Text |
2022-02-09 18:19:43 | FAILED |
| |
| PROVIDE WRITTEN RESPONSES TO COMMENTS. |
| |
| 1) THE PLAT REQUIRED PRIOR TO BUILDING PERMIT BY |
| RESOLUTION NO. 13-19 HAS NOT BEEN RECORDED. |
| |
| 2) IN ACCORDANCE WITH RESOLUTION NO. 13-19, PROVIDE |
| VERIFICATION THAT ALL SURFACES OF THE BUILDING'S |
| EXTERIOR FACADE, TO INCLUDE GLAZING, ARE DESIGNED OR |
| TREATED TO MINIMIZE THE IMPACTS OF GLARE AND REFLECTION |
| OF HIGH INTENSITY LIGHT FROM THE BUILDING'S FACADE ONTO |
| SURROUNDING PROPERTIES. |
| |
| 3) IN ACCORDANCE WITH RESOLUTION NO. 13-19, PROVIDE |
| VERIFICATION THAT THE DEVELOPER HAS CONTRACTED WITH AN |
| INDEPENDENT PROFESSIONAL THAT IS ACCREDITED IN THE |
| SPECIFIC CERTIFICATION BEING UTILIZED TO MEET THIS |
| DEVELOPMENT REGULATION TO ACT AS A GREEN DEVELOPMENT |
| REVIEW AGENT TO ENSURE THAT THE BUILDING WILL BE |
| CONSTRUCTED IN ACCORDANCE WITH A CERTIFICATION PLAN |
| THAT ACHIEVES TO A MINIMUM LEED SILVER LEVEL, OR |
| EQUIVALENT GREEN BUILDING STANDARD. |
| |
| 4) PROVIDE AN FAA EXTENSION LETTER FOR THE BUILDING. |
| THE LETTER THAT STAFF HAS ON FILE EXPIRED IN JANUARY |
| 2022. |
| |
| 5) SHEET 00.200 REFERENCES SAUNA SQUARE FOOTAGE ON THE |
| ROOF LEVEL. ROOFTOP SAUNAS ARE CONSIDERED AMENITIES AND |
| ARE NOT PERMITTED TO EXCEED THE HEIGHT OF THE ROOF DECK |
| (300 FEET). ALL SAUNA REFERENCES AND FACILITIES MUST BE |
| REMOVED FROM THE ENTIRE PLAN SET. |
| |
| 6) THE SURVEY PROVIDED A S-1-00 IS NOT THE LATEST |
| SURVEY THAT WAS SUBMITTED WITH THE FOUNDATION PERMIT. |
| THE LATEST, ACCURATE SURVEY IS REQUIRED TO BE INCLUDED |
| WITH THE PLANS. |
| |
| 7) THE CIVIL PLANS ARE NOT THE LATEST VERSION THAT WAS |
| SUBMITTED WITH THE RECENT FOUNDATION PERMIT |
| RESUBMITTAL. ALL PERMITS NEED TO INCLUDE THE SAME |
| LATEST, ACCURATE PLANS. |
| |
| 8) THE PLANS APPROVED AS PART OF THE MINOR PLANNED |
| DEVELOPMENT AMENDMENT SHOW THE WEST SETBACK DIMENSION |
| OF 5 FEET 6 INCHES FOR THE GENERATOR PIT, WHICH WAS |
| ALSO REFLECTED ON THE RECENT FOUNDATION PERMIT. THIS |
| PERMIT SHOWS A 5 FOOT 3 INCH WEST SETBACK. ALL PERMITS |
| NEED TO INCLUDE THE SAME LATEST, ACCURATE PLANS. |
| |
| 9) SHEET A1.1B1 IS NOT THE LATEST VERSION OF THIS PLAN |
| SUBMITTED WITH THE RECENT FOUNDATION PERMIT |
| RESUBMITTAL. ALL PERMITS NEED TO INCLUDE THE SAME |
| LATEST, ACCURATE PLANS. |
| |
| 10) THE GROUND LEVEL BUILDING PLAN DOES NOT MATCH THE |
| VERSION SUBMITTED AS PART OF THE FOUNDATION PERMIT NOR |
| OF THE PLANS APPROVED AS PART OF THE MINOR PLANNED |
| DEVELOPMENT AMENDMENT. ALL PERMITS NEED TO INCLUDE THE |
| SAME LATEST, ACCURATE PLANS. |
| |
| 11) PROVIDE THE SETBACKS FROM THE FACE OF GLASS TO THE |
| PROPERTY LINE FOR EACH FLOOR PLAN. THIS WAS SHOWN ON |
| THE MINOR PLANNED DEVELOPMENT AMENDMENT PLAN. |
| |
| 12) THE ELEVATION DRAWINGS DO NOT MATCH THE ONES |
| APPROVED AS PART OF THE MINOR PLANNED DEVELOPMENT |
| AMENDMENT. ALL PERMITS NEED TO INCLUDE THE SAME LATEST, |
| ACCURATE PLANS. |
| |
| 13) THE BASEMENT PARKING ELECTRIC PLANS DO NOT MATCH |
| THE VERSION SUBMITTED AS PART OF THE FOUNDATION PERMIT, |
| SPECIFICALLY RELATED TO THE PRE-WIRING OF THE PARKING |
| FOR EV. ALL PERMITS NEED TO INCLUDE THE SAME LATEST, |
| ACCURATE PLANS. |
| |
| 14) THE FOLLOWING ITEMS REQUIRE REVIEW AS SEPARATE |
| PERMITS WITH PLANS: |
| |
| A. THE WALLS, FENCES, GATES AND COLUMNS |
| B. HARDSCAPE, INCLUDING PAVERS, ARTIFICIAL TURF, DOG |
| PARK ITEMS, BENCHES/PLAZA AREA, ETC. |
| C. LANDSCAPE |
| D. IRRIGATION |
| E. GENERATOR |
| F. WATER FEATURES |
| G. PARKING STRIPING |
| H. SITE LIGHTING, INCLUDING BOLLARDS, NOTE: SINCE |
| ACACIA ROAD IS A SEPARATE PARCEL, IT REQUIRES ITS OWN |
| PERMIT FOR THE LIGHTING, BUT MAY BE INCLUDED ON ONE SET |
| OF PLANS FOR BOTH PERMIT NUMBERS. PHOTOMETRIC PLANS ARE |
| REQUIRED WITH THE PERMITS. |
| I. BICYCLE RACKS, INCLUDES WITHIN THE BICYCLE STORAGE |
| ROOM. |
| J. EV CHARGING STATIONS |
| |
| CONTACT ERIC SCHNEIDER @ (561) 822-1446 |
| [email protected] |
| |
| |