Plan Review Notes
Plan Review Notes For Permit 21071421
Permit Number 21071421
Review Stop P
Sequence Number 1
Notes
Date Text
2021-09-13 15:59:1509/13/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET A 2.1A WOULD YOU, PLEASE SHOW THE CLEAR
 FLOOR SPACE FOR THE EMPLOYEE LOUNGE, URINAL, AND
 DRINKING FOUNTAIN PER THE 2017 FBC ACC SEC. 602.2.
  
 2. ON SHEET A 2.1B, WOULD YOU PLEASE SHOW THE CLEAR
 FLOOR SPACE FOR TREATMENT B125, MEDICAL ROOM B123,
 DRINKING FOUNTAIN PER THE 2017 FBC ACC SEC. 602.2.
  
 3. ON SHEET A 5.4, WOULD YOU, PLEASE SHOW THE CLEAR
 FLOOR SPACE AND DIMENSION FOR THE URINAL AND EMPLOYEE
 LOUNGE PER THE 2017 FBC ACC SEC. 602.2.
  
 4. ON P- 2.1A;
 A. ON THE GREASE INTERCEPTOR AREA, NUMBER 5, THERE IS A
 FLOOR DRAIN IN THE TRASH COMPACTOR THAT IS GOING INTO
 THE GREASE INTERCEPTOR, WASTES THAT DO NOT REQUIRE
 TREATMENT OR SEPARATION SHALL NOT BE DISCHARGED INTO
 ANY INTERCEPTOR OR SEPARATOR PER THE 2017 FBC SEC. P
 1003.2 APPROVAL.
  
 B. IN THAT SAME AREA, A LINE IS ADDED UPSTREAM OF THE
 FLOOR DRAIN FOR THE INTERCEPTOR. IS IT FOR ANOTHER AREA
 AND TO BE SHARED WITH OTHER RESTAURANTS, AND IF SO,
 WHAT IS THEIR VOLUME. WOULD YOU PLEASE CLARIFY PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 C. GREASE INTERCEPTOR NUMBER 7 IS NEW, AND THE AREA IS
 COMING FROM IS UNKNOWN, PLUS THE FLOOR DRAIN SIZE IS
 NOT SHOWN. WASTES THAT DO NOT REQUIRE TREATMENT OR
 SEPARATION SHALL NOT BE DISCHARGED INTO ANY INTERCEPTOR
 OR SEPARATOR PER THE 2017 FBC SEC. P 1003.2 APPROVAL.
 WOULD YOU PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 D. IN THE EMPLOYEE LOUNGE AREA, THERE ARE TWO RESTROOMS
 NOT LABELED, AND THE FEMALES' RESTROOM DOES NOT HAVE
 THE SIZE FOR THE FLOOR DRAIN. WOULD YOU PLEASE CORRECT
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 E. IN THE EMPLOYEE LOUNGE AREA, THERE IS A NEW SINK AND
 NO DRAIN TO IT. WOULD YOU PLEASE ADD TO THE EXISTING
 ISOMETRIC DRAWING AND SHOW THAT AND ANY OTHER CHANGES
 MADE TO THIS PAGE PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 F. THERE IS A BAR AND GRILL AREA WITH A FLOOR DRAIN
 SHOWN GOING INTO THE SANITARY AND THREE-COMPARTMENT
 SINK, WHICH SHALL SEPARATE. THE THREE COMPARTMENTS NEED
 TO GO TO GREASE AND THE HAND SINK, ICE CHEST, AND
 OTHERS THAT DO NOT REQUIRE WASTES OR REQUIRE TREATMENT
 OR SEPARATION. WOULD YOU PLEASE CORRECT AND SHOW ON
 ISOMETRIC PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 G. IN THE KITCHEN AREA, THERE ARE GREASE LINES, AND IT
 SEEMS TO BE THAT HAND SINKS AND WASTES THAT DO NOT
 REQUIRE TREATMENT OR SEPARATION ARE DISCHARGING INTO
 ANY INTERCEPTOR.
  
 H. IN THAT SAME DRAWING, THE GREASE LINE IS LABELED,
 BUT NOT ALL THE REQUIRED DRAINS THAT ARE ALLOWED TO GO
 INTO THE INTERCEPTOR ARE NOT DRAINED INTO IT. WOULD YOU
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 I. THERE IS A 4" GREASE WASTE UP, AND PAGE P 3.1 SHOWS
 IT AS A 3" GOING UP. WOULD YOU PLEASE CORRECT PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 K. THERE IS A NEW LINE IN THE KITCHEN AREA COMING IN
 AND TIED TO THE TRASH COMPACTOR. THIS LINE IS NOT SHOWN
 ON THIS PAGE, AND THE ICE MAKER CANNOT DUMP INTO THE
 INTERCEPTOR. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 L. THE DRAINS FOR THE DINING FOUNTAIN ARE NOT SHOWN,
 AND THE WOMEN'S AND MEN'S ARE MISSING SANITARY. IT IS
 UNDERSTOOD THAT THEY ARE IN A SEPARATE DETAIL BUT WOULD
 YOU PLEASE SHOW THEM FOR FIELD CLARITY TO COINCIDE WITH
 P 2.1D PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 M. ON THE MAIN KITCHEN AREA, THERE APPEAR TO BE TWO
 KETTLES, A FLOOR DRAIN, A MOP SINK, AND OTHERS NOT
 SHOWN. WOULD YOU PLEASE CORRECT AND SHOW AS WELL ON
 P3.1 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. ON SHEET P2.1B;
  
 A. WOULD YOU PLEASE LABEL ROOMS, RESTROOMS, AND
 DIFFERENT AREAS ON THIS PAGE TO MATCH P2.1C PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. IN THE MEN?S SHOWER LOCKER ROOM, A WATER CLOSET IS
 SHOWN DRAINING THE WRONG WAY. WOULD YOU PLEASE CORRECT
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 6. ON SHEET P2.1C;
  
 A. IN THE BEAUTY SALON, THERE IS A TRAP FOR THE SECOND
 COSMETIC CHAIR THAT IS NOT VENTED. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. UNDER KEYNOTES, NUMBERS 8 AND NINE ARE MISSING FOR
 PLAN KEYNOTES. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 C. WOULD YOU PLEASE LABEL THE ROOM AND DIFFERENT AREAS
 IN THIS PAGE'S WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 7. ON SHEET P2.1D;
  
 A. THE LAVS THAT WERE MOVE DO NOT SHOW WATER TO THEM.
 WHERE ARE THEY COMING FROM, AND WOULD YOU PLEASE
 PROVIDE REVISED WATER ISOMETRIC DIAGRAM PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.5.1.3 (13) COMMERCIAL
 PLUMBING.
  
 B. HOT WATER LINES LOOPED FOR THE RECIRCULATING SYSTEM
 IT IS NOT IN A CONTINUOUS LOOP. THERE IS A REQUIREMENT
 IN THE FLORIDA ENERGY CODE SEC. C404.6.1. THERE IS A
 TABLE THAT LIMITS THE BETWEEN THE SOURCE AND THE
 OUTLET. PLEASE REFER TO TABLE 405.5.1 FOR THE MAXIMUM
 ALLOWABLE PIPE LENGTH METHOD AND SIZE ACCORDANTLY.
  
 C. ON THE WATER, PLEASE PROVIDE A SHUT-OFF VALVE FOR
 EACH RESTROOM AND SHOW IT ON ISOMETRIC PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
  
 8. ON SHEET P2.2A;
  
 A. THERE SEEM TO BE ADDED AREA DRAINS AND NO REVISED
 ISOMETRIC WITH NEW CALCULATION FOR DRAINAGE AREA. WOULD
 YOU PLEASE PROVIDE A REVISED ISOMETRIC PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 C. THERE SEEM TO BE TWO ADDED FOUNTAINS IN THE GARDEN
 PLAZA. WHAT IS THE SOURCE OF WATER, AND IS THERE A
 BACKFLOW DEVICE? WOULD YOU PLEASE PROVIDE ON THE
 ISOMERIC AND SHOW A DETAIL PER THE WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 C. THERE IS A SINK IN THE GARDEN AREA. IS THIS HANDICAP
 ACCESSIBLE, AND WHAT IS THE SOURCE OF HOT WATER. WOULD
 YOU PLEASE PROVIDE PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 D. THERE IS A HOSE BIBB ADDED TO THE WEST SIDE AND IS
 IT SHOWN ON THE ISOMETRIC DIAGRAM. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 9. ON SHEET P2.2B AND P 3.3B;
  
 A. WATER LINES WERE MOVED TO A VEHICULAR PATHWAY IN THE
 PARKING GARAGE EXPOSED TO DAMAGE SHALL BE RECESSED INTO
 THE WALL OR OTHERWISE PROTECTED IN AN APPROVED MANNER
 PER 2017 FBC SEC. P 305.7 PROTECTION OF COMPONENTS OF
 THE PLUMBING SYSTEM. WOULD YOU PLEASE PROVIDE A DETAIL
 OR SHOW BOLLARD IN FRONT OF PIPES PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS? YOU MAY MOVE BEHIND THE COLUMN
 NOT TO BE IN THE PATH OF A VEHICLE.
  
 B. THERE IS A 4' SANITARY LINE NEXT TO A COLUMN BY THE
 HANDICAP PARKING THAT WILL REQUIRE PROTECTION IN AN
 APPROVED MANNER PER 2017 FBC SEC. P 305.7 PROTECTION OF
 COMPONENTS OF THE PLUMBING SYSTEM. WOULD YOU PLEASE DO
 THIS FOR ANY OTHER PIPES SIMILAR TO THIS ONE PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 10. ON SHEET P 2.3A, THERE ARE SANITARY LINES MOVED IN
 UNIT 309 AND NO SANITARY TO REFLECT THE CHANGES MADE.
 WOULD YOU PLEASE PROVIDE THE SANITARY RISER FOR THIS
 LOCATION AND ANY OTHER ON THIS PAGE PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 11. ON SHEET 2.4B;
 A. IT DOES NOT SHOW THE TRAP PRIMER FOR THE FLOOR DRAIN
 IN POOL EQUIPMENT. WOULD YOU PLEASE PROVIDE IN A NOTE
 OR DRAW THEM IN PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. IN THE POOL EQUIPMENT, IT REFERS TO DWG P-6, AND
 THERE IS NO SUCH PAGE. WOULD YOU PLEASE CLARIFY PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 C. PLEASE PROVIDE A BACKFLOW DEVICE OR SHOW THE POOL
 WATER SOURCE IN A NOTE PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 12. ON SHEET P 2.5A, IT SHOWS SANITARY AND WATER LINES
 MOVED IN UNITS AND SKY LOUNGE BUT NO ISOMERIC DRAWING
 TO REFLECT CHANGES. WOULD YOU PLEASE PROVIDE PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 13. ON SHEET P 2.5B;
  
 A. IT SHOWS SANITARY AND WATER LINES MOVED IN UNITS AND
 SHOWER IN POOL MOVED BUT NO ISOMERIC DRAWING TO REFLECT
 CHANGES. WOULD YOU PLEASE PROVIDE PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. IT SHOWS A POOL COLLECTOR TANK ADDED AND NO DETAIL
 TO A REFERENCE PAGE. WOULD YOU PLEASE PROVIDE PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 C. THERE IS A NOTE FOR A TANK-LESS WATER HEATER FOR
 PAGE P-6 AND NO SUCH PARTICULAR PAGE. WOULD YOU PLEASE
 PROVIDE, I.E., P6.1 OR P6.2, ETC., PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 14. ON SHEET P 2.6A, IT SHOWS SANITARY AND WATER LINES
 MOVED IN UNITS BUT NO ISOMERIC DRAWING TO REFLECT
 CHANGES. WOULD YOU PLEASE PROVIDE PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 15. 11. ON SHEET P 2.6B, IT SHOWS SANITARY AND WATER
 LINES MOVED OR CHANGED IN UNITS AND CORRIDORS BUT NO
 ISOMERIC DRAWING TO REFLECT CHANGES. WOULD YOU PLEASE
 PROVIDE PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 16. ON SHEET P-4;
  
 A. ALL RISERS ARE MARKED WITH A NUMBER, AND ON ALL
 OTHER PAGES, THE SS NUMBER IS MISSING. WOULD YOU PLEASE
 REFER TO THIS PAGE AND NUMBER ALL RISER LABEL SS
 ACCORDANTLY PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. IN-UNIT IL D2, THE TUB HAS A SHOWER IN FRONT OF IT,
 AND HOW IS THIS FHA COMPLIANT; IS IT AN A OR B, AND
 WHERE IS THE SUPPORT FOR THE GRAB BAR IF REQUIRED. ON
 THE LAST COMMENTS, THE SECOND IS SPECKED OUT FOR
 SPECIFICATION B, WHICH IS NOT ALLOWED A BATHROOM IS A
 FORWARD APPROACH THAT CONSTITUTES AN A-TYPE BATHROOM.
 FOR THE B (VI), BATHTUBS AND TUB/SHOWERS LOCATED IN THE
 BATHROOM PROVIDE A CLEAR ACCESS AISLE ADJACENT TO THE
 LAVATORY THAT IS AT LEAST 2?6" WIDE AND EXTENDS FOR A
 LENGTH OF 4?0" (MEASURED FROM THE FOOT OF THE BATHTUB).
 (SEE FIGURE FHAG-8.) PER THE FHA GUIDELINES REQUIREMENT
 7 - USABLE KITCHENS AND BATHROOMS.
  
 17. ON SHEET P 3.1 FOR PRODUCTION KITCHEN;
  
 A. THE GREASE LINE NEEDS TO BE LABELED PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. WASTE DISPOSERS (GARBAGE) SHALL NOT DISCHARGE TO A
 GREASE INTERCEPTOR PER THE 2017 FBC SEC. 1003.3.2 FOOD
 WASTE DISPOSERS RESTRICTION.
  
 C. THE ICEMAKER P1-011 CANNOT GO INTO THE INTERCEPTOR.
 ONLY WASTES THAT DO NOT REQUIRE TREATMENT OR SEPARATION
 ARE DISCHARGING INTO ANY INTERCEPTOR. THERE IS A UNIT
 NEXT TO THE 4" RWL AND THE FS. WOULD YOU PLEASE
 IDENTIFY AND SHOW IT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 D. THERE IS AN FS NEST TO THAT ICEMAKER AD IT LOOKS
 LIKE IT IS TAKING CONDENSATE DRAIN FROM THE FREEZER.
 CONDENSATE FROM THE COOLER EVAPORATOR SHALL NOT
 DISCHARGE TO THE GREASY WASTE PER FBC PL 1003.2.
 ADDITIONALLY, PER WPB CODE OF ORDINANCE CHAPTER 90,
 ARTICLE 3, SECTION 90-12B5, A/C CONDENSATE (I INTERPRET
 THIS AS ANY CONDENSATION FROM EVAPORATOR COILS) SHALL
 NOT DISCHARGE TO THE CITY UTILITIES SANITARY SEWAGE
 INFRASTRUCTURE WITHOUT PERMISSION FROM THE UTILITY
 DEPARTMENT. YOU MAY CONTACT ENGINEERING AT 561-494-1128
 FOR ADDITIONAL INFORMATION. MOVING FORWARD, DISCHARGE
 THE CONDENSATE TO AN EXTERIOR DRY-WELL; PROVIDE DETAIL.
  
 E. ON THE MC PREPARATION KITCHEN, THEY SEEM TO BE LARGE
 KETTLES IN FRONT OF 4-008 THAT ARE NOT LABELED. IF SO
 AND THEY REQUIRE WATER AND DRAINAGE. WOULD YOU PLEASE
 LABEL THEM AND SHOW THE NECESSARY DRAINAGE FOR THEM
 ALONG WITH WATER PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 F. ON THE MC PREPARATION, THE GREASE LINE NEEDS TO BE
 LABELED PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. PLEASE REFER TO
 THE PREVIOUS COMMENTS IN THE MC KITCHEN AREA ON THE
 THREE-COMPARTMENT SINK, ICE CHEST, AND HAND SINK FOR
 INTERCEPTOR APPROVAL PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 18. ON SHEET P3.2;
  
 A. THE LINT INTERCEPTOR HAS OTHER FIXTURES DISCHARGING
 TO IT, AND WASTES THAT DO NOT REQUIRE TREATMENT OR
 SEPARATION SHALL NOT BE DISCHARGED INTO ANY INTERCEPTOR
 OR SEPARATOR PER THE 2017 FBC SEC. P 1003.2 APPROVAL.
  
 B. FOR 5-013 THROUGH 5-017, THERE IS NO SCHEDULE. ARE
 THESE FIXTURES WHICH MAY REQUIRE WATER? THERE SEEMS TO
 BE A FLOOR DRAIN. WOULD YOU PLEASE CLARIFY PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 C. IN THE SKY LOUNGE, THE BAR HAS A THREE COMPARTMENT
 SINK THAT GOES TO THE GREASE INTERCEPTOR, BUT THE HAND
 SINK IS WASTES THAT DO NOT REQUIRE TREATMENT OR
 SEPARATION SHALL NOT BE DISCHARGED INTO ANY INTERCEPTOR
 OR SEPARATOR PER THE 2017 FBC SEC. P 1003.2 APPROVAL.
  
 D. THERE ARE THREE TANKS NEXT TO THE FS IN THAT LOUNGE
 AREA THAT ARE NOT LABELED. WOULD YOU PLEASE CLARIFY
 WHAT THEY ARE PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 CLEAR FLOOR SPACE FOR THE WASHING MACHINES
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  
2021-08-03 13:44:05 
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved