Plan Review Notes
Plan Review Notes For Permit 21071625
Permit Number 21071625
Review Stop P
Sequence Number 2
Notes
Date Text
2022-03-31 09:12:3803/31/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE NOW,
 AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET 00.002; PAGES ARE MISSING FROM THE PLUMBING
 INDEX AS FOLLOWS;
  
 P2.126
 P3.105
 P3.206
 P3.207
 P3.208
 P3.209
 P3.210
 P3.300
 P3.301
 P3.302
 P3.303
 P3.304
 NOT BEEN UPDATED
  
 2. DONE
  
 3. DONE
  
 4. ON SHEET 00.205;
  
 A. SECOND REQUEST, FOR THE COMMENT, SHOWS NUMBER #1 BUT
 NO INFORMATION ON THE 34??THE FHA NOTES TALK ABOUT
 SPECIFICATION B AND NO MENTION ON THE LAV TO BE AT 34"
 PER 7.52 OF THE FHA DESIGN MANUAL.
  
 B. SECOND REQUEST, FOR THE COMMENT, IT SHOWS NUMBER #8
 BUT NO INFORMATION ON THE NOTE?THE PENTHOUSE IS A
 FUTURE BUILD-OUT AND, IN THIS WAY, ESTABLISHED IN THE
 BUILDING DEPARTMENT THAT THE POWDER ROOM IS FOR THE
 CONSTRUCTION WORKER. WOULD YOU PLEASE ADD A NOTE OF
 THIS ON THE PAGE UNDER FAIR HOUSING ITEM #8 PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 5. DONE
  
 6. ON SHEET 00.207;
  
 A. DONE
  
 B. DONE
  
 C. DONE
  
 D. SECOND REQUEST, THE DRAWING IS CORRECT, BUT THE
 VERBIAGE IS NOT? ON NUMBER 77, IT REFERS TO THE
 DISPENSER BEING 12 AND SHALL BE 7 INCHES MINIMUM AND 9
 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER PER THE 2017 FBC ACC
 SEC. 604.7. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 E. DONE
  
 F. DONE
  
 G. DONE
  
 I. DONE
  
 7. ON SHEET 00.210;
  
 A. UNDER GENERAL REQUIREMENTS, IT HAS BOTH THE
 GUIDELINES AND THE DESIGN MANUAL, TWO DIFFERENT SAFE
 HARBORS, AND ONLY ONE SHOULD BE NOTED. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS? THERE ARE EIGHT
 SAFE HARBORS FOR COMPLIANCE WITH THE FAIR HOUSING ACT.
 COMPLIANCE WITH ANY ONE OF THE ELEVEN WILL FULFILL THE
 FAIR HOUSING ACT'S ACCESS REQUIREMENTS. IF A PARTICULAR
 SAFE HARBOR IS CHOSEN FOR USE IN A PARTICULAR PROPERTY,
 HOUSING MUST COMPLY WITH ALL OF THE PROVISIONS OF THAT
 SAFE HARBOR FOR THERE TO BE A SAFE HARBOR. SO IT IS
 UNWISE TO PICK AND CHOOSE AMONG THE PROVISIONS OF
 DIFFERENT SAFE HARBOR STANDARDS.
 THIS COMMENT IS NOT ANSWERED, AND PUTTING IT ON THE
 PLAN DOES NOT ANSWER THE COMMENT. PICK THE SAFE HARBOR
 USED FOR FHA AND PUT IT UNDER GENERAL REQUIREMENTS.
  
 B. DONE
  
 C. DONE
  
 D. DONE
  
 8. DONE
  
 9. ON SHEET A1.1B1,
  
 A. DONE
  
 B. DONE
  
 C. DONE
  
 10. ON SHEET A-100;
  
 A. DONE
  
 B. DONE
  
 C. DONE
  
 D. DONE
  
 E. DONE
  
 F. DONE
  
 11. ON SHEET A-101;
  
 A. DONE
  
 B. DONE
  
 12. ON SHEET A-102;
  
 A. DONE
  
 B. DONE
  
 C. DONE
  
 13. ON SHEET A-103;
  
 A. DONE WITH NEW COMMENT-ON THE GUEST ROOM #2 BATH
 SHOWER DOES NOT COMPLY WITH THE 2020 FBC ACC SEC.
 608.2. SHOWER COMPARTMENTS. PLEASE SHOW THE CLEAR FLOOR
 SPACE PER THE 2017 FBC ACC SEC. 606.2. 2 CLEAR FLOOR
 SPACE. HOW WILL THE GRAB BARS COMPLY PER THE 2020 FBC
 ACC SEC. 608.2. PLEASE SHOW THE TURNING RADIUS SPACE OF
 FIVE FEET 603.2.1, 304.3.1 CIRCULAR SPACE.
  
 WHERE IS THE DETAIL FOR THE SHOWER AND GRAB BARS? WOULD
 YOU PLEASE SHOW THE CLEAR FLOOR SPACE IN FRONT OF THE
 SHOWER PER THE 2017 FBC ACC SEC. 608.2.1.
  
 B. DONE
  
 C. DONE
  
 D. DONE
  
 E. DONE
  
 14. ON SHEETS A1.104, 105, AND 124;
  
 A. SECOND REQUEST, WOULD YOU PLEASE IDENTIFY THE FHA
 UNITS AND SHOW THE CLEAR FLOOR SPACE FOR LAV, SHOWER,
 TUB, AND TOILET PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. DONE
  
 15. DONE
  
 16. ON SHEET A1.125;
  
 A. DONE
  
 B. DONE WITH NEW COMMENT. THERE IS A GAS GRILL; PLEASE
 IDENTIFY TANK PROPANE OR A GAS SYSTEM PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 WOULD YOU PLEASE PUT THAT THE BBQ WILL BE ELECTRIC PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 C. DONE
  
 17. ON SHEETS A1.204, 205, 206, 207, 208, 209, 210,
 300, 301, 302, 303, AND 304, PLEASE IDENTIFY THE
 BATHROOM WHICH IS THE FHA AND SHOW CLEAR FLOOR SPACE
 FOR ALL FIXTURES PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. WOULD
 YOU PLEASE PROVIDE DIMENSIONS FOR FIXTURES PER THE 2020
 FBC SEC. 405.3.1.
  
 18. ON SHEET A1.306;
  
 A. DONE
  
 B. DONE
  
 C. SECOND REQUEST, WOULD YOU PLEASE SHOW OR POINT TO
 THE PAGE WHERE THE SEAT REINFORCES VERTICAL OR
 HORIZONTAL FORCE OF 250 POUNDS IS APPLIED ON THE SEAT,
 FASTENER, MOUNTING DEVICE, OR SUPPORTING STRUCTURE PER
 THE 2020 FBC ACC SEC. 610.4 STRUCTURAL STRENGTH.
 PLEASE PUT A NOTE ON PLANS PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 D. SECOND REQUEST, ON DETAIL #3, WOULD YOU PLEASE SHOW
 THE GRAB BARS TO THE TOP OF THE GRIPPING SURFACE PER
 THE 2020 FBC ACC SEC. 609.4.
  
 E. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO
 A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
 NEW COMMENTS A0.207 AND A0.208 DO NOT EXIST; 00.207 AND
 00.208 DO. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 19. ON SHEET A1.306A;
  
 A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO
 A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
 NEW COMMENTS A0.207 AND A0.208 DO NOT EXIST, 00.207 AND
 00.208 DO. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
 B. DONE
  
 C. DONE
  
 20. ON SHEET A1.307;
  
 A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO
 A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
 NEW COMMENTS A0.207 AND A0.208 DO NOT EXIST, 00.207 AND
 00.208 DO. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
 B. DONE
  
 C. DONE.
  
 21. ON SHEET A1.308;
  
 A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO
 A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. DONE
  
 22. ON SHEET A1.309;
  
 A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO
 A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
 NEW COMMENTS A0.207 AND A0.208 DO NOT EXIST, 00.207 AND
 00.208 DO. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. DONE
  
 23. ON SHEET A1.310;
  
 A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO
 A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
 NEW COMMENTS A0.207 AND A0.208 DO NOT EXIST, 00.207 AND
 00.208 DO. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. DONE
  
 24. ON SHEET A1.311;
  
 A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO
 A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
 NEW COMMENTS A0.207 AND A0.208 DO NOT EXIST, 00.207 AND
 00.208 DO. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. DONE
  
 25. ON SHEET A1.312, IT SAYS FOR ADA FIXTURES AND
 ACCESSORIES, REFER TO A0.004 AND A0.005 AND NO SUCH
 PAGE. WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS
 TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS?
 NEW COMMENTS A0.207 AND A0.208 DO NOT EXIST, 00.207 AND
 00.208 DO. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 26. ON SHEET A1.313;
  
 A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO
 A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
 NEW COMMENTS A0.207 AND A0.208 DO NOT EXIST, 00.207 AND
 00.208 DO. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. DONE WITH NEW COMMENT; ON DETAIL #1, WOULD YOU
 PLEASE SHOW THE CLEAR FLOOR SPACE DIAGRAM AND
 DIMENSIONS FOR THE WATER CLOSET, LAV, AND TURNING SPACE
 PER THE 2020 FBC ACC SEC. 606.2. 2 CLEAR FLOOR SPACE
 AND WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 NEW COMMENT, WOULD YOU PLEASE SHOW THE CLEAR FLOOR
 SPACE FOR THE SHOWER PER THE 202 FBC SEC. 608.2.1.
  
 C. DONE
  
 27. ON SHEET A1.314;
  
 A. DONE
  
 B. DONE
  
 C. ON DETAILS #7 AND #8. WOULD YOU PLEASE SHOW THE
 CLEAR FLOOR SPACE TO THE TUBS AND SHOWER PER THE FHA
 PAGE 7.43 AND THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 D. DONE
  
 E. DONE
  
 F. DONE
  
 G. DONE
  
 28. DONE
  
 29. DONE WITH NEW COMMENT. WOULD YOU PLEASE PROVIDE A
 PLUMBING PLAN INCLUDING THE SANITARY, CONDENSATE,
 STORM, AND WATER ISOMETRIC DRAWINGS PER THE WPB AMEND
 TO FBC 107.3.5.1.3(13)?
 NEW COMMENT, ON SHEET P5.104 ON THE THIRD TO
 FOUR-FLOOR, THE WATER, SHOWER ON A HORIZONTAL WET VENT,
 THE KITCHEN, AND THE RISER ON UPSTREAM. WOULD YOU
 PLEASE CORRECT PER THE 2020 FBC SEC. 2020 FBC SEC.
 912.1 HORIZONTAL WET VENT PERMITTED?
 ON SHEET P106, THE DRAINS FOR THE SUMP PIT ARE NOT
 SHOWING A FLOOR DRAIN ON THE GROUND FLOOR.
  
 30. ON SHEET P2.1B2;
  
 A. DONE WITH COMMENT; WOULD YOU PLEASE SHOW THE
 INDIRECT CONNECTION FOR THE ELEVATOR TO THE SANITARY ON
 THE PLUMBING DETAILS AND GIVE A REFERENCE PAGE NUMBER
 FOR IT PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 A WASTER RECEPTOR CONSISTS OF A FLOOR OR HUB DRAIN AND
 SHALL HAVE A TRAP AND A PRIMER. THE INDIRECT CONNECTION
 HAS TO BE DRAINED INTO A WASTE RECEPTOR SHALL BE
 TRAPPED AND VENTED, AND SHALL CONNECT TO THE BUILDING
 DRAINAGE SYSTEM PER THE 2017 FBC SEC 802.3. IF THE
 ELEVATOR IS NOT OIL-INDUCED, THEY MAY GO TO THE STORM,
 BUT A LOCAL ORDINANCE MAY NOT ALLOW IT.
  
 B. SECOND REQUEST, WOULD YOU PLEASE LABEL THE STAIRWELL
 AND ELEVATOR PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. DONE.
  
  
 31. ON SHEET P2.1B1;
  
 A. DONE
  
 B. DONE
  
 C. DONE
  
 D. DONE
  
 E. DONE
  
 F. DONE.
  
 32. ON SHEET P2.101;
  
 A. DONE
  
 B. DONE
  
 C. NOT FOUND AS PER COMMENT; HOT WATER LINES LOOPED FOR
 THE RECIRCULATING SYSTEM ARE NOT IN A CONTINUOUS LOOP.
 THERE IS A REQUIREMENT IN THE FLORIDA ENERGY CODE SEC.
 C404.6.1. THERE IS A TABLE THAT LIMITS THE BETWEEN THE
 SOURCE AND THE OUTLET; PLEASE REFER TO TABLE 404.5.1
 FOR THE MAXIMUM ALLOWABLE PIPE LENGTH METHOD AND SIZE
 ACCORDANTLY. THE COMMENT WILL APPLY TO ALL AND WHERE
 THERE IS A LOOP SYSTEM.
  
 33. ON SHEET P2.102;
  
 A. DONE.
  
 B. DONE
  
 C. DONE
  
 34. DONE
  
 35. DONE
  
 36. DONE
  
 37. ON SHEET P4.201;
  
 A. DONE.
  
 B. DONE
  
 C. DONE
  
 38. ON SHEET P5.101;
  
 A. DONE
  
 B. DONE.
  
 39. ON SHEET P5.103;
  
 A. DONE
  
 B. DONE.
  
 C. DONE
  
 D. DONE
  
 E. DONE
  
 40. ON SHEET P5.104;
  
 A. DONE
  
 B. DONE
  
 41. ON SHEET P5.106;
  
 A. DONE
  
 B. DONE
  
 42. DONE
  
 43. DONE
  
 44. ON SHEET P7.102;
  
 A. DONE
  
 B. DONE
  
 PLEASE FEEL FREE TO SET UP A MEETING OR CONTACT ME ON
 ANY OF THE COMMENTS BY PHONE OR ZOOM MEETING IF YOU
 LIKE TO PREVENT FURTHER REVIEWS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  