Plan Review Notes
Plan Review Notes For Permit 21071625
Permit Number 21071625
Review Stop Z
Sequence Number 2
Notes
Date Text
2022-05-17 15:24:36FAILED
  
 REPEAT COMMENT: PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) THE PLANS SUBMITTED WITH THIS TOWER PERMIT DO NOT
 MATCH THE PLANS THAT HAVE BEEN APPROVED AS PART OF THE
 LATEST MINOR PLANNED DEVELOPMENT AMENDMENT OR THE
 APPROVED FOUNDATION PERMIT. THE REPEAT COMMENTS WILL
 CONTINUE TO BE ISSUED UNTIL THE PLANS ALIGN AND MEET
 ZONING REQUIREMENTS.
  
 2) REPEAT COMMENT: IN ACCORDANCE WITH RESOLUTION NO.
 13-19, PROVIDE VERIFICATION THAT ALL SURFACES OF THE
 BUILDING'S EXTERIOR FACADE, TO INCLUDE GLAZING, ARE
 DESIGNED OR TREATED TO MINIMIZE THE IMPACTS OF GLARE
 AND REFLECTION OF HIGH INTENSITY LIGHT FROM THE
 BUILDING'S FACADE ONTO SURROUNDING PROPERTIES.
  
 3) REPEAT COMMENT: IN ACCORDANCE WITH RESOLUTION NO.
 13-19, PROVIDE VERIFICATION THAT THE DEVELOPER HAS
 CONTRACTED WITH AN INDEPENDENT PROFESSIONAL THAT IS
 ACCREDITED IN THE SPECIFIC CERTIFICATION BEING UTILIZED
 TO MEET THIS DEVELOPMENT REGULATION TO ACT AS A GREEN
 DEVELOPMENT REVIEW AGENT TO ENSURE THAT THE BUILDING
 WILL BE CONSTRUCTED IN ACCORDANCE WITH A CERTIFICATION
 PLAN THAT ACHIEVES TO A MINIMUM LEED SILVER LEVEL, OR
 EQUIVALENT GREEN BUILDING STANDARD.
  
 4) REPEAT COMMENT: PROVIDE AN FAA EXTENSION LETTER FOR
 THE BUILDING. THE LETTER THAT STAFF HAS ON FILE EXPIRED
 IN JANUARY 2022.
  
 5) REPEAT COMMENT: SHEET 00.200 REFERENCES SAUNA SQUARE
 FOOTAGE ON THE ROOF LEVEL. ROOFTOP SAUNAS ARE
 CONSIDERED AMENITIES AND ARE NOT PERMITTED TO EXCEED
 THE HEIGHT OF THE ROOF DECK (300 FEET). ALL SAUNA
 REFERENCES AND FACILITIES MUST BE REMOVED FROM THE
 ENTIRE PLAN SET.
  
 6) REPEAT COMMENT: THE SURVEY PROVIDED A S-1-00 IS NOT
 THE LATEST SURVEY THAT WAS SUBMITTED WITH THE
 FOUNDATION PERMIT. THE LATEST, ACCURATE SURVEY IS
 REQUIRED TO BE INCLUDED WITH THE PLANS.
  
 7) REPEAT COMMENT: THE CIVIL PLANS ARE NOT THE LATEST
 VERSION THAT WAS SUBMITTED WITH THE RECENT FOUNDATION
 PERMIT RESUBMITTAL. ALL PERMITS NEED TO INCLUDE THE
 SAME LATEST, ACCURATE PLANS.
  
 8) REPEAT COMMENT: THE PLANS APPROVED AS PART OF THE
 MINOR PLANNED DEVELOPMENT AMENDMENT SHOW THE WEST
 SETBACK DIMENSION OF 5 FEET 6 INCHES FOR THE GENERATOR
 PIT, WHICH WAS ALSO REFLECTED ON THE APPROVED
 FOUNDATION PERMIT. THIS PERMIT SHOWS A 5 FOOT 3 INCH
 WEST SETBACK. ALL PERMITS NEED TO INCLUDE THE SAME
 LATEST, ACCURATE PLANS. (OCCURS ON SHEETS A1.100 AND
 A1.1B1)
  
 9) REPEAT COMMENT: SHEET A1.1B1 IS NOT THE LATEST
 VERSION OF THIS PLAN SUBMITTED WITH THE RECENT
 FOUNDATION PERMIT RESUBMITTAL. ALL PERMITS NEED TO
 INCLUDE THE SAME LATEST, ACCURATE PLANS. *** SEE
 SETBACK COMMENT ABOVE.
  
 10) PLEASE EXPLAIN HOW THE BUILDING INCREASED FROM A
 NORTH/SOUTH DIMENSION OF 137 FEET 5 INCHES ON THE
 FOUNDATION PLAN TO 137 FEET 9 INCHES ON THE TOWER PLAN
 WITHOUT IMPACTING THE SIDE SETBACKS? NOTE THE MINIMUM
 SETBACKS MUST BE MAINTAINED.
  
 11) REPEAT COMMENT: THE GROUND LEVEL BUILDING PLAN DOES
 NOT MATCH THE VERSION APPROVED AS PART OF THE
 FOUNDATION PERMIT (LIFE SAFETY) NOR OF THE PLANS
 APPROVED AS PART OF THE MINOR PLANNED DEVELOPMENT
 AMENDMENT. ALL PERMITS NEED TO INCLUDE THE SAME LATEST,
 ACCURATE PLANS. NOTE: THE DIMENSION LINES LISTED TO THE
 COLUMNS DO NOT ACTUALLY REACH THE COLUMNS.
  
 12) REPEAT COMMENT: PROVIDE THE SETBACKS FROM THE FACE
 OF GLASS TO THE PROPERTY LINE FOR EACH FLOOR PLAN. THIS
 WAS SHOWN ON THE MINOR PLANNED DEVELOPMENT AMENDMENT
 PLAN.
  
 13) REPEAT COMMENT: THE ELEVATION DRAWINGS DO NOT MATCH
 THE ONES APPROVED AS PART OF THE MINOR PLANNED
 DEVELOPMENT AMENDMENT. ALL PERMITS NEED TO INCLUDE THE
 SAME LATEST, ACCURATE PLANS.
  
 14) THE FOLLOWING ITEMS REQUIRE REVIEW AS SEPARATE
 PERMITS WITH PLANS:
  
 A. THE WALLS, FENCES, GATES AND COLUMNS
 B. HARDSCAPE, INCLUDING PAVERS, ARTIFICIAL TURF, DOG
 PARK ITEMS, BENCHES/PLAZA AREA, ETC.
 C. LANDSCAPE
 D. IRRIGATION
 E. GENERATOR
 F. WATER FEATURES
 G. PARKING STRIPING
 H. SITE LIGHTING, INCLUDING BOLLARDS, NOTE: SINCE
 ACACIA ROAD IS A SEPARATE PARCEL, IT REQUIRES ITS OWN
 PERMIT FOR THE LIGHTING, BUT MAY BE INCLUDED ON ONE SET
 OF PLANS FOR BOTH PERMIT NUMBERS. PHOTOMETRIC PLANS ARE
 REQUIRED WITH THE PERMITS.
 I. BICYCLE RACKS, INCLUDES WITHIN THE BICYCLE STORAGE
 ROOM.
 J. EV CHARGING STATIONS
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  