Plan Review Notes For Permit 21071518 |
Permit Number |
21071518 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-09-15 17:20:26 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | PLAN REVIEW IN PROGRESS | | | | 1. FBC B 1609, ENGINEER'S CALCULATIONS ARE VERY LENGTHY | | AND COMPLIANCE IS NOT CLEAR, DESIGN PRESSURES ON A1 DO | | NOT ALWAYS CORRELATE WITH THE ENGINEER'S CALCULATIONS. | | SEE PAGE 7-8 OF CALCULATIONS. A1.0 SHOWS ZONE 4 AS | | +66.97/-66.97, ENGINEER'S CALCS SHOW +62.01/-66.97. | | | | THE PRODUCT APPROVALS ARE NOT MARKED AS TO OPTIONS | | PROPOSED. | | | | THE FIXED PRODUCT APPROVAL FL 26095 OPTION ON DRAWING | | SHEET 4 OF 5 FOR OPTION MEETING DESIGN PRESSURE OF | | +55/-59.3, BUT DESIGN PRESSURES FOR ZONE 4 ARE HIGHER | | THAN THAT PER ENGINEERING. | | | | TO RESOLVE: | | | | CONFIRM THAT ALL DESIGN PRESSURES IN THE CALCULATIONS | | EXACTLY CORRELATE WITH THOSE SHOWN ON A1.0 | | MARK PRODUCT APPROVALS TO SHOW OPTION SELECTED, BUT | | OPTIONS MUST MEET THE DESIGN PRESSURES SPECIFIED BY THE | | ENGINEER. NOTE IF THE OPTION IS FOR ZONE 4 OR ZONE 5 AS | | IT APPEARS THAT THERE ARE OPENINGS FOR FIXED, SINGLE | | HUNG, AND SGD IN BOTH ZONES. | | | | | | | | |
|