Plan Review Notes
Plan Review Notes For Permit 21071421
Permit Number 21071421
Review Stop E
Sequence Number 1
Notes
Date Text
2021-09-07 13:29:58ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E3-4 BAR AND GRILL NEEDS GFCI PROTECTION FOR
 OUTLETS NEAR SINKS AND IN KITCHEN 210.8(B)
  
 PAGE E-3.5 KITCHEN AND SKY LOUNGE NEED GFCI PROTECTION
 INSTALLED PER 210.8(B)
  
 PAGE E-5.1 RISER DIAGRAM OVER CURRENT PROTECTION OF
 1200 AMPERES OR MORE SHALL COMPLY WITH 240.87
  
 240.87 ARC ENERGY REDUCTION. WHERE THE HIGHEST
 CONTINUOUS CURRENT TRIP SETTING FOR WHICH THE ACTUAL
 OVERCURRENT DEVICE
 INSTALLED IN A CIRCUIT BREAKER IS RATED OR CAN BE
 ADJUSTED IS 1200 A OR HIGHER, 240.87(A) AND (B) SHALL
 APPLY.
  
 PAGE E-5.2 COMMUNICATION PLAN NEEDS A SEPARATE PERMIT.
  
 PAGE E-7.2 GENERATOR PLAN NEEDS A SEPARATE PERMIT.
  
  