Plan Review Notes
Plan Review Notes For Permit 21071625
Permit Number 21071625
Review Stop B
Sequence Number 1
Notes
Date Text
2022-01-04 16:51:57NEW COMMERCIAL BUILDING R2
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A NOTE THAT THE FIRE SERVICE ACCESS
 ELEVATOR LOBBY DOORS COMPLY WITH FBC 3007.6.3 THE FIRE
 DOOR ASSEMBLY SHALL COMPLY WITH THE SMOKE AND DRAFT
 CONTROL DOOR ASSEMBLY REQUIREMENTS OF SECTION
 716.5.3.1, AND BE TESTED IN ACCORDANCE WITH UL 1784
 WITHOUT AN ARTIFICIAL BOTTOM SEAL.
  
 2) EXIT ACCESS DOORS FROM THE 2ND FLOOR POOL DECK
 SHOULD SWING IN THE DIRECTION OF EGRESS FBC 1010.1.2.1
  
 3) STAIR "C" - DOORS IN A SERIES = FBC 1010.1.8 DOOR
 ARRANGEMENT.
 SPACE BETWEEN TWO DOORS IN A SERIES SHALL BE 48 INCHES
 (1219 MM) MINIMUM PLUS THE WIDTH OF A DOOR SWINGING
 INTO THE SPACE.
  
 4) PLEASE SHOW THE POOL BARRIER FOR DECK LEVEL 2 POOL
 AND THE PENTHOUSE POOL FBC 454.1.3.1.9
  
 5) PLEASE SHOW THE SPA STEAM SHOWER AND SAUNA TO BE
 ACCESSIBLE PER - FBC FHA REQUIREMENT 2. (14)
  
 6) PLEASE SHOW THE MEN'S RESTROOM IN THE MEN'S SPA AREA
 TO BE ACCESSIBLE - FBC FHA REQUIREMENT 2. (11)
  
 7) PLEASE SHOW A CLEAR DOOR WIDTH OF 32" FOR WALK-IN
 CLOSETS, WALK-IN PANTRYS, WALK-IN WINE CELLARS, SPA
 STEAM SHOWER AND SPA SAUNA ETC. - FBC FHA REQUIREMENT
 3. (2)
  
 8) ALL FLOOR PLANS NEED TO SHOW THE DOOR DESIGNATION
 NUMBER PER THE DOOR SCHEDULE - SOME ARE SHOWN BUT NOT
 ALL - FBC WPB 107.2.1
  
 9) PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE TOILET IN
 THE TOILET ROOMS WHICH ARE IN THE MASTER BATHROOMS -
 FBC FHA REQUIREMENT 7. (2)
  
 10) PLEASE SHOW ON THE FLOOR PLANS THAT EACH UNIT
 BATHROOM COMPLIES WITH SPEC. A OR B - FBC FHA
 REQUIREMENT 7. (2)
  
 11) PLEASE SHOW THE UNIT FLOOR FINISHES - FOR OTHER
 THAN CARPET AND PROVIDE THE FOLLOWING ACOUSTICAL TEST
 REPORTS -
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
 12) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, EXTERIOR
 DOORS, ROOFING SYSTEMS, EXTERIOR LOUVERS, EXTERIOR
 CLADDING - ETC. - ALL PRODUCT APPROVALS NEED TO BE
 REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER
 OF RECORD FBC WPB 107.3.4
  
 13) ITEMS SUCH AS WINDOW, DOOR AND ROOFING PRODUCT
 APPROVALS, FLOORING/UNDERLAYMENT ACOUSTICAL TEST
 REPORTS - ETC. MAY BE DEFERRED SUBMITTALS BY LISTING
 ITEMS TO BE DEFERRED ON THE CONSTRUCTION DOCUMENTS -
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 14) A SEPARATE PERMIT SHALL BE REQUIRED FOR - EXISTING
 BUILDING DEMO., SITE PAVING, SITE WALKWAYS, SITE
 LIGHTING, WATER FALLS, FENCING, SIGNS ETC..
  
 15) TO VERIFY THAT THE BUILDING IS NOT IN A FLOOD ZONE
 - PLEASE SHOW THE BUILDING FOOT PRINT (B1 AND B2) ON A
 DRAWING WITH THE FLOOD ZONE - SUCH AS DRAWING C5.00