2022-01-04 16:51:57 | NEW COMMERCIAL BUILDING R2 |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| |
| 1) PLEASE PROVIDE A NOTE THAT THE FIRE SERVICE ACCESS |
| ELEVATOR LOBBY DOORS COMPLY WITH FBC 3007.6.3 THE FIRE |
| DOOR ASSEMBLY SHALL COMPLY WITH THE SMOKE AND DRAFT |
| CONTROL DOOR ASSEMBLY REQUIREMENTS OF SECTION |
| 716.5.3.1, AND BE TESTED IN ACCORDANCE WITH UL 1784 |
| WITHOUT AN ARTIFICIAL BOTTOM SEAL. |
| |
| 2) EXIT ACCESS DOORS FROM THE 2ND FLOOR POOL DECK |
| SHOULD SWING IN THE DIRECTION OF EGRESS FBC 1010.1.2.1 |
| |
| 3) STAIR "C" - DOORS IN A SERIES = FBC 1010.1.8 DOOR |
| ARRANGEMENT. |
| SPACE BETWEEN TWO DOORS IN A SERIES SHALL BE 48 INCHES |
| (1219 MM) MINIMUM PLUS THE WIDTH OF A DOOR SWINGING |
| INTO THE SPACE. |
| |
| 4) PLEASE SHOW THE POOL BARRIER FOR DECK LEVEL 2 POOL |
| AND THE PENTHOUSE POOL FBC 454.1.3.1.9 |
| |
| 5) PLEASE SHOW THE SPA STEAM SHOWER AND SAUNA TO BE |
| ACCESSIBLE PER - FBC FHA REQUIREMENT 2. (14) |
| |
| 6) PLEASE SHOW THE MEN'S RESTROOM IN THE MEN'S SPA AREA |
| TO BE ACCESSIBLE - FBC FHA REQUIREMENT 2. (11) |
| |
| 7) PLEASE SHOW A CLEAR DOOR WIDTH OF 32" FOR WALK-IN |
| CLOSETS, WALK-IN PANTRYS, WALK-IN WINE CELLARS, SPA |
| STEAM SHOWER AND SPA SAUNA ETC. - FBC FHA REQUIREMENT |
| 3. (2) |
| |
| 8) ALL FLOOR PLANS NEED TO SHOW THE DOOR DESIGNATION |
| NUMBER PER THE DOOR SCHEDULE - SOME ARE SHOWN BUT NOT |
| ALL - FBC WPB 107.2.1 |
| |
| 9) PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE TOILET IN |
| THE TOILET ROOMS WHICH ARE IN THE MASTER BATHROOMS - |
| FBC FHA REQUIREMENT 7. (2) |
| |
| 10) PLEASE SHOW ON THE FLOOR PLANS THAT EACH UNIT |
| BATHROOM COMPLIES WITH SPEC. A OR B - FBC FHA |
| REQUIREMENT 7. (2) |
| |
| 11) PLEASE SHOW THE UNIT FLOOR FINISHES - FOR OTHER |
| THAN CARPET AND PROVIDE THE FOLLOWING ACOUSTICAL TEST |
| REPORTS - |
| |
| MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| |
| A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.. |
| PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING |
| SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY |
| DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP |
| CEILING DESCRIPTION) |
| |
| B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP |
| CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING |
| ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED |
| DROP CEILING DESCRIPTION) |
| |
| C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS |
| ATTACHED TO THE FLOORING) |
| |
| 12) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, EXTERIOR |
| DOORS, ROOFING SYSTEMS, EXTERIOR LOUVERS, EXTERIOR |
| CLADDING - ETC. - ALL PRODUCT APPROVALS NEED TO BE |
| REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER |
| OF RECORD FBC WPB 107.3.4 |
| |
| 13) ITEMS SUCH AS WINDOW, DOOR AND ROOFING PRODUCT |
| APPROVALS, FLOORING/UNDERLAYMENT ACOUSTICAL TEST |
| REPORTS - ETC. MAY BE DEFERRED SUBMITTALS BY LISTING |
| ITEMS TO BE DEFERRED ON THE CONSTRUCTION DOCUMENTS - |
| 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR |
| DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE |
| REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING |
| OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE |
| IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING. |
| THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED |
| UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN |
| APPROVED BY THE BUILDING OFFICIAL. |
| |
| 14) A SEPARATE PERMIT SHALL BE REQUIRED FOR - EXISTING |
| BUILDING DEMO., SITE PAVING, SITE WALKWAYS, SITE |
| LIGHTING, WATER FALLS, FENCING, SIGNS ETC.. |
| |
| 15) TO VERIFY THAT THE BUILDING IS NOT IN A FLOOD ZONE |
| - PLEASE SHOW THE BUILDING FOOT PRINT (B1 AND B2) ON A |
| DRAWING WITH THE FLOOD ZONE - SUCH AS DRAWING C5.00 |