS TO INSTALL MORE |
| FURNITURE, MORE FURNITURE EQUALS MORE PEOPLE. THERE ARE |
| AREAS IN EACH SPACE WHERE OCCUPANTS COULD STAND. |
| AS WE KNOW THE CODE COMMENTARY IS NOT ENFORCEABLE BUT |
| ONLY AN EXPLANATION AS TO THE INTENT OF THE CODE. I |
| HAVE QUOTED THE 2018 IMC COMMENTARY BELOW THAT STATES |
| YOU MUST MEET MINIMUMS TO JUSTIFY NOT USING TABLE |
| 403.3.1.1, IN THIS LATEST REVIEW CYCLE YOU HAVE NOT |
| DONE SO. |
| |
| IMC CODE COMMENTARY: |
| ?THE EXCEPTION ALLOWS THE OCCUPANT LOAD FOR VENTILATION |
| TO BE BASED ON THE ACTUAL OCCUPANT FOR WHICH THE SPACE |
| IS DESIGNED WHERE IT CAN BE SHOWN TO THE CODE |
| OFFICIAL?S SATISFACTION THAT THE OCCUPANT LOAD IS |
| REALISTIC. THE OCCUPANT DENSITY ENTRIES IN TABLE |
| 403.3.1.1 ARE BASED ON EMPIRICAL DATA AND ARE |
| REASONABLY ACCURATE FOR THE TYPICAL CASES IN EACH TYPE |
| OF OCCUPANCY. SUFFICIENT DOCUMENTATION MUST BE |
| SUBMITTED TO THE CODE OFFICIAL TO JUSTIFY ANY DEVIATION |
| FROM THE PRESCRIBED OCCUPANT DENSITIES. |
| |
| 2) SHEET M2.102D: THE ADDED EXHAUST FAN EF-8 IN THE |
| WARMING KITCHEN, THE TERMINATION LOCATION MUST BE A |
| MINIMUM OF 10 FEET FROM THE OUTDOOR AIR INTAKE. FMC |
| 501.3.1 NUMBER 3 |
| |
| 1) PLEASE SEE THE 2ND CYCLE REVIEW COMMENT BELOW: |
| |
| 1) PLEASE USE FMC 403.3.1.1 3RD SENTENCE AND TABLE |
| 403.3.1.1 TO DETERMINE THE OCCUPANCY CLASSIFICATION |
| USED TO PROVIDE THE OUTDOOR AIR FOR EACH USE OF SPACE. |
| THE ARCHITECTS EGRESS OCCUPANT COUNT CANNOT BE USED TO |
| DETERMINE THE OUTDOOR AIR NEEDED FOR THE OCCUPANCY |
| CLASSIFICATION. PLEASE NAME EACH SPACE PER THE CLOSEST |
| OCCUPANCY CLASSIFICATION OF TABLE 403.3.1.1 AND PROVIDE |
| THE OUTDOOR AIR CALCULATIONS USING THE TABLE 403.3.1.1 |
| AND NOT THE ARCHITECTS EGRESS OCCUPANT COUNTS. EXAMPLE: |
| BUSINESS/MEETING COULD BE A CONFERENCE ROOM WHICH IF |
| USING THE CALCULATIONS IN TABLE 403.3.1.1 WOULD REQUIRE |
| 149 CFM OF OUTDOOR AIR. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |