Plan Review Notes
Plan Review Notes For Permit 21071433
Permit Number 21071433
Review Stop B
Sequence Number 3
Notes
Date Text
2022-02-28 16:24:43RESIDENTIAL (R3) ADDITION, THIRD BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21071433
  
 ORIGINAL COMMENT:
 1- ALL DRAWINGS NEED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OF RECORD. PLANS NEED TO HAVE ARCHITECT'S
 ORIGINAL SEAL AND SIGNATURE WHEN SUBMITTING DOCUMENTS
 FOR PUBLIC RECORDS AS REQUIRED BY 61G1-16.003 FAC.
  
 RESPONSE:
 UNABLE TO VERIFY ARCHITECT'S DIGITAL SIGNATURE. PLANS
 SUBMITTED SHOW A COPY OF A DIGITAL SIGNATURE. I WAS
 ABLE TO VERIFY THE DIGITAL SIGNATURE ON THE ARCHITECT'S
 RESPONSE LETTER BUT NOT ON THE DRAWINGS. PLANS NEED TO
 HAVE ORIGINAL DIGITAL SIGNATURE TO VERIFY ARCHITECT'S
 DIGITAL SIGNATURE.
 NOTE: SUBMIT ALL PLANS WITH ORIGINAL DIGITAL SIGNATURE.
  
 2- OK.
 3- OK.
 4- OK.
 5- OK.
  
 ORIGINAL COMMENT:
 6- GARAGE DOOR NOA 20-1015.22 SUBMITTED IS ONLY FOR UP
 TO 9'-0" WIDE DOOR. NEED TO PROVIDE PRODUCT APPROVAL
 FOR GARAGE DOOR SIZE SPECIFIED ON PLANS.
 FAC 61G20-3.001.
 NOTE: COORDINATE DESIGN PRESSURES WITH THOSE SPECIFIED
 BY THE ARCHITECT OF RECORD.
  
 RESPONSE:
 DESIGN PRESSURES OF GARAGE DOOR NOA 20-0416.02 DON'T
 MEET THE DESIGN PRESSURES CALCULATED BY THE ARCHITECT
 OF RECORD. NEED PRODUCT APPROVAL THAT MEETS OR EXCEEDS
 CALCULATED DESIGN PRESSURES.
 NOTE: NEW PRODUCT APPROVAL TO BE REVIEWED/APPROVED BY
 ARCHITECT PRIOR TO SUBMITTAL.
  
 ORIGINAL COMMENT:
 7- PROVIDE FIRE RATING SPECIFICATIONS FOR GARAGE DOOR
 LEADING TO THE INTERIOR OF THE HOUSE SHOWING COMPLIANCE
 WITH SEC. R302.5.1 FBC-RESIDENTIAL. NOTE: EXISTING DOOR
 CAN NOT BE USED UNLESS PROOF IS PROVIDED SHOWING
 COMPLIANCE.
  
 RESPONSE:
 CONSTRUCTION PLAN ON SHEET A-1 WAS REVISED BY THE
 ARCHITECT SPECIFYING 20 MINUTE FIRE RATED DOOR. THIS IS
 OK. NO NEED TO SUBMIT SPECIFICATIONS FOR FIRE RATED
 DOOR. THIS WILL BE VERIFIED BY THE INSPECTOR IN THE
 FIELD.
 NOTE: MAKE SURE DOOR IS FIRE RATED AS PER ARCHITECT'S
 SPECIFICATIONS. FLORIDA PRODUCT APPROVAL FL8845-R6
 SUBMITTED IS FOR EXTERIOR DOORS AND DOESN'T SHOW THE
 FIRE RATING.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION