2022-05-17 15:24:36 | FAILED |
| |
| REPEAT COMMENT: PROVIDE WRITTEN RESPONSES TO COMMENTS. |
| |
| 1) THE PLANS SUBMITTED WITH THIS TOWER PERMIT DO NOT |
| MATCH THE PLANS THAT HAVE BEEN APPROVED AS PART OF THE |
| LATEST MINOR PLANNED DEVELOPMENT AMENDMENT OR THE |
| APPROVED FOUNDATION PERMIT. THE REPEAT COMMENTS WILL |
| CONTINUE TO BE ISSUED UNTIL THE PLANS ALIGN AND MEET |
| ZONING REQUIREMENTS. |
| |
| 2) REPEAT COMMENT: IN ACCORDANCE WITH RESOLUTION NO. |
| 13-19, PROVIDE VERIFICATION THAT ALL SURFACES OF THE |
| BUILDING'S EXTERIOR FACADE, TO INCLUDE GLAZING, ARE |
| DESIGNED OR TREATED TO MINIMIZE THE IMPACTS OF GLARE |
| AND REFLECTION OF HIGH INTENSITY LIGHT FROM THE |
| BUILDING'S FACADE ONTO SURROUNDING PROPERTIES. |
| |
| 3) REPEAT COMMENT: IN ACCORDANCE WITH RESOLUTION NO. |
| 13-19, PROVIDE VERIFICATION THAT THE DEVELOPER HAS |
| CONTRACTED WITH AN INDEPENDENT PROFESSIONAL THAT IS |
| ACCREDITED IN THE SPECIFIC CERTIFICATION BEING UTILIZED |
| TO MEET THIS DEVELOPMENT REGULATION TO ACT AS A GREEN |
| DEVELOPMENT REVIEW AGENT TO ENSURE THAT THE BUILDING |
| WILL BE CONSTRUCTED IN ACCORDANCE WITH A CERTIFICATION |
| PLAN THAT ACHIEVES TO A MINIMUM LEED SILVER LEVEL, OR |
| EQUIVALENT GREEN BUILDING STANDARD. |
| |
| 4) REPEAT COMMENT: PROVIDE AN FAA EXTENSION LETTER FOR |
| THE BUILDING. THE LETTER THAT STAFF HAS ON FILE EXPIRED |
| IN JANUARY 2022. |
| |
| 5) REPEAT COMMENT: SHEET 00.200 REFERENCES SAUNA SQUARE |
| FOOTAGE ON THE ROOF LEVEL. ROOFTOP SAUNAS ARE |
| CONSIDERED AMENITIES AND ARE NOT PERMITTED TO EXCEED |
| THE HEIGHT OF THE ROOF DECK (300 FEET). ALL SAUNA |
| REFERENCES AND FACILITIES MUST BE REMOVED FROM THE |
| ENTIRE PLAN SET. |
| |
| 6) REPEAT COMMENT: THE SURVEY PROVIDED A S-1-00 IS NOT |
| THE LATEST SURVEY THAT WAS SUBMITTED WITH THE |
| FOUNDATION PERMIT. THE LATEST, ACCURATE SURVEY IS |
| REQUIRED TO BE INCLUDED WITH THE PLANS. |
| |
| 7) REPEAT COMMENT: THE CIVIL PLANS ARE NOT THE LATEST |
| VERSION THAT WAS SUBMITTED WITH THE RECENT FOUNDATION |
| PERMIT RESUBMITTAL. ALL PERMITS NEED TO INCLUDE THE |
| SAME LATEST, ACCURATE PLANS. |
| |
| 8) REPEAT COMMENT: THE PLANS APPROVED AS PART OF THE |
| MINOR PLANNED DEVELOPMENT AMENDMENT SHOW THE WEST |
| SETBACK DIMENSION OF 5 FEET 6 INCHES FOR THE GENERATOR |
| PIT, WHICH WAS ALSO REFLECTED ON THE APPROVED |
| FOUNDATION PERMIT. THIS PERMIT SHOWS A 5 FOOT 3 INCH |
| WEST SETBACK. ALL PERMITS NEED TO INCLUDE THE SAME |
| LATEST, ACCURATE PLANS. (OCCURS ON SHEETS A1.100 AND |
| A1.1B1) |
| |
| 9) REPEAT COMMENT: SHEET A1.1B1 IS NOT THE LATEST |
| VERSION OF THIS PLAN SUBMITTED WITH THE RECENT |
| FOUNDATION PERMIT RESUBMITTAL. ALL PERMITS NEED TO |
| INCLUDE THE SAME LATEST, ACCURATE PLANS. *** SEE |
| SETBACK COMMENT ABOVE. |
| |
| 10) PLEASE EXPLAIN HOW THE BUILDING INCREASED FROM A |
| NORTH/SOUTH DIMENSION OF 137 FEET 5 INCHES ON THE |
| FOUNDATION PLAN TO 137 FEET 9 INCHES ON THE TOWER PLAN |
| WITHOUT IMPACTING THE SIDE SETBACKS? NOTE THE MINIMUM |
| SETBACKS MUST BE MAINTAINED. |
| |
| 11) REPEAT COMMENT: THE GROUND LEVEL BUILDING PLAN DOES |
| NOT MATCH THE VERSION APPROVED AS PART OF THE |
| FOUNDATION PERMIT (LIFE SAFETY) NOR OF THE PLANS |
| APPROVED AS PART OF THE MINOR PLANNED DEVELOPMENT |
| AMENDMENT. ALL PERMITS NEED TO INCLUDE THE SAME LATEST, |
| ACCURATE PLANS. NOTE: THE DIMENSION LINES LISTED TO THE |
| COLUMNS DO NOT ACTUALLY REACH THE COLUMNS. |
| |
| 12) REPEAT COMMENT: PROVIDE THE SETBACKS FROM THE FACE |
| OF GLASS TO THE PROPERTY LINE FOR EACH FLOOR PLAN. THIS |
| WAS SHOWN ON THE MINOR PLANNED DEVELOPMENT AMENDMENT |
| PLAN. |
| |
| 13) REPEAT COMMENT: THE ELEVATION DRAWINGS DO NOT MATCH |
| THE ONES APPROVED AS PART OF THE MINOR PLANNED |
| DEVELOPMENT AMENDMENT. ALL PERMITS NEED TO INCLUDE THE |
| SAME LATEST, ACCURATE PLANS. |
| |
| 14) THE FOLLOWING ITEMS REQUIRE REVIEW AS SEPARATE |
| PERMITS WITH PLANS: |
| |
| A. THE WALLS, FENCES, GATES AND COLUMNS |
| B. HARDSCAPE, INCLUDING PAVERS, ARTIFICIAL TURF, DOG |
| PARK ITEMS, BENCHES/PLAZA AREA, ETC. |
| C. LANDSCAPE |
| D. IRRIGATION |
| E. GENERATOR |
| F. WATER FEATURES |
| G. PARKING STRIPING |
| H. SITE LIGHTING, INCLUDING BOLLARDS, NOTE: SINCE |
| ACACIA ROAD IS A SEPARATE PARCEL, IT REQUIRES ITS OWN |
| PERMIT FOR THE LIGHTING, BUT MAY BE INCLUDED ON ONE SET |
| OF PLANS FOR BOTH PERMIT NUMBERS. PHOTOMETRIC PLANS ARE |
| REQUIRED WITH THE PERMITS. |
| I. BICYCLE RACKS, INCLUDES WITHIN THE BICYCLE STORAGE |
| ROOM. |
| J. EV CHARGING STATIONS |
| |