2022-01-11 15:07:29 | RESIDENTIAL (R3) ADDITION, SECOND BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #21071433 |
| |
| ORIGINAL COMMENT: |
| 1- ALL DRAWINGS NEED TO BE SIGNED AND SEALED BY THE |
| ARCHITECT OF RECORD. PLANS NEED TO HAVE ARCHITECT'S |
| ORIGINAL SEAL AND SIGNATURE WHEN SUBMITTING DOCUMENTS |
| FOR PUBLIC RECORDS AS REQUIRED BY 61G1-16.003 FAC. |
| |
| RESPONSE: |
| SOME PLANS STILL DON'T HAVE THE ARCHITECT'S DIGITAL |
| SIGNATURE. ALSO, PLANS SUBMITTED SHOW A COPY OF A |
| DIGITAL SIGNATURE. PLANS NEED TO HAVE ORIGINAL DIGITAL |
| SIGNATURE TO VERIFY ARCHITECT'S DIGITAL SIGNATURE. |
| NOTE: SUBMIT ALL PLANS WITH ORIGINAL DIGITAL SIGNATURE. |
| |
| 2- OK. |
| 3- OK. |
| 4- OK. |
| 5- OK. |
| |
| ORIGINAL COMMENT: |
| 6- GARAGE DOOR NOA 20-1015.22 SUBMITTED IS ONLY FOR UP |
| TO 9'-0" WIDE DOOR. NEED TO PROVIDE PRODUCT APPROVAL |
| FOR GARAGE DOOR SIZE SPECIFIED ON PLANS. |
| FAC 61G20-3.001. |
| NOTE: COORDINATE DESIGN PRESSURES WITH THOSE SPECIFIED |
| BY THE ARCHITECT OF RECORD. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| NEW COMMENT: |
| 7- PROVIDE FIRE RATING SPECIFICATIONS FOR GARAGE DOOR |
| LEADING TO THE INTERIOR OF THE HOUSE SHOWING COMPLIANCE |
| WITH SEC. R302.5.1 FBC-RESIDENTIAL. NOTE: EXISTING DOOR |
| CAN NOT BE USED UNLESS PROOF IS PROVIDED SHOWING |
| COMPLIANCE. |
| I APOLOGIZE FOR NO WRITING THIS COMMENT ON MY FIRST |
| REVIEW. I WROTE IT ON MY INITIAL CHECKLIST NOTES, BUT |
| SOMEHOW I FORGOT TO WRITE IT ON THE OFFICIAL REVIEW |
| CHECKLIST. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |