Plan Review Notes
Plan Review Notes For Permit 21071298
Permit Number 21071298
Review Stop E
Sequence Number 1
Notes
Date Text
2021-08-09 22:29:23ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SMOKE ALARMS SHOWN ON SEPARATE CIRCUITS. SMOKE
 ALARMS MUST BE TIED INTO LOCAL LIGHTING CIRCUIT PER FBC
 APENDIX J
  
 2. PANEL B HAS 125AMP MAIN BREAKER WITH LOAD OF 128
 AMPS. NEC 240 NEC 215
  
 3. PROVIDE CUT SHEETS FOR PRODUCT APPROVAL OF TANKLESS
 WATER HEATER. WATER HEATER SHOWN AS 4KW ONLY. NEC
 110.3B NEC 220
  
 4. SMOKE ALARMS OUTSIDE BEDROOMS MUST BE SMOKE/CARBON
 COMBOS. FBC 314 AND 315.
  
 5. AFCI PROTECTION REQUIRED PER NEC 210.12A 210.12B
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  