Plan Review Notes
Plan Review Notes For Permit 21071257
Permit Number 21071257
Review Stop B
Sequence Number 1
Notes
Date Text
2021-08-24 13:46:11NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21071257
  
 1- LOT DRAINAGE
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 2- CLEARLY SPECIFY SIZE OF BEDROOM EGRESS WINDOWS
 (WIDTH AND HEIGHT) TO VERIFY COMPLIANCE WITH SEC.
 R310.2.1 FBC-RESIDENTIAL, SPECIALLY FOR SECOND FLOOR
 EGRESS WINDOWS. PLANS ONLY SPECIFY 25SH EGRESS BUT NO
 SIZE.
  
 3- WIND INFORMATION ON SHEET 2 OF 12:
 A)MEAN ROOF HEIGHT IS INCORRECT. SEE PLANS AND REVISE.
 SEC. 107.2.1 CITY AMENDMENTS.
 B)SPECIFY THE SECOND FLOOR TRUSSES LIVE LOAD AS
 REQUIRED BY TABLE R301.5 FBC-RESIDENTIAL. SPECIFY DEAD
 LOADS ALSO.
 C)SPECIFY ROOF TRUSSES DEAD AND LIVE LOADS. CLEARLY
 SPECIFY TOP AND BOTTOM LOADS. INCLUDING THE ATTIC LIVE
 LOAD AS REQUIRED BY TABLE R301.5 FBC-RESIDENTIAL.
  
 4- SOIL TEST REPORT SUBMITTED: GEOTECHNICAL ENGINEER
 RECOMMENDS THE BOTTOM OF THE FOUNDATION TO BE A MINIMUM
 OF 18 INCHES BELOW THE LOWEST ADJACENT GRADE TO ASSURE
 A SAFETY FACTOR AGAINST BEARING CAPACITY FAILURE. SEE
 PAGE 4 OF SOIL TEST REPORT. ENGINEER OF RECORD TO
 REVIEW SOIL TEST REPORT AND ACKNOWLEDGE IF GEOTECHNICAL
 ENGINEER RECOMMENDATIONS WILL BE REQUIRED FOR THIS
 PROJECT OR NOT. REVISE PLANS AS REQUIRED.
 SEC. 107.2.1.2 CITY AMENDMENTS.
  
 5- TYPICAL EXTERIOR WALL SECTION ON SHEET 9 OF 12.
 CLEARLY SPECIFY SIZE AND SPACING OF ATTIC VENT.
 SEC. R806 FBC-RESIDENTIAL.
  
 6- PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR THE
 SOFFIT CONSTRUCTION SHOWING COMPLIANCE WITH SEC.
 R703.1.2.1 FBC-RESIDENTIAL.
  
 7- ROOF SHEATHING NAILING SCHEDULE ON SHEET 10 OF 12:
 A)CLARIFY WHY THE DESIGN PRESSURES FOR ZONE 2E AND 3E
 ARE LOWER THAN THAN THE DESIGN PRESSURES FOR ZONE 2R?
 SEC. 301.2.1 FBC-RESIDENTIAL.
  
 B)ACCORDING TO TABLE R301.2(2) FBC-RESIDENTIAL THE
 DESIGN PRESSURES FOR ZONES 2E, 2R AND 3 ARE THE SAME.
 CLARIFY WHY SHOWING DIFFERENT DESIGN PRESSURES FOR
 THESE ZONES.
  
 C)REVISE ROOF SHEATHING FASTENING SPECIFICATIONS BASED
 ON REVISED DESIGN PRESSURES ON ITEM #7(B) ABOVE. SEC.
 301.2.1 FBC-RESIDENTIAL.
  
 D)ACCORDING TO FIGURE R301.2(7) FBC-RESIDENTIAL, THERE
 IS NOT ZONE #3E ON HIP ROOFS. REVISE AS REQUIRED.
  
 E)REVISE EDGE DIMENSION. ACCORDING TO FIGURE R301.2(7)
 FBC-RESIDENTIAL, THE MIN. EDGE DIMENSION "A" IS 4'-0"
 NOT 3'-0". SEE FOOTNOTE "A" ON FIGURE R301.2(7) AND
 REVISE AS REQUIRED.
  
 8-STAIR DETAILS ON SHEET 10 OF 12:
 A)TREAD DIMENSION CAN NOT BE LESS THAN 10". SEE SEC.
 R311.7.5.2 FBC-RESIDENTIAL AND REVISE AS REQUIRED.
 NOTE: REVISE FLOOR PLANS ACCORDINGLY.
  
 B)RISER HEIGHT IS NOT CLEAR. STAIR DETAIL SAYS 7-3/4"
 RISER TYP. , WHILE NOTE ADJACENT TO THE STAIR DETAIL
 SAYS STAIR RISER=7.65. REVISE AS REQUIRED TO MATCH.
 ALSO, NUMBER OF RISER SPECIFIED NEXT TO THE STAIR
 DETAIL (18) DOESN'T MATCH NUMBER OF RISERS SHOWN ON
 FLOOR PLANS. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1
 CITY AMENDMENTS.
  
 9-DOOR/WINDOW BUCK DETAIL ON SHEET 10 OF 12 SPECIFIES
 2"X4" BUCK FOR DOORS. REVISE THE SIZE OF THE STRUCTURAL
 BUCK. STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO
 THE DOOR FRAME AND NEED TO EXTEND BEYOND THE INTERIOR
 FACE OF THE WINDOW OR DOOR FRAME AS REQUIRED BY SEC.
 R609.7.2.1 FBC-RESIDENTIAL. 2X4 BUCK IS SMALLER THAN
 THE DOOR FRAME. REVISE AS REQUIRED.
 NOTE: BEVELED BUCKS ARE NOT ALLOWED EITHER.
  
 10- ENERGY CALCULATIONS:
 A)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S AND BUILDER'S NAME. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 B)PROVIDE CORRECT INFORMATION FOR ITEM #2. THE QUESTION
 ON THIS ITEM IS SINGLE FAMILY OR MULTIPLE FAMILY?.
 "DETACHED IS NOT THE ANSWER. REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C)ROOF TYPE SPECIFIED ON PAGE 2 OF 5 IS INCORRECT.
 THERE IS NOT GABLE OR SHED ROOF. SEE PLANS AND REVISE
 AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D)REVISE THE ATTIC VENT RATIO ON PAGE 2 OF 5.
 TYPICALLY, THE RATIO IS 1/150 NOT 1/300. SEC. R806.2
 FBC-RESIDENTIAL. SEE PLANS AND REVISE AS REQUIRED.
  
 E)REVISE DOOR INFORMATION PAGE 3 OF 5. ONLY THE SIDE
 DOOR IS INSULATED. SEE PLANS AND PRODUCT APPROVAL AND
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
 NOTE: GLAZING IN ENTRY DOOR NEEDS TO BE INCLUDED IN THE
 WINDOW GLAZING AREA. SEE SEC. R405.5.3 FBC-ENERGY
 CONSERVATION)
  
 F) BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 11-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)ENTRY DOOR WITH SIDELITES THAT MEETS THE DESIGN
 PRESSURES CALCULATED BY THE ENGINEER OF RECORD. AND
 PROVIDE COMPLETE PRODUCT APPROVAL, INCLUDING THE
 FLORIDA PRODUCT APPROVAL COVER PAGE.
  
 B)SLIDING GLASS DOORS. PROVIDE COMPLETE PRODUCT
 APPROVAL, INCLUDING THE FLORIDA PRODUCT APPROVAL COVER
 PAGE.
  
 C) SINGLE HUNG WINDOWS. PROVIDE COMPLETE PRODUCT
 APPROVAL, INCLUDING THE FLORIDA PRODUCT APPROVAL COVER
 PAGE.
  
 D)METAL ROOF. AND, CLEARLY SPECIFY FASTENING METHOD.
  
 E)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO AVOID DELAYS/CONFLICTS).
  
 F)ROOFING UNDERLAYMENT SPECIFIED ON PLANS FOR METAL
 ROOFING.
  
 G)ALUMINUM SOFFIT AND ROOF VENTS SPECIFIED ON PLANS.
  
 H)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
  
 12- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  