Plan Review Notes
Plan Review Notes For Permit 21071518
Permit Number 21071518
Review Stop B
Sequence Number 1
Notes
Date Text
2021-09-15 17:20:26****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 PLAN REVIEW IN PROGRESS
  
 1. FBC B 1609, ENGINEER'S CALCULATIONS ARE VERY LENGTHY
 AND COMPLIANCE IS NOT CLEAR, DESIGN PRESSURES ON A1 DO
 NOT ALWAYS CORRELATE WITH THE ENGINEER'S CALCULATIONS.
 SEE PAGE 7-8 OF CALCULATIONS. A1.0 SHOWS ZONE 4 AS
 +66.97/-66.97, ENGINEER'S CALCS SHOW +62.01/-66.97.
  
 THE PRODUCT APPROVALS ARE NOT MARKED AS TO OPTIONS
 PROPOSED.
  
 THE FIXED PRODUCT APPROVAL FL 26095 OPTION ON DRAWING
 SHEET 4 OF 5 FOR OPTION MEETING DESIGN PRESSURE OF
 +55/-59.3, BUT DESIGN PRESSURES FOR ZONE 4 ARE HIGHER
 THAN THAT PER ENGINEERING.
  
 TO RESOLVE:
  
 CONFIRM THAT ALL DESIGN PRESSURES IN THE CALCULATIONS
 EXACTLY CORRELATE WITH THOSE SHOWN ON A1.0
 MARK PRODUCT APPROVALS TO SHOW OPTION SELECTED, BUT
 OPTIONS MUST MEET THE DESIGN PRESSURES SPECIFIED BY THE
 ENGINEER. NOTE IF THE OPTION IS FOR ZONE 4 OR ZONE 5 AS
 IT APPEARS THAT THERE ARE OPENINGS FOR FIXED, SINGLE
 HUNG, AND SGD IN BOTH ZONES.
  
  
  
  