2021-08-24 13:46:11 | NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #21071257 |
| |
| 1- LOT DRAINAGE |
| PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| FOLLOWING: |
| R401.3 FBC-RESIDENTIAL. |
| SEC. 107.2.5 CITY AMENDMENTS. |
| SEC. 110.9 CITY AMENDMENTS. |
| |
| 2- CLEARLY SPECIFY SIZE OF BEDROOM EGRESS WINDOWS |
| (WIDTH AND HEIGHT) TO VERIFY COMPLIANCE WITH SEC. |
| R310.2.1 FBC-RESIDENTIAL, SPECIALLY FOR SECOND FLOOR |
| EGRESS WINDOWS. PLANS ONLY SPECIFY 25SH EGRESS BUT NO |
| SIZE. |
| |
| 3- WIND INFORMATION ON SHEET 2 OF 12: |
| A)MEAN ROOF HEIGHT IS INCORRECT. SEE PLANS AND REVISE. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| B)SPECIFY THE SECOND FLOOR TRUSSES LIVE LOAD AS |
| REQUIRED BY TABLE R301.5 FBC-RESIDENTIAL. SPECIFY DEAD |
| LOADS ALSO. |
| C)SPECIFY ROOF TRUSSES DEAD AND LIVE LOADS. CLEARLY |
| SPECIFY TOP AND BOTTOM LOADS. INCLUDING THE ATTIC LIVE |
| LOAD AS REQUIRED BY TABLE R301.5 FBC-RESIDENTIAL. |
| |
| 4- SOIL TEST REPORT SUBMITTED: GEOTECHNICAL ENGINEER |
| RECOMMENDS THE BOTTOM OF THE FOUNDATION TO BE A MINIMUM |
| OF 18 INCHES BELOW THE LOWEST ADJACENT GRADE TO ASSURE |
| A SAFETY FACTOR AGAINST BEARING CAPACITY FAILURE. SEE |
| PAGE 4 OF SOIL TEST REPORT. ENGINEER OF RECORD TO |
| REVIEW SOIL TEST REPORT AND ACKNOWLEDGE IF GEOTECHNICAL |
| ENGINEER RECOMMENDATIONS WILL BE REQUIRED FOR THIS |
| PROJECT OR NOT. REVISE PLANS AS REQUIRED. |
| SEC. 107.2.1.2 CITY AMENDMENTS. |
| |
| 5- TYPICAL EXTERIOR WALL SECTION ON SHEET 9 OF 12. |
| CLEARLY SPECIFY SIZE AND SPACING OF ATTIC VENT. |
| SEC. R806 FBC-RESIDENTIAL. |
| |
| 6- PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR THE |
| SOFFIT CONSTRUCTION SHOWING COMPLIANCE WITH SEC. |
| R703.1.2.1 FBC-RESIDENTIAL. |
| |
| 7- ROOF SHEATHING NAILING SCHEDULE ON SHEET 10 OF 12: |
| A)CLARIFY WHY THE DESIGN PRESSURES FOR ZONE 2E AND 3E |
| ARE LOWER THAN THAN THE DESIGN PRESSURES FOR ZONE 2R? |
| SEC. 301.2.1 FBC-RESIDENTIAL. |
| |
| B)ACCORDING TO TABLE R301.2(2) FBC-RESIDENTIAL THE |
| DESIGN PRESSURES FOR ZONES 2E, 2R AND 3 ARE THE SAME. |
| CLARIFY WHY SHOWING DIFFERENT DESIGN PRESSURES FOR |
| THESE ZONES. |
| |
| C)REVISE ROOF SHEATHING FASTENING SPECIFICATIONS BASED |
| ON REVISED DESIGN PRESSURES ON ITEM #7(B) ABOVE. SEC. |
| 301.2.1 FBC-RESIDENTIAL. |
| |
| D)ACCORDING TO FIGURE R301.2(7) FBC-RESIDENTIAL, THERE |
| IS NOT ZONE #3E ON HIP ROOFS. REVISE AS REQUIRED. |
| |
| E)REVISE EDGE DIMENSION. ACCORDING TO FIGURE R301.2(7) |
| FBC-RESIDENTIAL, THE MIN. EDGE DIMENSION "A" IS 4'-0" |
| NOT 3'-0". SEE FOOTNOTE "A" ON FIGURE R301.2(7) AND |
| REVISE AS REQUIRED. |
| |
| 8-STAIR DETAILS ON SHEET 10 OF 12: |
| A)TREAD DIMENSION CAN NOT BE LESS THAN 10". SEE SEC. |
| R311.7.5.2 FBC-RESIDENTIAL AND REVISE AS REQUIRED. |
| NOTE: REVISE FLOOR PLANS ACCORDINGLY. |
| |
| B)RISER HEIGHT IS NOT CLEAR. STAIR DETAIL SAYS 7-3/4" |
| RISER TYP. , WHILE NOTE ADJACENT TO THE STAIR DETAIL |
| SAYS STAIR RISER=7.65. REVISE AS REQUIRED TO MATCH. |
| ALSO, NUMBER OF RISER SPECIFIED NEXT TO THE STAIR |
| DETAIL (18) DOESN'T MATCH NUMBER OF RISERS SHOWN ON |
| FLOOR PLANS. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 |
| CITY AMENDMENTS. |
| |
| 9-DOOR/WINDOW BUCK DETAIL ON SHEET 10 OF 12 SPECIFIES |
| 2"X4" BUCK FOR DOORS. REVISE THE SIZE OF THE STRUCTURAL |
| BUCK. STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO |
| THE DOOR FRAME AND NEED TO EXTEND BEYOND THE INTERIOR |
| FACE OF THE WINDOW OR DOOR FRAME AS REQUIRED BY SEC. |
| R609.7.2.1 FBC-RESIDENTIAL. 2X4 BUCK IS SMALLER THAN |
| THE DOOR FRAME. REVISE AS REQUIRED. |
| NOTE: BEVELED BUCKS ARE NOT ALLOWED EITHER. |
| |
| 10- ENERGY CALCULATIONS: |
| A)PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING OWNER'S AND BUILDER'S NAME. SEC. R101.5.1.1.2 |
| FBC-ENERGY CONSERVATION. |
| |
| B)PROVIDE CORRECT INFORMATION FOR ITEM #2. THE QUESTION |
| ON THIS ITEM IS SINGLE FAMILY OR MULTIPLE FAMILY?. |
| "DETACHED IS NOT THE ANSWER. REVISE AS REQUIRED. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| C)ROOF TYPE SPECIFIED ON PAGE 2 OF 5 IS INCORRECT. |
| THERE IS NOT GABLE OR SHED ROOF. SEE PLANS AND REVISE |
| AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| D)REVISE THE ATTIC VENT RATIO ON PAGE 2 OF 5. |
| TYPICALLY, THE RATIO IS 1/150 NOT 1/300. SEC. R806.2 |
| FBC-RESIDENTIAL. SEE PLANS AND REVISE AS REQUIRED. |
| |
| E)REVISE DOOR INFORMATION PAGE 3 OF 5. ONLY THE SIDE |
| DOOR IS INSULATED. SEE PLANS AND PRODUCT APPROVAL AND |
| REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY |
| CONSERVATION. |
| NOTE: GLAZING IN ENTRY DOOR NEEDS TO BE INCLUDED IN THE |
| WINDOW GLAZING AREA. SEE SEC. R405.5.3 FBC-ENERGY |
| CONSERVATION) |
| |
| F) BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE |
| LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY |
| CONSERVATION. |
| |
| 11-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| 61G20-3.001 FOR |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| |
| A)ENTRY DOOR WITH SIDELITES THAT MEETS THE DESIGN |
| PRESSURES CALCULATED BY THE ENGINEER OF RECORD. AND |
| PROVIDE COMPLETE PRODUCT APPROVAL, INCLUDING THE |
| FLORIDA PRODUCT APPROVAL COVER PAGE. |
| |
| B)SLIDING GLASS DOORS. PROVIDE COMPLETE PRODUCT |
| APPROVAL, INCLUDING THE FLORIDA PRODUCT APPROVAL COVER |
| PAGE. |
| |
| C) SINGLE HUNG WINDOWS. PROVIDE COMPLETE PRODUCT |
| APPROVAL, INCLUDING THE FLORIDA PRODUCT APPROVAL COVER |
| PAGE. |
| |
| D)METAL ROOF. AND, CLEARLY SPECIFY FASTENING METHOD. |
| |
| E)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE |
| TO AVOID DELAYS/CONFLICTS). |
| |
| F)ROOFING UNDERLAYMENT SPECIFIED ON PLANS FOR METAL |
| ROOFING. |
| |
| G)ALUMINUM SOFFIT AND ROOF VENTS SPECIFIED ON PLANS. |
| |
| H)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE |
| IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION |
| SCHEDULE. SEE CITY SAMPLE. |
| |
| 12- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |