Plan Review Notes
Plan Review Notes For Permit 21071625
Permit Number 21071625
Review Stop M
Sequence Number 1
Notes
Date Text
2022-01-10 15:22:181ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21071625
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE ADD A NOTE ON THE DRAWINGS STATING THAT THE
 GENERATOR WILL REQUIRE A SEPARATE PERMIT AND PLAN
 REVIEW AS IT WILL NOT BE REVIEWED UNDER THIS PERMIT.
 FBC 107.2.1
  
 2) PLEASE SHOW THAT THE CARBON MONOXIDE AND NITROGEN
 DIOXIDE DETECTORS ARE SEPARATE PIECES OF EQUIPMENT AND
 SHOW THE MOUNTING HEIGHTS OF EACH PIECE OF EQUIPMENT
 ACCORDING TO FBC M 404.1. PLEASE PROVIDE A DRAWING
 SHOWING THE LOCATIONS OF EACH CARBON MONOXIDE AND
 NITROGEN DIOXIDE LOCATION PER THE MANUFACTURER?S
 INSTRUCTIONS. FBC 107.2.1
  
 3) SHEET LS1.100 INDICATES FIRE RATED WALLS IN SEVERAL
 LOCATIONS ON BOTH LEVELS OF THE PARKING GARAGE. PLEASE
 SHOW THE REQUIRED PENETRATION PROTECTION AT ALL
 DUCTWORK PENETRATING THESE RATED WALLS. FBC M 607
  
 4) SHEET M2.1B1D: PLEASE SHOW HOW MANY DRYERS ARE IN
 THE LAUNDRY ROOM, ALSO PLEASE PROVIDE A DETAIL OF THE
 DRYER DUCT TERMINATION LOCATION. FBC 504
  
 5) SHEET M2.1B1D: THE DRYER DUCTS ARE PENETRATING RATED
 WALLS, PLEASE PROVIDE PROTECTION FOR THESE
 PENETRATIONS. FBC M 607
  
 6) THE MAKEUP AIR FOR THE LAUNDRY ROOM, STORAGE AND
 EQUIPMENT ROOM CANNOT BE TAKEN FROM THE GARAGE.
  
 7) SHEET M2.1B1D: NOTE 4 OF THE CODE NOTES INDICATES A
 MAKEUP AIR PLENUM ON THE ARCHITECTURAL DRAWINGS, PLEASE
 REFERENCE THE SHEET NUMBER OF THE ARCHITECTURAL DRAWING
 THAT HAS THIS INFORMATION.
  
 8) SHEET M2.1B1P: PLEASE PROVIDE PIPE SIZES FOR THE
 PIPING ON THE PIPING PLAN.
  
 9) PLEASE SHOW THE REQUIRED FIRE DAMPERS ON THE
 DRAWINGS WHERE THE DUCTWORK IS PENETRATING ALL RATED
 WALLS. FBC M607
  
 10) PLEASE SHOW OUTDOOR AIR DAMPERS IN THE OUTDOOR AIR
 DUCTWORK.
  
 11) THE PFSF?S DUCTWORK ARE PENETRATING A RATED WALL,
 PLEASE PROVIDE A DETAIL OF HOW THIS PENETRATION WILL BE
 PROTECTED. FBC M 607
  
 12) PLEASE SHOW THE SMOKE DETECTORS INSIDE THE SUPPLY
 DUCTWORK ACCORDING TO FBC M 606.2.2
  
 13) PLEASE REVISIT THE OUTDOOR AIR CALCULATIONS
 PROVIDED AS IT APPEARS THAT SOME HAVE A LOWER OCCUPANT
 COUNT THAN WHAT FBC M 403.3.1.1 AND TABLE 403.3.1.1
 ALLOWS.
  
 14) SHEET M6.101: THE AIR DEVICE SCHEDULE STOPS AT
 DESIG. M, PLEASE SHOW INFORMATION FOR THE DESIG. P. FBC
 107.2.1
  
 15) PLEASE SHOW THE CONDENSATE PIPING MATERIAL, SIZING
 AND TERMINATION LOCATION. FBC M 307
  
 16) SHEET M5.101: PLEASE IDENTIFY AND INCLUDE
 SPECIFICATIONS FOR THE EXHAUST FANS FOR THE DRYER
 EXHAUST.
  
 17) PLEASE PROVIDE SPECIFICATIONS FOR THE LAUNDRY
 DRYERS INCLUDING THE DUCT LENGTH. FBC M 504
  
 18) PLEASE PROVIDE A DETAIL SHOWING THE DUCT SUPPORTS
 IN THE SHAFTS. FBC M 305
  
 19) SHEET M5.103: PLEASE SHOW THE SPF FOR STAIR B
 PRESSURIZATION ON THIS RISER DETAILS.
  
 20) SHEET M8.101: THE GARAGE CARBON MONOXIDE/NITROGEN
 DIOXIDE SUPPLY/EXHAUST FAN CONTROL SEQUENCE MUST MATCH
 FBC M 404.1- 1 AND 2
  
 21) SHEET M2.101D: PLEASE SHOW THAT THE EF-3 IS A
 CORROSION RESISTANT FAN BECAUSE OF IT?S LOCATION IN THE
 POOL EQUIPMENT ROOM.
  
 22) PLEASE SHOW THAT ALL EXHAUST TERMINATION LOCATIONS
 MEET THE 3 FOOT CLEARANCE FROM OPERABLE OPENINGS INTO
 THE BUILDING. FBC M 501.3
  
 23) FBC M2.125D: PLEASE SIZE THE DUCTWORK ON THE ROOF
 FROM THE SHAFT TO THE DOAS-1 INCLUDING THE DUCT SIZE TO
 THE CSEF-1. FBC 107.2.1
  
 24) PLEASE SHOW DUCT SIZES FOR THE DUCT BOXES LEAVING
 THE FCU?S. FBC 107.2.1
  
 25) COMMON EXHAUST SYSTEM FOR CLOTHES DRYERS LOCATED IN
 MULTISTORY STRUCTURES MUST MEET THE REQUIREMENTS OF
 504.10 1-12.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  