2022-02-28 16:24:43 | RESIDENTIAL (R3) ADDITION, THIRD BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #21071433 |
| |
| ORIGINAL COMMENT: |
| 1- ALL DRAWINGS NEED TO BE SIGNED AND SEALED BY THE |
| ARCHITECT OF RECORD. PLANS NEED TO HAVE ARCHITECT'S |
| ORIGINAL SEAL AND SIGNATURE WHEN SUBMITTING DOCUMENTS |
| FOR PUBLIC RECORDS AS REQUIRED BY 61G1-16.003 FAC. |
| |
| RESPONSE: |
| UNABLE TO VERIFY ARCHITECT'S DIGITAL SIGNATURE. PLANS |
| SUBMITTED SHOW A COPY OF A DIGITAL SIGNATURE. I WAS |
| ABLE TO VERIFY THE DIGITAL SIGNATURE ON THE ARCHITECT'S |
| RESPONSE LETTER BUT NOT ON THE DRAWINGS. PLANS NEED TO |
| HAVE ORIGINAL DIGITAL SIGNATURE TO VERIFY ARCHITECT'S |
| DIGITAL SIGNATURE. |
| NOTE: SUBMIT ALL PLANS WITH ORIGINAL DIGITAL SIGNATURE. |
| |
| 2- OK. |
| 3- OK. |
| 4- OK. |
| 5- OK. |
| |
| ORIGINAL COMMENT: |
| 6- GARAGE DOOR NOA 20-1015.22 SUBMITTED IS ONLY FOR UP |
| TO 9'-0" WIDE DOOR. NEED TO PROVIDE PRODUCT APPROVAL |
| FOR GARAGE DOOR SIZE SPECIFIED ON PLANS. |
| FAC 61G20-3.001. |
| NOTE: COORDINATE DESIGN PRESSURES WITH THOSE SPECIFIED |
| BY THE ARCHITECT OF RECORD. |
| |
| RESPONSE: |
| DESIGN PRESSURES OF GARAGE DOOR NOA 20-0416.02 DON'T |
| MEET THE DESIGN PRESSURES CALCULATED BY THE ARCHITECT |
| OF RECORD. NEED PRODUCT APPROVAL THAT MEETS OR EXCEEDS |
| CALCULATED DESIGN PRESSURES. |
| NOTE: NEW PRODUCT APPROVAL TO BE REVIEWED/APPROVED BY |
| ARCHITECT PRIOR TO SUBMITTAL. |
| |
| ORIGINAL COMMENT: |
| 7- PROVIDE FIRE RATING SPECIFICATIONS FOR GARAGE DOOR |
| LEADING TO THE INTERIOR OF THE HOUSE SHOWING COMPLIANCE |
| WITH SEC. R302.5.1 FBC-RESIDENTIAL. NOTE: EXISTING DOOR |
| CAN NOT BE USED UNLESS PROOF IS PROVIDED SHOWING |
| COMPLIANCE. |
| |
| RESPONSE: |
| CONSTRUCTION PLAN ON SHEET A-1 WAS REVISED BY THE |
| ARCHITECT SPECIFYING 20 MINUTE FIRE RATED DOOR. THIS IS |
| OK. NO NEED TO SUBMIT SPECIFICATIONS FOR FIRE RATED |
| DOOR. THIS WILL BE VERIFIED BY THE INSPECTOR IN THE |
| FIELD. |
| NOTE: MAKE SURE DOOR IS FIRE RATED AS PER ARCHITECT'S |
| SPECIFICATIONS. FLORIDA PRODUCT APPROVAL FL8845-R6 |
| SUBMITTED IS FOR EXTERIOR DOORS AND DOESN'T SHOW THE |
| FIRE RATING. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |