Plan Review Notes
Plan Review Notes For Permit 21071298
Permit Number 21071298
Review Stop B
Sequence Number 2
Notes
Date Text
2021-09-22 15:31:52ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) PLEASE SHOW THE INTERIOR STOREFRONT GLAZING WHICH IS
 TO BE USED AS A GUARD RAIL (2ND FLOOR) TO BE LAMINATED
 FBC 1015.2.1 GLAZING.
 WHERE GLASS IS USED TO PROVIDE A GUARD OR AS A PORTION
 OF THE GUARD SYSTEM, THE GUARD SHALL COMPLY WITH
 SECTION 2407. WHERE THE GLAZING PROVIDED DOES NOT MEET
 THE STRENGTH AND ATTACHMENT REQUIREMENTS OF SECTION
 1607.8, COMPLYING GUARDS SHALL BE LOCATED ALONG GLAZED
 SIDES OF OPEN-SIDED WALKING SURFACES. FBC 2407.1
 MATERIALS.
 GLASS USED IN A HANDRAIL, GUARDRAIL OR GUARD SECTION
 SHALL BE LAMINATED GLASS CONSTRUCTED OF FULLY TEMPERED
 OR HEAT-STRENGTHENED GLASS AND SHALL COMPLY WITH
 CATEGORY II OR CPSC 16 CFR PART 1201 OR CLASS A OF ANSI
 Z97.1.
  
 2) EXIT DOORS FOR OTHER UNITS HAVE BEEN REMOVED - TO
 ALLOW THE UNIT TO HAVE ONE EXIT DOOR PLEASE PROVIDE THE
 FOLLOWING INFORMATION - PLEASE SHOW THE EXIT ACCESS (
 DISTANCE FROM THE MOST REMOTE PLACE IN THE UNIT TO THE
 UNIT EXIT DOOR) TRAVEL DISTANCE1017.3 MEASUREMENT. EXIT
 ACCESS TRAVEL DISTANCE SHALL BE MEASURED FROM THE MOST
 REMOTE POINT OF EACH ROOM, AREA OR SPACE ALONG THE
 NATURAL AND UNOBSTRUCTED PATH OF HORIZONTAL AND
 VERTICAL EGRESS TRAVEL TO THE ENTRANCE TO AN EXIT. -
 PLEASE SEE FBC TABLE 1006.2.1SPACES WITH ONE EXIT OR
 EXIT ACCESS DOORWAY
  
 3) PLEASE SHOW THE MEZZANINE AREA TO COMPLY WITH FBC
 505.2.1 OR SHOW THE 2ND FLOOR (5TH FLOOR) EXIT PER FBC
 TABLE 1006.3.2 MINIMUM NUMBER OF EXITS OR ACCESS TO
 EXITS PER STORY
  
 4TH FLOOR UNIT WILL REQUIRE THE FOLLOWING.
 THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
 4). YOU CAN EMAIL ME THE PROPOSED TEST REPORTS TO
 VERIFY THAT THEY ARE TEST REPORTS BEFORE RESUBMITTING
 TO PROJECTDOX ( [email protected] )
  
 5) A UNITY OF TITLE IS REQUIRED.
  
  