Plan Review Notes For Permit 21071257 |
Permit Number |
21071257 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-08-09 12:40:10 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | 1) PLEASE SEE 210.12(A),(B) FOR CIRCUITS TO BE AFCI | | PROTECTED. PANEL SCHECDULE NOT SHOWING ALL CIRCUITS | | THAT NEED AFCI PROTECTION. | | | | 2) DRYER SHOWN AS A 1P30A CIRCUIT. PLEASE VERIFY | | | | 3) SMALL BATHROOM ON SECOND FLOOR NEED AM ADDITIONAL | | OUTLET FOR DOUBLE SINK. 210.52(F) | | | | 4) LAUNDRY SHOWS SEVERAL CIRCUITS TO LAUNDRY ROOM | | EXCEPT FOR THE DRYER ALL NEED TO BE AFCI/GFCI PROTECTED | | 210.8, 210.12 |
|