Plan Review Notes
Plan Review Notes For Permit 21071625
Permit Number 21071625
Review Stop P
Sequence Number 1
Notes
Date Text
2022-01-26 16:00:0801/26/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 1. ON SHEET 00.002; PAGES ON ARE MISSING FROM THE
 PLUMBING INDEX AS FOLLOWS;
  
 P2.126
 P3.105
 P3.206
 P3.207
 P3.208
 P3.209
 P3.210
 P3.300
 P3.301
 P3.302
 P3.303
 P3.304
  
 2. ON SHEET 00.200, UNDER BUILDING TYPE, IT REFERS TO
 FLORIDA BUILDING CODE 2017, WHICH CURRENT IS 2020.
 WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 3. ON SHEET A0.204, UNDER APPLICABLE CODES # 1 AND 2,
 IT REFERS TO FLORIDA BUILDING CODE 2017 AND
 ACCESSIBILITY 2017, WHICH IS CURRENTLY 2020 7 TH
 EDITION. FOR FHA # 5, IF YOU ARE USING THE DESIGN
 MANUAL OR THE GUIDELINES, WOULD YOU PLEASE CLARIFY
 WHICH SAFE HARBOR. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 4. ON SHEET 00.205;
  
 A. THE FHA NOTES TALKS ABOUT SPECIFICATION B AND NO
 MENTION ON THE LAV TO BE AT 34" PER 7.52 OF THE FHA
 DESIGN MANUAL.
  
 B. THE PENTHOUSE IS A FUTURE BUILD-OUT AND, IN THIS
 WAY, ESTABLISHED IN THE BUILDING DEPARTMENT THAT THE
 POWDER ROOM IS FOR THE CONSTRUCTION WORKER. WOULD YOU
 PLEASE ADD A NOTE OF THIS ON THE PAGE UNDER FAIR
 HOUSING ITEM #8 PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. ON SHEET 00.206 UNDER LIFE SAFETY # 1 AND 2, IT
 REFERS TO FLORIDA BUILDING CODE 2017 AND ACCESSIBILITY
 2017, WHICH IS CURRENTLY 2020 7 TH EDITION. FOR FHA #
 5, IF YOU ARE USING THE DESIGN MANUAL OR THE
 GUIDELINES, WOULD YOU PLEASE CLARIFY WHICH SAFE HARBOR.
 WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 6. ON SHEET 00.207;
  
 A. ON DETAIL C, THE TOILET SEATS NEED TO BE 17 INCHES
 TO 19 INCHES MAXIMUM MEASURED TO THE TOP OF THE SEAT
 PER THE 2020 FBC ACC SEC. 604.4 SEATS.
  
 B. ON DETAIL C AND F, THE FIXED 18 INCHES FROM THE WALL
 IS HAS A MINIMUM AND MAXIMUM PER 2020 FBC ACC SEC.
 604.2 LOCATION.
  
 C. UNDER GENERAL REQUIREMENTS # 1, 13, 14, 15, 16, IT
 REFERS TO FLORIDA BUILDING CODE 2017 AND ACCESSIBILITY
 2017, WHICH IS CURRENTLY 2020 7 TH EDITION. WOULD YOU
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 D. ON NUMBER 77, IT REFERS TO THE DISPENSER BEING 12
 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN
 FRONT OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF
 DISPENSER PER THE 2020 FBC ACC SEC. 604.7. WOULD YOU
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 E. ON NUMBER 81 WATER CLOSET IN THE ACCESSIBLE RESTROOM
 SHALL BE TO THE CENTERLINE OF THE WATER CLOSET 16
 INCHES MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL
 PER THE 2020 FBC ACC. SEC. 604.2 LOCATION. SEATS OF
 WATER CLOSETS SHALL BE OPEN-FRONT TYPE PER 2020 FBC P
 425.3 WATER CLOSET SEATS
  
 F. UNDER URINAL FOR PARTITION, WOULD YOU PLEASE ADD
 THAT THE PARTITIONS TO PROVIDE PRIVACY SHALL EXTEND NOT
 LESS THAN 60 INCHES ABOVE THE FINISHED FLOOR SURFACE
 PER THE 2020 FBC SEC. P 405.3.5 URINAL PARTITIONS.
  
 G. FOR THE LABORATORIES, IT SAYS 29 INCHES BUT A
 MINIMUM OF 27" KNEE CLEARANCE PER THE 2020 FBC SEC.
 306.3.
  
 I. GRAB BARS # 95 ON THE REAR NEED TO BE MEASURED TO
 THE CENTER OF THE WATER CLOSET TO 12 INCHES TO THE WALL
 AND 24 INCHES TO THE OPEN SIDE PER THE 604.5.1 SIDE
 WALL AND 604.5.2 REAR WALL.
  
 7. ON SHEET 00.210;
  
 A. UNDER GENERAL REQUIREMENTS, IT HAS BOTH THE
 GUIDELINES AND THE DESIGN MANUAL, TWO DIFFERENT SAFE
 HARBORS, AND ONLY ONE SHOULD BE NOTED. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS? THERE ARE EIGHT
 SAFE HARBORS FOR COMPLIANCE WITH THE FAIR HOUSING ACT.
 COMPLIANCE WITH ANY ONE OF THE ELEVEN WILL FULFILL THE
 FAIR HOUSING ACT?S ACCESS REQUIREMENTS. IF A PARTICULAR
 SAFE HARBOR IS CHOSEN FOR USE IN A PARTICULAR PROPERTY,
 HOUSING MUST COMPLY WITH ALL OF THE PROVISIONS OF THAT
 SAFE HARBOR IN ORDER FOR THERE TO BE A SAFE HARBOR. SO
 IT IS UNWISE TO PICK AND CHOOSE AMONG THE PROVISIONS OF
 DIFFERENT SAFE HARBOR STANDARDS.
  
 B. THERE ARE TWO DETAILS, 1 AND 3, AND OTHER FHA
 DETAILS THAT ARE NOT NEEDED IN THIS SET OF PLANS. WOULD
 YOU PLEASE REMOVE FOR FIELD CLARITY PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS? THESE IMAGES SEEM TO COME FROM
 THE DESIGN MANUAL, BUT THE VERBIAGE UP TOP SEEMS TO BE
 ON THE GUIDELINES. PLEASE REFER TO THE ABOVE COMMENT
 AND CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. UNDER CHAPTER SIX REQUIREMENTS, IT REFERS TO THE
 ANSI 117.1 STANDARD, WHICH IS NOT MENTIONED UNDER
 APPLICABLE CODES. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS? IT IS IMPORTANT TO NOTE THAT
 THE ANSI A117.1 STANDARD CONTAINS ONLY TECHNICAL
 CRITERIA, WHEREAS THE FAIR HOUSING ACT, THE
 REGULATIONS, AND THE GUIDELINES CONTAIN BOTH SCOPING
 AND TECHNICAL CRITERIA. THEREFORE, IN USING ANY OF THE
 ANSI STANDARDS, IT IS ALSO NECESSARY TO CONSULT THE ACT
 HUD'S REGULATIONS AND THE GUIDELINES.
  
 D. FOR DETAIL TWO AND 11 ON A0.211 FOR THE SPEC B
 BATHROOM USED DOES NOT MATCH THE FLOOR LAYOUT PRESENTED
 IN THESE PLANS. FOR EXAMPLE, THE TUB IS DIFFERENT, AND
 THERE IS IN THE FHA DESIGN MANUAL REINFORCING FOR GRAB
 BARS AT NON-CONVENTIONAL BATHTUBS PAGE 6.10. WOULD YOU
 PLEASE PROVIDE DETAIL FOR BACKING PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 8. ON SHEET LS1.100 AND LS1.101 AND ALL OTHERS, THE
 APPLICABLE CODES IT HAS THE FLORIDA BUILDING AND
 ACCESSIBILITY REFERS TO THE 2017 6 TH EDITION AND THE
 CURRENT IS 2020 7 THE EDITION. WOULD YOU PLEASE CORRECT
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS? IF YOU ARE USING
 THE DESIGN MANUAL OR THE GUIDELINES FOR THE FHA, WOULD
 YOU PLEASE CLARIFY WHICH SAFE HARBOR? WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 9. ON SHEET A1.1B1,
  
 A. LEVEL B1 IN THE BREAK ROOM, PLEASE SHOW THE CLEAR
 FLOOR SPACE FOR THE SINK PER THE 2020 FBC ACC SEC.
 602.2.
  
 B. LEVEL B2, THE PUMPROOM DOES NOT SHOW A FLOOR DRAIN,
 AND IT IS NOT REQUIRED BUT RECOMMENDED. WOULD YOU
 PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 C. IN STAIRCASE C, THERE IS A FLOOR DRAIN WITH NUMBER
 04 POINTING TO IT AND NOT LABELED. WOULD YOU PLEASE
 CLARIFY OR CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 10. ON SHEET A-100;
  
 A. THE PLANTER SHOW DRAIN BUT NOT LABELED. WOULD YOU
 PLEASE PROVIDE PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. WOULD YOU PLEASE LABEL ALL ROOMS AND FLOOR DRAIN PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 C. IN. THE MEN'S RESTROOM DOES NOT SHOW THE WATER
 CLOSET. WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS
 TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS?
  
 D. IN THE EMPLOYEE RR, THE FIXTURES ARE MISSING. WOULD
 YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 E. THE GENERATOR IS SHOWN, AND IT SHOULD BE NOTED THAT
 IT IS BELOW B1. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 F. WOULD YOU PLEASE SHOW ALL CLEAR FLOOR SPACE PER THE
 FLORIDA BUILDING CODE AND FLORIDA ACCESSIBILITY CODE.
 PLEASE INDICATE THE CLEAR FLOOR SPACE DIAGRAM AND
 DIMENSIONS PER THE 2020 FBC ACC SEC. 606.2. 2 CLEAR
 FLOOR SPACE AND WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. LAV IN THE OPEN
 AREA ON THE WOMEN'S REQUIRES CLEAR FLOOR SPACE.
  
 11. ON SHEET A-101;
  
 A. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE
 WOMEN'S RESTROOM FOR THE LAV ON THE OPEN AREA PER THE
 2020 FBC ACC SEC. 602.2. PLEASE INDICATE THE CLEAR
 FLOOR SPACE DIAGRAM AND DIMENSIONS PER THE 2020 FBC ACC
 SEC. 606.2. 2 CLEAR FLOOR SPACE AND WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 B. IN THE JANITOR'S ROOM, THE SERVICE SINK (MOP SINK)
 SURROUNDING THE WALL SHALL BE A NON-ABSORBENT SURFACE
 IN ACCORDANCE WITH THE 2020 FBC BUILDING SEC. 1210.2.2
 AND 2020 FBC SEC. P 310.3. PLEASE MAKE A NOTE ON THIS
 SHEET.
  
 12. ON SHEET A-102;
  
 A. IN THE WARMING KITCHEN, THERE IS S SINK. WOULD YOU
 PLEASE SHOW THE CLEAR FLOOR SPACE PER THE 2020 FBC ACC
 SEC. 602.2. PLEASE INDICATE THE CLEAR FLOOR SPACE
 DIMENSIONS PER THE 2020 FBC ACC SEC. 606.2. 2 CLEAR
 FLOOR SPACE AND WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. WOULD YOU PLEASE LABEL THE JANITOR SINK PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 C. IN THE MEN'S RESTROOM, THERE IS A LAV IN THE OPEN
 AREA THAT REQUIRES CLEAR FLOOR SPACE PER THE 2020 FBC
 ACC SEC. 606.2. 2 CLEAR FLOOR SPACE.
  
 13. ON SHEET A-103;
  
 A. ON THE GUEST ROOM #2 BATH SHOWER DOES NOT COMPLY
 WITH THE 2020 FBC ACC SEC. 608.2. SHOWER COMPARTMENTS.
 PLEASE SHOW THE CLEAR FLOOR SPACE PER THE 2020 FBC ACC
 SEC. 606.2. 2 CLEAR FLOOR SPACE. HOW WILL THE GRAB BARS
 COMPLY PER THE 2020 FBC ACC SEC. 608.2. PLEASE SHOW THE
 TURNING RADIUS SPACE OF FIVE FEET 603.2.1, 304.3.1
 CIRCULAR SPACE.
  
 B. IN WOMEN'S AND MEN'S SPAS, THE OPEN LAVS NEED TO
 SHOW THE CLEAR FLOOR SPACE PER THE 2020 FBC ACC SEC.
 606.2. 2 CLEAR FLOOR SPACE.
  
 C. THE MEN'S RESTROOM NEEDS TO COMPLY WITH THE 2020
 ACCESSIBILITY AND SHOW THE CLEAR FLOOR SPACE FOR LAV,
 TURNING RADIUS, AND TOILET. THE WOMAN'S RESTROOM NEEDS
 TO SHOW THE TURNING SPACE PER THE 2020 FBC ACC SEC.
 612.3 TURNING SPACE.
  
 D. THE MEN'S AND WOMAN'S SAUNA AND STEAM NEED TO SHOW
 THE TURNING SPACE PER THE 2020 FBC ACC SEC. 612.3
 TURNING SPACE.
  
 E. THE TREATMENT ROOM NEEDS TO SHOW THE LAVS CLEAR
 FLOOR SPACE PER THE 2020 FBC ACC SEC. 606.2. 2 CLEAR
 FLOOR SPACE.
  
 14. ON SHEET A1.104, 105, AND 124;
  
 A. WOULD YOU PLEASE IDENTIFY THE FHA UNITS AND SHOW THE
 CLEAR FLOOR SPACE FOR LAV, SHOWER, TUB, AND TOILET PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 B. IT IS SAID THAT SPECIFICATION B IS TO BE USED IN THE
 MASTER, SO PLEASE TELL US HOW THE FHA GRAB BAR BACKING
 WILL COMPLY SINCE IT IS AN OPEN SHOER TO TWO SIDES.
 WOULD YOU PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 15. ON SHEET A1.124, THE BUILD-OUT IS FOR THE FUTURE.
 WOULD YOU PLEASE PROVIDE A NOTE ON THIS PAGE STATING
 THE FHA BATHROOM AND ITS COMPLIANCE PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 16. ON SHEET A1.125;
  
 A. IN THE POOL EQUIPMENT, THERE IS A SINK AND A HOSE
 BIBB. WOULD YOU PLEASE LABEL PER THE SOLAR COVER
 REQUIRED PER 2020 FBC RE 403.10.3?
  
 B. THERE IS A GAS GRILL; PLEASE IDENTIFY TANK PROPANE
 OR A GAS SYSTEM PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. UNDER ROOF GENERAL NOTES, THERE IS MENTION FOR ROOF
 DRAIN AND OVERFLOW CALCULATION. WOULD YOU PLEASE
 PROVIDE THE PAGE NUMBER WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 17. ON SHEET A1.204, 205, 206, 207, 208, 209, 210, 300,
 301, 302, 303, AND 304, PLEASE IDENTIFY THE BATHROOM
 WHICH IS THE FHA AND SHOW CLEAR FLOOR SPACE FOR ALL
 FIXTURES PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. WOULD YOU PLEASE
 PROVIDE DIMENSIONS FOR FIXTURES PER THE 2020 FBC SEC.
 405.3.1.
  
 18. ON SHEET A1.306;
  
 A. THE SHOWER IS SHOWN AT 2'-11", AND IT SHALL HAVE
 SIZES AND CLEARANCES COMPLYING WITH 2020 FBC ACC SEC.
 608.2.
  
 B. WOULD YOU PLEASE SHOW A CLEAR FLOOR SPACE DIAGRAM
 AND DIMENSIONS FOR ALL FOUR SHOWERS PER THE 2020 FBC
 ACC SEC. 606.2. 2 CLEAR FLOOR SPACE.
  
 C. WOULD YOU PLEASE SHOW OR POINT TO THE PAGE WHICH THE
 SEAT REINFORCES VERTICAL OR HORIZONTAL FORCE OF 250
 POUNDS IS APPLIED AT ANY POINT ON THE SEAT, FASTENER,
 MOUNTING DEVICE, OR SUPPORTING STRUCTURE PER THE 2020
 FBC ACC SEC. 610.4 STRUCTURAL STRENGTH.
  
 D. ON DETAIL #3, WOULD YOU PLEASE SHOW THE GRAB BARS TO
 THE TOP OF THE GRIPPING SURFACE PER THE 2020 FBC ACC
 SEC. 609.4.
  
 E. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO
 A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 19. ON SHEET A1.306A;
  
 A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO
 A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. WOULD YOU PLEASE SHOW A CLEAR FLOOR SPACE DIAGRAM
 AND DIMENSIONS FOR THE SINK PER THE 2020 FBC ACC SEC.
 606.2. 2 CLEAR FLOOR SPACE.
  
 C. WOULD YOU PLEASE SHOW THE SINK OF 34 INCHES MAXIMUM
 PER THE 2020 FBC ACC SEC. 606.3.
  
 20. ON SHEET A1.307;
  
 A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO
 A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. ON DETAIL # 4, 9, AND 10, WOULD YOU PLEASE SHOW THE
 GRAB BARS TO THE TOP OF THE GRIPPING SURFACE PER THE
 2020 FBC ACC SEC. 609.4.
  
 C. UNDER URINAL FOR PARTITION, WOULD YOU PLEASE ADD
 THAT THE PARTITIONS TO PROVIDE PRIVACY SHALL EXTEND NOT
 LESS THAN 60 INCHES ABOVE THE FINISHED FLOOR SURFACE
 PER THE 2020 FBC SEC. P 405.3.5 URINAL PARTITIONS.
  
 21. ON SHEET A1.308;
  
 A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO
 A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. IN WOMEN'S AND MEN'S SPAS, THE OPEN LAVS NEED TO
 SHOW THE CLEAR FLOOR SPACE PER THE 2020 FBC ACC SEC.
 606.2. 2 CLEAR FLOOR SPACE.
  
 22. ON SHEET A1.309;
  
 A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO
 A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. ON DETAIL #1, WOULD YOU PLEASE SHOW THE CLEAR FLOOR
 SPACE DIAGRAM AND DIMENSIONS FOR THE WATER CLOSET, LAV,
 AND TURNING SPACE PER THE 2020 FBC ACC SEC. 606.2. 2
 CLEAR FLOOR SPACE AND WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 23. ON SHEET A1.310;
  
 A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO
 A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. ON DETAIL #1, WOULD YOU PLEASE SHOW THE CLEAR FLOOR
 SPACE DIAGRAM AND DIMENSIONS FOR THE WATER CLOSET, LAV,
 AND TURNING SPACE PER THE 2020 FBC ACC SEC. 606.2. 2
 CLEAR FLOOR SPACE AND WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. THE OPEN
 LAV REQUIRES CLEAR FLOOR SPACE PER THE 2020 FBC ACC
 SEC. 606.2. 2 CLEAR FLOOR SPACE.
  
 24. ON SHEET A1.311;
  
 A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO
 A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. ON DETAIL #1, WOULD YOU PLEASE SHOW THE CLEAR FLOOR
 SPACE DIAGRAM AND DIMENSIONS FOR THE WATER CLOSET, LAV,
 AND TURNING SPACE PER THE 2020 FBC ACC SEC. 606.2. 2
 CLEAR FLOOR SPACE AND WPB
  
 25. ON SHEET A1.312, IT SAYS FOR ADA FIXTURES AND
 ACCESSORIES, REFER TO A0.004 AND A0.005 AND NO SUCH
 PAGE. WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS
 TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS?
  
 26. ON SHEET A1.313;
  
 A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO
 A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. ON DETAIL #1, WOULD YOU PLEASE SHOW THE CLEAR FLOOR
 SPACE DIAGRAM AND DIMENSIONS FOR THE WATER CLOSET, LAV,
 AND TURNING SPACE PER THE 2020 FBC ACC SEC. 606.2. 2
 CLEAR FLOOR SPACE AND WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. THE GUEST ROOM #2 BATH SHOWER DOES NOT COMPLY WITH
 THE 2020 FBC ACC SEC. 608.2. SHOWER COMPARTMENTS.
 PLEASE SHOW THE CLEAR FLOOR SPACE PER THE 2020 FBC ACC
 SEC. 606.2. 2 CLEAR FLOOR SPACE. HOW ARE THE GRAB BARS
 GOING TO COMPLY PER THE 2020 FBC ACC SEC. 608.2. PLEASE
 SHOW THE TURNING RADIUS SPACE OF FIVE FEET 603.2.1,
 304.3.1 CIRCULAR SPACE.
  
 27. ON SHEET A1.314;
  
 A. ON THIS PAGE HAS FHA PLANS FOR THE DIFFERENT
 RESTROOMS, BUT SHEET 00.205 SAYS THE MASTER BEDROOM TO
 BE SPECIFICATION B. WHICH ONE IS THE CORRECT ONE, AND
 WOULD YOU LABEL THE ONE PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. ONE OF EACH TYPE OF FIXTURE MUST BE USABLE BY A
 PERSON WITH A DISABILITY IN A SPECIFICATION B BATHROOM
 PER THE FHA PAGE 7.34.
  
 C. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE TO THE
 WATER CLOSET PER THE FHA PAGE 7.43 AND THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 D. ON DETAIL # 5 ON THE SHOWER, WHERE ARE THE GRAB BARS
 SUPPORTS FOR THE SIDE AND SHOW THE BACKING FOR FRONT
 AND BACK PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. SHOW THE CLEAR
 FLOOR SPACE FOR THE TUB AND WATER CLOSET PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. ONLY ON LAV SHALL COMPLY ON
 SPECIFICATION B.
  
 E. ON DETAIL # 6, WOULD YOU PLEASE SHOW THE CLEAR FLOOR
 SPACE TO THE WATER CLOSET PER THE FHA PAGE 7.43 AND THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 F. ON DETAIL # 7, IT SHOWS THE CLEAR FLOOR SPACE TO THE
 WATER CLOSET BUT CAN YOU SHOW DIMENSIONS PER THE FHA
 PAGE 7.43 AND THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. FOR THE
 SHOWER, WHERE ARE THE GRAB BARS SUPPORTS FOR THE SIDE,
 AND PLEASE SHOW THE BACKING FOR FRONT AND BACK PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. SHOW THE CLEAR FLOOR SPACE FOR
 THE TUB AND WATER CLOSET PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 ONLY ON LAV SHALL COMPLY ON SPECIFICATION B.
  
 G. ON DETAIL # 8, SHOW THE BACKING FOR SIDE, FRONT, AND
 BACK PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. SHOW THE CLEAR
 FLOOR SPACE FOR THE TUB PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 SHOWS THE CLEAR FLOOR SPACE TO THE WATER CLOSET, TUB,
 AND SHOWER WITH DIMENSIONS PER THE FHA PAGE 7.43 AND
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 28. ON SHEET A1.400, IN THE EMPLOYEE RR, WOULD YOU
 PLEASE SHOW THE TURNING SPACE PER THE 2020 FBC ACC SEC.
 612.3 TURNING SPACE.
  
 29. WOULD YOU PLEASE A PLUMBING PLAN INCLUDING THE
 SANITARY, CONDENSATE, STORM, AND WATER ISOMETRIC
 DRAWINGS PER THE WPB AMEND TO FBC 107.3.5.1.3(13).
  
 30. ON SHEET P2.1B2;
  
 A. WOULD YOU PLEASE SHOW THE INDIRECT CONNECTION FOR
 THE ELEVATOR TO THE SANITARY ON THE PLUMBING DETAILS
 AND GIVE A REFERENCE PAGE NUMBER FOR IT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. WOULD YOU PLEASE LABEL THE STAIR WELL AND ELEVATOR
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. IT IS MOTION ON PLANS HOW THE PIPES SHALL BE
 PROTECTED WATER LINES AND SANITARY WHERE THE VEHICULAR
 PATHWAY IN THE PARKING GARAGE EXPOSED TO DAMAGE AND
 SHALL BE RECESSED INTO THE WALL OR OTHERWISE PROTECTED
 IN AN APPROVED MANNER PER 2020 FBC SEC. P 305.7
 PROTECTION OF COMPONENTS OF THE PLUMBING SYSTEM. PLEASE
 PROVIDE DETAILS OR SHOW BOLLARDS IN FRONT OF PIPES PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 WOULD YOU INCORPORATE A NUMBER ON THE LEGEND PRESENT
 FOR THE BOLLARD LOCATION AND SHOW IT ON B1 AND B2 PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 31. ON SHEET P2.1B1;
  
 A. IT IS MOTION ON PLANS HOW THE PIPES SHALL BE
 PROTECTED WATER LINES AND SANITARY WHERE THE VEHICULAR
 PATHWAY IN THE PARKING GARAGE EXPOSED TO DAMAGE AND
 SHALL BE RECESSED INTO THE WALL OR OTHERWISE PROTECTED
 IN AN APPROVED MANNER PER 2020 FBC SEC. P 305.7
 PROTECTION OF COMPONENTS OF THE PLUMBING SYSTEM. PLEASE
 PROVIDE DETAILS OR SHOW BOLLARDS IN FRONT OF PIPES PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 WOULD YOU INCORPORATE A NUMBER ON THE LEGEND PRESENT
 FOR THE BOLLARD LOCATION AND SHOW IT ON B1 AND B2 PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 B. THERE ARE TWO RPZ'S AND AN FD IN A ROOM. WOULD YOU
 PLEASE LABEL THE ROOM PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. THERE IS A RESTROOM NEXT TO THE SERVICE CORRIDOR,
 THE EMPLOYEE RESTROOM THAT IS NOT LABELED, AND THE
 LAUNDRY ROOM. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 D. WOULD YOU, PLEASE LABEL THE DRAIN IN THE EMPLOYEE
 RESTROOM AND THE LAUNDRY ROOM PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 E. WHERE THE FOUR SHOWERS ARE, WOULD YOU PLEASE LABEL
 THE BREAKROOM, W, AND M LOCKER ROOM PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 F. IN STAIRWELL C, THE SECONDARY STAIRS THAT GO OUTSIDE
 LOOK LIKE A DRAIN AT THE BOTTOM. WOULD YOU PLEASE LABEL
 ALL STAIRWELLS AND IDENTIFY DRAINS PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 32. ON SHEET P2.101;
  
 A. THERE ARE DRAINS IN THE FIRE PUMP AND NEXT TO THE
 TRASHING STAGE THAT IS NOT LABELED. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. WOULD YOU PLEASE LABEL THE ROOMS NEXT TO THE TRASH
 STAGING ARE PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. HOT WATER LINES LOOPED FOR THE RECIRCULATING SYSTEM
 ARE NOT IN A CONTINUOUS LOOP. THERE IS A REQUIREMENT IN
 THE FLORIDA ENERGY CODE SEC. C404.6.1. THERE IS A TABLE
 THAT LIMITS THE BETWEEN THE SOURCE AND THE OUTLET;
 PLEASE REFER TO TABLE 404.5.1 FOR THE MAXIMUM ALLOWABLE
 PIPE LENGTH METHOD AND SIZE ACCORDANTLY. THE COMMENT
 WILL APPLY TO ALL AND WHERE THERE IS A LOOP SYSTEM.
  
 33. ON SHEET P2.102;
  
 A. THE RESTROOM NEXT TO THE ELEVATOR IS NOT LABELED.
 WOULD YOU PLEASE LABEL PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. DOES THE KITCHEN HAVE AN ICEMAKER OR COFFEE MAKER,
 AND IF SO, IT SHALL BE EQUIPPED WITH AN IN-LINE VACUUM
 BREAKER THAT COMPLIES WITH ASSE 1024 PER THE 2020 FBC
 SEC. 608.13.10.
  
 C. THERE IS A SHOWER FOR THE POOL IS THE DRAIN GOING IN
 A STORM OR TO A DRY WELL. IF RAIN IS COLLECTED, IT
 CANNOT GO INTO THE SANITARY. WOULD YOU PLEASE CLARIFY
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 34. ON SHEET P2.103, THERE IS A DRINKING FOUNTAIN IN
 FRONT OF THE BUSINESS ROOM. WHAT IS THE DISTANCE TO THE
 GYM PER THE 2020 FBC SEC. P 403.5 DRINKING FOUNTAIN
 LOCATION.
  
 35. ON SHEET P2.104 AND P2.124, WOULD YOU PLEASE LABEL
 ALL RESTROOMS, BEDROOMS, AND AMENITY ROOMS PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 36. ON SHEETS P3.105, P3.204, P3.205, P3.206, P3.207,
 P3.208, P3.209, P3.210, P3.300, P3.301, P3.302, P3. 303
 AND P3.304 WOULD YOU PLEASE LABEL ROOMS AND RESTROOM
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 37. ON SHEET P4.201;
  
 A. WOULD YOU PLEASE LABEL THE ROOM AND SHOW THE
 SANITARY PIPE FOR THEM PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL
 SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE
 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P
 310.3. PLEASE MAKE A NOTE ON THIS SHEET.
  
 C. WOULD YOU PLEASE LABEL THE FLOOR DRAIN IN THE
 RESTROOM PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 38. ON SHEET P5.101;
  
 A. WOULD YOU PLEASE PROVIDE SHUTOFF VALVES ON EACH
 RISER PER THE 2020 FBC SEC. 606.1 (4).
  
 B. IT SHOWS A DOUBLE CHECK VALVE AS BACKFLOW AND
 REDUCED PRESSURE ZONE VALVE REQUIRED PER THE CITY OF
 WEST PALM BEACH AND THE CROSS CONNECTION PROGRAM. WOULD
 YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 39. ON SHEET P5.103;
  
 A. RISER 1 SHOWS THE L-3, SH-3 AND WC-3 ARE VENTED
 INCORRECTLY TWICE PER THE 2020 FBC SEC. P 901.2.
  
 B. RISER 2 SHOWS THE DF-1 AND WASHERS ARE VENTED
 INCORRECTLY PER THE 2020 FBC SEC. P 901.2.
  
 C. FOR RISER 2, THE CONTINUATION FOR LETTER F SAYS
 P4.505 THAT PAGE DOES NOT EXIST. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 D. ON RISER 2, THERE IS A FLOOR DRAIN AND WATER CLOSET
 TOGETHER, AND A VENT IS REQUIRED PER THE 2020 FBC SEC.
 910.1 INDIVIDUAL VENTS PERMITTED.
  
 E. ON RISER 2, THERE IS A VENT WITH NO CONTINUATION
 POINT ON THE GROUND FLOOR AND ON B2 AS WELL. WOULD YOU
 PLEASE PROVIDE PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 40. ON SHEET P5.104;
  
 A. THE DRAIN PAN IS SHOWN GOING INTO THE SANITARY ON 4
 TH, AND 5 TH DOES THIS DRAIN CARRY CONDENSATE. WOULD
 YOU PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. THE 4 TH FLOOR SHOWS 4 SH 2, 1 SH 1, 1 DP, 1 B-1, 4
 WC-2, AND 1 WC-1 THAT ARE NOT VENTED AND ON THE MAIN
 DRAIN BY THE STACK. WOULD YOU PLEASE CORRECT PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 41. ON SHEET P5.106;
  
 A. THE CLEANOUTS ARE REQUIRED IN THE BOTTOM OF THE
 STACK PER THE 2020 FBC SEC. P 1101.8 CLEANOUTS
 REQUIRED.
  
 B. AT GROUND LEVEL, IT SAT TP PODIUM PLATER DRAINAGE.
 WOULD YOU PLEASE GIVE THE CORRESPONDING PAGE NUMBER PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 42. ON SHEETS, P5.106 AND P5.107 SHOW THE TABLES USED
 FOR THE SIZING OF THE STORM PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 43. ON SHEET P5.107, LETTERS A, B, AND C REFER TO
 CONTINUATION FOR P5.06 AND NO SUCH PAGE. WOULD YOU
 PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 44. ON SHEET P7.102;
  
 A. PLEASE PROVIDE DETAIL ON RIGID SUPPORT SWAY BRACING
 SHALL BE PROVIDED AT CHANGES IN A DIRECTION MORE
 SIGNIFICANT THAN 45 DEGREES FOR PIPE SIZES 4 INCHES AND
 LARGER PER FBC-PLUMBING SEC. 308.6. SUBMIT DETAILS FOR
 THE BRACING.
  
 B. ON DETAIL 4 FOR THE CONDENSATE DRAIN, WOULD YOU
 PLEASE PROVIDE THE LOCATION WHERE THE DRAIN WILL BE
 DISCHARGING PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 PLEASE FEEL FREE TO SET UP A MEETING OR CONTACT ME ON
 ANY OF THE COMMENTS BY PHONE OR ZOOM MEETING IF YOU
 LIKE TO PREVENT FURTHER REVIEWS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  