2021-08-04 14:27:25PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 WHERE ADDITION OR MODIFICATION IS MADE TO AN EXISTING
 SYSTEM AFFECTING MORE THAN 20 SPRINKLERS, THE NEW
 PORTION SHALL BE ISOLATED AND TESTED AT NOT LESS THAN
 200 PSI (13.8 BAR) FOR 2 HOURS.
  