Plan Review Notes
Plan Review Notes For Permit 21071257
Permit Number 21071257
Review Stop E
Sequence Number 1
Notes
Date Text
2021-08-09 12:40:10ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PLEASE SEE 210.12(A),(B) FOR CIRCUITS TO BE AFCI
 PROTECTED. PANEL SCHECDULE NOT SHOWING ALL CIRCUITS
 THAT NEED AFCI PROTECTION.
  
 2) DRYER SHOWN AS A 1P30A CIRCUIT. PLEASE VERIFY
  
 3) SMALL BATHROOM ON SECOND FLOOR NEED AM ADDITIONAL
 OUTLET FOR DOUBLE SINK. 210.52(F)
  
 4) LAUNDRY SHOWS SEVERAL CIRCUITS TO LAUNDRY ROOM
 EXCEPT FOR THE DRYER ALL NEED TO BE AFCI/GFCI PROTECTED
 210.8, 210.12