2021-08-26 14:54:561ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21071617
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SHOW THE BATH EXHAUST AND THE TERMINATION
 LOCATION. FBC RES M1507.4
  
 2) PLEASE PROVIDE A DETAIL OF THE SECURING OF THE
 OUTDOOR APPLIANCE. FBC RES M1307.2
  
 3) PLEASE SHOW THE CONDENSATION DRAIN AND THE
 TERMINATION LOCATION. FBC RES M1411.3
  
 4) THE MECHANICAL CONTRACTOR THAT SIGNED THE A-1
 MECHANICAL DRAWING MUST ALSO OBTAIN THE MECHANICAL SUB
 PERMIT FOR THIS PROJECT.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  