Plan Review Notes
Plan Review Notes For Permit 21071518
Permit Number 21071518
Review Stop B
Sequence Number 3
Notes
Date Text
2022-01-19 07:02:47****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FYI THE MAJORITY OF FILES IN THIS SUBMITTAL HAVE BEEN
 LOCKED AS THEY DO NOT MEET DESIGN PRESSURE
 REQUIREMENTS.
  
 1. FBC B 1609, FROM PREVIOUS LISTS:
  
 MARK PRODUCT APPROVALS TO SHOW OPTION SELECTED, BUT
 OPTIONS MUST MEET THE DESIGN PRESSURES SPECIFIED BY THE
 ENGINEER. NOTE IF THE OPTION IS FOR ZONE 4 OR ZONE 5 AS
 IT APPEARS THAT THERE ARE OPENINGS FOR FIXED, SINGLE
 HUNG, AND SGD IN BOTH ZONES.
  
 2. SEE SGD FL251-R33, IT IS NOT CLEAR WHAT DESIGN
 PRESSURE OPTION IS PROPOSED AND NONE MEET THE
 REQUIREMENT FOR ZONE 5. PRESSURES REQUIRED PER
 ENGINEER:
  
 ZONE 4 +59.79/-62.18
 ZONE 5 +56.01/-93.54
  
 OPTIONS ON PAGES 6 AND 7 HAVE DP LIMITATION OF +-60,
 OPTIONS ON PAGE 8 HAVE DP LIMITATION OF +-90, SEE ALSO
 TABLE 1A, 2A, 3A.
  
 2. SEE FIXED WINDOW FL26095, SHEET 4 OF 5 HAS +55/-59.3
 HIGHLIGHTED. THIS DOES NOT MEET PRESSURES REQUIRED BY
 THE ENGINEER:
  
 ZONE 4 +62.01/-66.97
 ZONE 5 +66.97/-122.79
  
 3. SINGLE HUNG FL9064 APPEARS OK.
  
 4. IT APPEARS THAT MULLIONS ARE REQUIRED, BUT HAVE NOT
 BEEN SUBMITTED.
  