2022-01-06 10:21:31 | ROOFING REVIEW: |
| |
| 1-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| 61G20-3.001 FOR |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| |
| ORIGINAL COMMENT: |
| A) METAL ROOF. AND, CLEARLY SPECIFY FASTENING METHOD. |
| RESPONSE: |
| ACCORDING TO PRODUCT APPROVAL FL27985.06 THE FASTENING |
| METHOD IS NOT RATED (NR) FOR ROOF ZONES 2 AND 3. A |
| DESIGN PROFESSIONAL IS REQUIRED TO PROVIDE CALCULATIONS |
| FOR FASTENING AT THESE ROOF ZONES. SEE FASTENING TABLES |
| ON PAGE 3 OF METAL ROOFING INSTALLATION INSTRUCTIONS. |
| PROVIDE SIGNED AND SEALED CALCULATIONS OR PROVIDE |
| ANOTHER PRODUCT APPROVAL THAT MEETS THE DESIGN |
| PRESSURES FOR ALL ROOF ZONES. |
| |
| ORIGINAL COMMENT: |
| B) ROOFING UNDERLAYMENT SPECIFIED ON PLANS FOR METAL |
| ROOFING. |
| RESPONSE: |
| PRODUCT APPROVAL SUBMITTED DOESN'T MATCH ENGINEER OF |
| RECORD SPECIFICATIONS ON DETAIL 1/A301. |
| |
| 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |
| |