Plan Review Notes
Plan Review Notes For Permit 21071433
Permit Number 21071433
Review Stop B
Sequence Number 1
Notes
Date Text
2021-10-13 13:42:33RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21071433
  
 NOTE:
 SEC. 606 FBC-EXISTING BUILDING. SEC. 801.3 FBC-EXISTING
 BUILDING. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE.
  
 1- ALL DRAWINGS NEED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OF RECORD. PLANS NEED TO HAVE ARCHITECT'S
 ORIGINAL SEAL AND SIGNATURE WHEN SUBMITTING DOCUMENTS
 FOR PUBLIC RECORDS AS REQUIRED BY 61G1-16.003 FAC.
 NOTE: PLANS MAY BE UPLOADED TO PROJECTDOX WITH A
 DIGITAL SIGNATURE OR HARD COPIES WITH LICENSED DESIGN
 PROFESSIONAL SEAL AND SIGNATURE MAY BE DROPPED (OR
 MAILED) TO CITY HALL FOR RECORDS RETENTION.
  
 2- SHEET CVR:
 A)BUILDING IS LOCATED IN EXPOSURE "D" NOT EXPOSURE "C".
 REVISE AS REQUIRED.
 SEC. R301.2.1.4 FBC-RESIDENTIAL.
  
 B) CURRENT BUILDING CODE (2020) REFERENCES ASCE 7-16
 NOT ASCE 7-10. REVISE AS REQUIRED.
 SEC. 553.73 F.S.
  
 C)CLEARLY SPECIFY THE ULTIMATE DESIGN WIND SPEED AND
 THE NOMINAL DESIGN WIND SPEED. ALSO, REVISE DESIGN WIND
 PRESSURES TO CORRESPOND TO EXPOSURE "D" AS REQUIRED BY
 ITEM #2(A) ABOVE. AND, CLARIFY IF THE GIVEN DESIGN
 PRESSURES ARE ULTIMATE DESIGN WIND SPEEDS OR NOMINAL
 DESIGN WIND SPEEDS. SEC. R301.2.1.3 FBC-RESIDENTIAL.
  
 D)BUILDING CLASSIFICATION IS INCORRECT. TYPE IIIB
 CONSTRUCTION REQUIRES 2 HOUR FIRE RATED WALLS.
 TYPICALLY, SINGLE FAMILY RESIDENCES DON'T HAVE 2 HOUR
 FIRE RATED WALLS. REVISE AS REQUIRED OR PROVIDE
 DOCUMENTATION SHOWING THAT EXISTING HOUSE AND PROPOSED
 WALLS HAVE 2 HOUR FIRE RATED BEARING WALLS.
 TABLE 601 FBC-BUILDING.
  
 E)BUILDING AND ZONING DEPARTMENTS ARE INCORRECT. THIS
 IS CITY OF WEST PALM BEACH NOT CITY OF DELRAY. REVISE
 AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 3- SHOW ON PLANS CARBON MONOXIDE ALARMS BY ALL THE
 BEDROOMS AS REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL.
  
 4- SHEET A-1:
 A)TYP. GARAGE DOOR DETAIL IS MISSING THE FASTENING
 SPECIFICATIONS FOR THE STRUCTURAL BUCK. DESIGNER OF
 RECORD IS RESPONSIBLE FOR THE SPECIFICATION. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 B) COORDINATE DESIGN WIND PRESSURES WITH ITEM # 2(C)
 ABOVE. SEC. 107.2.1 CITY AMENDMENTS.
  
 5- SHEET A-4:
 A)FOOTING F1 IS NOT CLEAR. FOOTING SIZE SPECIFIED ON
 THE FOOTING SCHEDULE AND FOOTING SHOWN ON THE TYP.
 EXTERIOR WALL DON'T MATCH. ALSO. CLARIFY WHY THE
 FOOTING DEPTH IS ONLY 5 INCHES?. FOOTING NEEDS TO BE
 12" BELOW GRADE. SEC. R403.1.4 FBC-RESIDENTIAL. SEC.
 107.2.1 CITY AMENDMENTS.
  
 B)TYPICAL WALL SECTION: THERE ARE NOT SPECIFICATIONS
 FOR THE NEW BOND BEAM. CLARIFY WHY NOTES ON WALL
 SECTION SPECIFIES EXISTING DOUBLE BEAM IF THIS IS A NEW
 WALL? SEC. 107.2.1 CITY AMENDMENTS.
  
 C)THERE ARE NO SPECIFICATIONS FOR THE VERTICAL
 REINFORCEMENT ON CONCRETE FILLED COLUMNS. PROVIDE
 COMPLETE DETAIL/SPECIFICATIONS.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 D) CLARIFY WHAT IS THE "2'-0" TYP" NOTE SHOWN ON THE
 FOUNDATION PLAN FOR?
 SEC. 107.2.1 CITY AMENDMENTS.
  
 6- GARAGE DOOR NOA 20-1015.22 SUBMITTED IS ONLY FOR UP
 TO 9'-0" WIDE DOOR. NEED TO PROVIDE PRODUCT APPROVAL
 FOR GARAGE DOOR SIZE SPECIFIED ON PLANS.
 FAC 61G20-3.001.
 NOTE: COORDINATE DESIGN PRESSURES WITH ITEM #2(C)
 ABOVE.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]