Plan Review Notes
Plan Review Notes For Permit 21071469
Permit Number 21071469
Review Stop G
Sequence Number 1
Notes
Date Text
2021-08-26 13:52:3208/26/21 1ST LP GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE SPECIFICATIONS FOR THE GENERATOR ARE 24 KW, AND
 UNDER PROPANE, IT HAS 142 BTU FULL LAOD, AND THE
 ISOMETRIC HAS 355 BTU. WOULD YOU PLEASE PROVIDE CORRECT
 BTU?S PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 2. THE LP TANK SPECS PROVIDED REFER TO THE 2017 FBC GAS
 CODE. PLEASE PROVIDE THE CURRENT CODE PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 3. THE ENGINEER WHO PREPARED THE TANK TIE-DOWN DETAILS
 SHALL PROVIDE AN ELECTRONIC SIGNATURE AND SEAL THE
 DOCUMENT- FL. STATUTE 471.025 & FLORIDA ADMINISTRATIVE
 CODE SEC. 61G15-23.005.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  