2021-08-09 22:29:23 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. SMOKE ALARMS SHOWN ON SEPARATE CIRCUITS. SMOKE |
| ALARMS MUST BE TIED INTO LOCAL LIGHTING CIRCUIT PER FBC |
| APENDIX J |
| |
| 2. PANEL B HAS 125AMP MAIN BREAKER WITH LOAD OF 128 |
| AMPS. NEC 240 NEC 215 |
| |
| 3. PROVIDE CUT SHEETS FOR PRODUCT APPROVAL OF TANKLESS |
| WATER HEATER. WATER HEATER SHOWN AS 4KW ONLY. NEC |
| 110.3B NEC 220 |
| |
| 4. SMOKE ALARMS OUTSIDE BEDROOMS MUST BE SMOKE/CARBON |
| COMBOS. FBC 314 AND 315. |
| |
| 5. AFCI PROTECTION REQUIRED PER NEC 210.12A 210.12B |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2020 7TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| FRANK GIAQUINTO III |
| ELECTRICAL INSPECTOR |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| [email protected] |
| CELL: 561-657-1653 |
| |