2021-09-22 15:31:52 | ALTERATION |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected]. |
| CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| 1) PLEASE SHOW THE INTERIOR STOREFRONT GLAZING WHICH IS |
| TO BE USED AS A GUARD RAIL (2ND FLOOR) TO BE LAMINATED |
| FBC 1015.2.1 GLAZING. |
| WHERE GLASS IS USED TO PROVIDE A GUARD OR AS A PORTION |
| OF THE GUARD SYSTEM, THE GUARD SHALL COMPLY WITH |
| SECTION 2407. WHERE THE GLAZING PROVIDED DOES NOT MEET |
| THE STRENGTH AND ATTACHMENT REQUIREMENTS OF SECTION |
| 1607.8, COMPLYING GUARDS SHALL BE LOCATED ALONG GLAZED |
| SIDES OF OPEN-SIDED WALKING SURFACES. FBC 2407.1 |
| MATERIALS. |
| GLASS USED IN A HANDRAIL, GUARDRAIL OR GUARD SECTION |
| SHALL BE LAMINATED GLASS CONSTRUCTED OF FULLY TEMPERED |
| OR HEAT-STRENGTHENED GLASS AND SHALL COMPLY WITH |
| CATEGORY II OR CPSC 16 CFR PART 1201 OR CLASS A OF ANSI |
| Z97.1. |
| |
| 2) EXIT DOORS FOR OTHER UNITS HAVE BEEN REMOVED - TO |
| ALLOW THE UNIT TO HAVE ONE EXIT DOOR PLEASE PROVIDE THE |
| FOLLOWING INFORMATION - PLEASE SHOW THE EXIT ACCESS ( |
| DISTANCE FROM THE MOST REMOTE PLACE IN THE UNIT TO THE |
| UNIT EXIT DOOR) TRAVEL DISTANCE1017.3 MEASUREMENT. EXIT |
| ACCESS TRAVEL DISTANCE SHALL BE MEASURED FROM THE MOST |
| REMOTE POINT OF EACH ROOM, AREA OR SPACE ALONG THE |
| NATURAL AND UNOBSTRUCTED PATH OF HORIZONTAL AND |
| VERTICAL EGRESS TRAVEL TO THE ENTRANCE TO AN EXIT. - |
| PLEASE SEE FBC TABLE 1006.2.1SPACES WITH ONE EXIT OR |
| EXIT ACCESS DOORWAY |
| |
| 3) PLEASE SHOW THE MEZZANINE AREA TO COMPLY WITH FBC |
| 505.2.1 OR SHOW THE 2ND FLOOR (5TH FLOOR) EXIT PER FBC |
| TABLE 1006.3.2 MINIMUM NUMBER OF EXITS OR ACCESS TO |
| EXITS PER STORY |
| |
| 4TH FLOOR UNIT WILL REQUIRE THE FOLLOWING. |
| THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED: |
| |
| MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| |
| A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.. |
| PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING |
| SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY |
| DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP |
| CEILING DESCRIPTION) |
| |
| B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP |
| CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING |
| ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED |
| DROP CEILING DESCRIPTION) |
| |
| C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS |
| ATTACHED TO THE FLOORING) |
| |
| 4). YOU CAN EMAIL ME THE PROPOSED TEST REPORTS TO |
| VERIFY THAT THEY ARE TEST REPORTS BEFORE RESUBMITTING |
| TO PROJECTDOX ( [email protected] ) |
| |
| 5) A UNITY OF TITLE IS REQUIRED. |
| |
| |