2021-10-05 16:13:21THE MEP SHEET HAS A SECTION HEADED AS AIR CONDITIONING
 NOTES THAT INDICATES THAT THE MECHANICAL CONTRACTOR
 WILL INSTALL A COMPLETE AND OPERATING A/C SYSTEM BUT
 THE NOTE AT THE BOTTOM LEFT OF THE SHEET IS REVISED TO
 INDICATE THE MECHANICAL SCOPE OF WORK IS TO REPLACE
 EXISTING EXHAUST FANS AS PER PLANS. PLEASE CLEAR THIS
 UP, IS THERE GOING TO BE NEW MECHANICAL SYSTEMS
 INSTALLED? IF SO PLEASE PROVIDE THE MECHANICAL
 EQUIPMENT SIZING CALCULATIONS. IF NOT PLEASE REMOVE THE
 AIR CONDITIONING NOTES SECTION. PROVIDE A COMPLETE
 SCOPE OF WORK FOR THE MECHANICAL AND A MECHANICAL
 SUBPERMIT WILL BE REQUIRED.
  