2021-09-27 10:03:01 | 2ND REVIEW FBC-2020 PLUMBING |
| PERMIT- 21071298 |
| 9/27/2021 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. COMMENTS #1 & 6 FROM THE |
| 1ST REVIEW PRINTED BELOW STILL EXISTS. PLEASE NOTE THAT |
| SHEET A8.04 IS REFERENCED ON SHEET A2-01 FOR LOCATION |
| OF ACCESSIBILITY ACCESSORY REINFORCEMENT?. |
| |
| 1) FAIR HOUSING ACT COMPLIANCE: PLEASE REFER TO PAGE 7 |
| OF THE INTRODUCTION TO THE FAIR HOUSING DESIGN ACT |
| MANUAL- IF THE CONDOMINIUMS AT 101 N. CLEMATIS (THE |
| LOFT) WERE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH |
| THE FAIR HOUSING ACT DESIGN GUIDELINES, THEN THE |
| PROPOSED ALTERATIONS TO UNIT 405 SHALL ALSO BE IN |
| COMPLIANCE WITH THE GUIDELINES. THE FAIR HOUSING |
| ACCESSIBILITY GUIDELINES ARE INCLUDED IN THE FLORIDA |
| ACCESSIBILITY CODE- 2020 7TH EDITION AND THE FAIR |
| HOUSING DESIGN ACT MANUAL. IF APPLICABLE PLEASE INCLUDE |
| THE FAIR HOUSING COMPLIANCE INFORMATION IN THE |
| APPLICABLE CODE LIST ON G-01, AND REVISE THE PLANS IN |
| ACCORDANCE WITH THE NOTES BELOW: |
| A) THE DESIGN PROFESSIONAL OF RECORD SHALL INDICATE ON |
| THE PLANS WHICH OF THE TWO BATHROOM TYPES IS THE BASIS |
| OF DESIGN- SPECIFICATION TYPE A OR B ON THE PLANS. |
| PLEASE REFER TO PAGES 7.34- 7.39 OF THE DESIGN MANUAL |
| FOR EXPLANATORY INFORMATION ON SPECIFICATION A & B AND |
| SHOW COMPLIANCE. |
| B) REFER TO CHAPTER 7 (REQUIREMENT 7 USABLE KITCHENS & |
| USABLE BATHROOMS) AND PROVIDE ENLARGED BATHROOM AND |
| KITCHEN DRAWINGS AND DETAILS. THE SECTIONS LISTED BELOW |
| MAY BE APPLICABLE BASED ON THE CHOSEN DESIGN |
| SPECIFICATION. |
| PAGES 7.1- 7.6 CLEAR FLOOR SPACES FOR SINKS AND |
| APPLIANCES |
| PAGES 7.7- 7.11 CLEARANCES BETWEEN KITCHEN COUNTERS AND |
| ALL OPPOSING ELEMENTS. |
| PAGES 7.12- 7.16 REMOVABLE SINK AND APPLIANCE CABINET |
| DOORS INCLUDING KNEE SPACES. |
| PAGES 7.40-7.46 WATER CLOSET CLEAR FLOOR SPACES. |
| PAGES 7.47- 7.52: LAVATORY AND VANITY CLEAR FLOOR AND |
| KNEE AND TOE CLEARANCES. |
| PAGES 7.53- 7.55: BATHTUB CLEAR FLOOR SPACE AND CONTROL |
| LOCATIONS |
| C) REFER TO CHAPTER 6 (REINFORCED WALLS FOR GRAB BARS). |
| BASED ON CHAPTER 7 COMPLIANCES LISTED ABOVE, PLEASE |
| PROVIDE DRAWINGS AND DETAILS SHOWING GRAB BAR |
| REINFORCEMENT LOCATIONS AND INSTALLATION DETAILS. |
| PAGES 6.3- 6.8- WATER CLOSETS. |
| PAGES 6.8- 6.11 BATHTUBS |
| PAGES 6.14- 6.16 REINFORCEMENT METHODS. |
| |
| 6) FAILED. PLEASE NOTE THAT THE FIXTURE DRAIN FOR A |
| WASHING MACHINE STANDPIPE SHALL CONNECT TO A 3-INCH OR |
| LARGER DIAMETER BRANCH OR STACK- SECTION 406.2 FBC P. |
| PLEASE LABEL THE 3-INCH FIXTURE DRAIN ON SHEET |
| P-03/DETAIL-1. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |