2022-06-01 17:15:04 | 1) IF THE ENGINEER OF RECORD WOULD LIKE TO USE THE |
| EXCEPTION TO FMC 403.3.1.1 THEY WOULD NEED TO SUBMIT |
| THE STATISTICAL DATA TO THE BUILDING OFFICIAL TO |
| APPROVE OR DENY. |
| |
| 2) THE TREATMENT ROOM, BARBER AREA WILL NEED 61 CFM?S |
| OF EXHAUST. FMC TABLE 403.3.1.1 |
| |
| 3) THE DRESSING ROOMS WILL REQUIRE EXHAUST AIR. THE 477 |
| SQ FT WILL NEED 119 CFM?S AND THE 328 SQ. FT. WILL NEED |
| 82 CFM?S FMC TABLE 403.3.1.1 |
| |
| 4) THE CHANGING ROOMS ON SHEET M2.103D WILL NEED |
| EXHAUST. THE 30 SF CHANGING ROOM WILL REQUIRE 8 CFM?S |
| EXHAUST AND THE 27SF CHANGING ROOM WILL REQUIRE 7 CFM?S |
| EXHAUST. FMC TABLE 403.3.1.1 |
| |
| 5) WHY IS THE DINING ROOM BEING CLASSIFIED AS A |
| LOBBY/PREFUNCTION? THE DINING ROOM WILL REQUIRE 723 |
| CFM?S OF OUTDOOR AIR. |
| |
| 6) THE WARMING KITCHEN/BREAKROOM WILL REQUIRE OUTDOOR |
| AIR AND EXHAUST. |
| |
| 7) SHEET M2.101D: THE OFFICE AND MAILROOM WILL REQUIRE |
| OUTDOOR AIR BUT THE FCU-2 SUPPLYING THIS AREA DOES NOT |
| SHOW AN OUTDOOR AIR DUCT AT THE RETURN. |
| |
| 8) THE MEN?S AND WOMEN?S SPAS WILL REQUIRE OUTDOOR AIR. |
| FMC 403.3.1.1 |
| VENTILATION RATES FOR OCCUPANCIES NOT REPRESENTED IN |
| TABLE 403.3.1.1 SHALL BE THOSE FOR A LISTED OCCUPANCY |
| CLASSIFICATION THAT IS MOST SIMILAR IN TERMS OF |
| OCCUPANT DENSITY, ACTIVITIES AND BUILDING |
| CONSTRUCTION; OR SHALL BE DETERMINED BY AN APPROVED |
| ENGINEERING ANALYSIS. |
| |