Plan Review Notes
Plan Review Notes For Permit 21071625
Permit Number 21071625
Review Stop E
Sequence Number 2
Notes
Date Text
2022-04-13 15:58:24FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NO MEANS TO BACK UP THE GENERATOR IS SHOWN ON THESE
 PLANS PER 700.3
  
 2) MAINS NOT LABLED AS 1 OF 6, 2 OF 6 AND SO FORTH.
 230.2.(E) PLEASE IDENTIFY ALL MAINS ON RISER DIAGRAM.
  
 3) LOAD CALCULATION ON DWELLING UNITS SHOW A VERY LIGHT
 LOAD FOR 4 ACS OR 4 HEAT STRIPS IN EACH UNIT. 215.5
  
 4) PANEL SCHEDULES TO BE MORE SPECIFIC. 408.4(A) A NOTE
 ON PLAN WILL BE GOOD.
  
 5) PANEL SCHEDULE NOT SHOWN FOR SUB PANELS (EMERGENCY)
 IN LIVING UNITS. 408.4(A)
  
 6) PLANS NEED TO NOTE SOURCE OF POWER IN ALL PANELS IN
 ALL UNITS AND OTHER SUB PANELS PER 408.4(B)
  
 7) MAINS 1200 AMPERES OR MORE SHALL BE INSTALLED PER
 240.87 FOR ARC ENERGY REDUCTION. 240.87
  
 8) FIRE PUMP WIRING IS INSTALLED WITH THE OTHER
 EMERGENCY WIRING, BUT 695.6(A)(2)(A) STATES ALL FIRE
 PUMP WIRING TO
 BE KEPT ENTIRELY INDEPENDENT OF OTHER WIRING?
  
 9) FIRE PUMP HAS A 450A BREAKER OR FUSE AHEAD OF THE
 CONTROLLER? THE SIZE WAS BASED ON WHAT? 695.4?